Datasheet
2 | AUTOMATION.CROUZET.COM 06/2018 Logic Controller
XBP24 XBP24-E XDP24 XDP24-E
Storage temperature -40°C (-40 °F) → +80°C (176 °F)
Relative humidity 95% max. (no condensation or dripping water)
Screw terminals connection capacity Flexible wire with ferrule: 1 conductor: 0.2 to 2.5 mm2 (AWG 24-14)
Flexible wire with ferrule: 2 conductors: 0.2 to 0.75 mm2 (AWG 24-18)
Rigid wire: 1 conductor: 0.2 to 2.5 mm2 (AWG 24-14)
Rigid wire: 2 conductors: 0.2 to 0.75 mm2 (AWG 24-18)
Tightening torque: 0.5 N.m (4.5 lb-in) (tighten using screwdriver diam. 3.5 mm)
Stripping length: 6 mm
Material Lexan, UL94V0
Environnement Reach, RoHS, Halogen free 1272/2008/CE
On front panel color Grey RAL 7035
On sole color Black RAL 9011
Protection rating
(in accordance with IEC/EN 60529)
IP 40 on front panel
IP 20 on terminal block
Weight Without packing: 270 g
With packing: 320 g
Without packing: 300 g
With packing: 350 g
Without packing: 330 g
With packing: 380 g
Dimensions Without packing:
124.6 x 90 x 61.1 mm / 4.91 x 3.54 x 2.4 inch
With packing:
148 x 103 x 65 mm / 5.83 x 4.06 x 2.56 inch
Without packing:
124.6 x 90 x 62 mm / 4.91 x 3.54 x 2.44 inch
With packing:
148 x 103 x 65 mm / 5.83 x 4.06 x 2.56 inch
Processing characteristics
LCD display Without Display with 4 lines of 18 characters, yellow/
green
Programming method FBD (Function Block Diagram), including SFC (Sequential Function Chart) (Grafcet)
Program size Function blocks: typically 512 blocks
Macro blocks: 127 max. (255 blocks per macro)
Program memory Flash
Removable memory N.A
Data memory 2 k octets
Back-up time
(in the event of power failure)
Program and settings in the controller: 10 years
Data memory: 10 years
Data back-up Data backup in the ash memory is guaranteed if the product is powered on more than 10 seconds
Cycle time From 2 ms* to 90 ms, default value: 10 ms
*: Depending on conguration
Clock data retention 10 years (lithium battery) at 25°C (77°F)
Clock drift Drift < 12 min/year (at 25°C (77°F))
6 s / month (at 25°C (77°F) with user-denable correction of drift).
Synchronizable by network
Timer block accuracy 0.5 % ± 2 cycle time
Start up time on power up < 8 s base alone, < 5 s
base + 2 expansions +
1 accessory (RS485)
< 10 s base alone, < 5
s base + 2 expansions
+ 1 accessory (RS485)
< 8 s base alone, < 5 s
base + 2 expansions +
1 accessory (RS485)
< 10 s base alone, < 5
s base + 2 expansions
+ 1 accessory (RS485)
Self test Test rmware integrity (checksum memory)
Stability of the internal power supply
Check the conformity of the em4 device conguration with the conguration in the application
program.
Supply
Nominal voltage 24 VDC (-15% / +20%)
Operating limits 20.4 - 28.8 VDC
Immunity from micro power cuts ≤ 1 ms (repetition 20 times)
Max. absorbed power 3.8 W @ 24 VDC, 5 W
@ 28.8 VDC,
1.5 W @ 24 VDC I/O
OFF
4.8W @ 24 VDC, 6.2
W @ 28.8 VDC,
1.5W @ 24 VDC I/O
OFF
4W @ 24 VDC, 5.3 W
@ 28.8 VDC, - 0.3 W
backlight OFF
1.5W @ 24 VDC (I/O
+ backlight) OFF
5W @ 24 VDC, 6.5 W
@ 28.8 VDC, - 0.3 W
backlight OFF
1.5W @ 24 VDC (I/O
+ backlight) OFF