Datasheet

2 | AUTOMATION.CROUZET.COM 06/2018 Logic Controller
XBP24 XBP24-E XDP24 XDP24-E
Storage temperature -40°C (-40 °F) → +80°C (176 °F)
Relative humidity 95% max. (no condensation or dripping water)
Screw terminals connection capacity Flexible wire with ferrule: 1 conductor: 0.2 to 2.5 mm2 (AWG 24-14)
Flexible wire with ferrule: 2 conductors: 0.2 to 0.75 mm2 (AWG 24-18)
Rigid wire: 1 conductor: 0.2 to 2.5 mm2 (AWG 24-14)
Rigid wire: 2 conductors: 0.2 to 0.75 mm2 (AWG 24-18)
Tightening torque: 0.5 N.m (4.5 lb-in) (tighten using screwdriver diam. 3.5 mm)
Stripping length: 6 mm
Material Lexan, UL94V0
Environnement Reach, RoHS, Halogen free 1272/2008/CE
On front panel color Grey RAL 7035
On sole color Black RAL 9011
Protection rating
(in accordance with IEC/EN 60529)
IP 40 on front panel
IP 20 on terminal block
Weight Without packing: 270 g
With packing: 320 g
Without packing: 300 g
With packing: 350 g
Without packing: 330 g
With packing: 380 g
Dimensions Without packing:
124.6 x 90 x 61.1 mm / 4.91 x 3.54 x 2.4 inch
With packing:
148 x 103 x 65 mm / 5.83 x 4.06 x 2.56 inch
Without packing:
124.6 x 90 x 62 mm / 4.91 x 3.54 x 2.44 inch
With packing:
148 x 103 x 65 mm / 5.83 x 4.06 x 2.56 inch
Processing characteristics
LCD display Without Display with 4 lines of 18 characters, yellow/
green
Programming method FBD (Function Block Diagram), including SFC (Sequential Function Chart) (Grafcet)
Program size Function blocks: typically 512 blocks
Macro blocks: 127 max. (255 blocks per macro)
Program memory Flash
Removable memory N.A
Data memory 2 k octets
Back-up time
(in the event of power failure)
Program and settings in the controller: 10 years
Data memory: 10 years
Data back-up Data backup in the ash memory is guaranteed if the product is powered on more than 10 seconds
Cycle time From 2 ms* to 90 ms, default value: 10 ms
*: Depending on conguration
Clock data retention 10 years (lithium battery) at 25°C (77°F)
Clock drift Drift < 12 min/year (at 25°C (77°F))
6 s / month (at 25°C (77°F) with user-denable correction of drift).
Synchronizable by network
Timer block accuracy 0.5 % ± 2 cycle time
Start up time on power up < 8 s base alone, < 5 s
base + 2 expansions +
1 accessory (RS485)
< 10 s base alone, < 5
s base + 2 expansions
+ 1 accessory (RS485)
< 8 s base alone, < 5 s
base + 2 expansions +
1 accessory (RS485)
< 10 s base alone, < 5
s base + 2 expansions
+ 1 accessory (RS485)
Self test Test rmware integrity (checksum memory)
Stability of the internal power supply
Check the conformity of the em4 device conguration with the conguration in the application
program.
Supply
Nominal voltage 24 VDC (-15% / +20%)
Operating limits 20.4 - 28.8 VDC
Immunity from micro power cuts ≤ 1 ms (repetition 20 times)
Max. absorbed power 3.8 W @ 24 VDC, 5 W
@ 28.8 VDC,
1.5 W @ 24 VDC I/O
OFF
4.8W @ 24 VDC, 6.2
W @ 28.8 VDC,
1.5W @ 24 VDC I/O
OFF
4W @ 24 VDC, 5.3 W
@ 28.8 VDC, - 0.3 W
backlight OFF
1.5W @ 24 VDC (I/O
+ backlight) OFF
5W @ 24 VDC, 6.5 W
@ 28.8 VDC, - 0.3 W
backlight OFF
1.5W @ 24 VDC (I/O
+ backlight) OFF