Isolation between analog channel and power supply None
Protection against polarity inversions Yes
Potentiometer control 2.2 kΩ / 0.5 W (recommended), 10 KΩ max.
Cable length y 10 m with shielded twisted cable (sensor not isolated)
Digital 24 VDC and analog inputs 12 bits / 10 V & 11 bits / 0-20 mA- potentiometer - 4 inputs from ID to IG
Input used as digital input (power off state)
Input voltage 24 VDC (-15% / +20%)
Input current 1.5 mA @ 20.4 V
1.7 mA @ 24 V
2.1 mA @ 28.8 V
Input impedance 13.9 kΩ
Logic 1 voltage threshold u 11 VDC
Making current at logic state 1 u 0.8 mA
Logic 0 voltage threshold y 8 VDC
Release current at logic state 1 y 0.5 mA
Response time 1 to 2 cycle times
Sensor type Contact or 3-wire PNP
Conforming to IEC/EN 61131-2 Type 1
Input type Resistive
Isolation between power supply and inputs None
Isolation between inputs None
Protection against polarity inversions No
Status indicator On LCD screen
Cable length y 100 m
Input used as 0-10 V analog input
Measuring range
0 10 V
Input impedance 13.9 kΩ
Maximum value without destruction 28.8 VDC max
Input type Common mode
Resolution 12 bit / 10V
Value of LSB 2.45 mV
Conversion time Controller cycle time
Maximum error at 25°C (77°F) +/- 0.8 % of full scale
Maximum error at 55°C (131°F) +/- 1.2 % of full scale
Repeat accuracy at 55°C (131°F) +/- 0.5 %
Isolation between analog channel and power supply None
Protection against polarity inversions Yes for voltage y 10 V
Potentiometer control 2.2 kΩ / 0.5 W (recommended), 10 KΩ max.
Cable length y 10 m with shielded twisted cable (sensor not isolated)
Input used as 0-20 mA analog input
Measuring range
0 20 mA (4 20 mA by the application)
Input impedance 245 Ω
Maximum value without destruction 30 mA max
Input type Common mode
Resolution 11 bit (normalized at 0 - 2000) / 20 mA
Value of LSB 10 µA
Conversion time Controller cycle time
Maximum error at 25°C (77°F) +/- 1.2 % of full scale
Maximum error at 55°C (131°F) +/- 1.7 % of full scale
Repeat accuracy at 55°C (131°F) +/- 0.5 %
Isolation between analog channel and power supply None
Protection against polarity inversions Yes
Overvoltage protection
Yes If the input voltage is > 7 V, this one is automatically switched on 0-10V conguration.
Cable length y 30 m with shielded twisted cable (sensor not isolated)
Outputs
Digital / PWM solid state output - 2 solid state outputs from O1 to O2
Output used as digital output
Breaking voltage
10 28.8 VDC
Nominal voltage 12 / 24 VDC
Nominal current 0.5 A on resistive load @ 25°C (77°F)
Max. breaking current 0.625 A
Non repetitive overload current 1 A
Maximum breaking current in the common 1 A
Voltage drop < 1 V for I = 0.5 A
Response time Make = 1 cycle time + 30 µs typical
Release = 1 cycle time + 40 µs typical
Built-in protections Against overloads and short-circuits: Yes
Against over voltages (*): Yes
Against inversions of power supply: Yes
(*) In the absence of a potential free contact between the output of the programmable
logic controller and the load
Min. load 1 mA
Galvanic isolation No
Cable length y 10 m
Truth table of the default
Command Output Fault
Normal condition 0 0 No
1 1 No
Overheating 0 0 No
1 0 Yes
Underpowered 0 0 X
1 0 X
Short circuit (current limit) 0 0 No
1 0 Yes
Output used as PWM output
PWM frequency 14.11 Hz ; 56.45 Hz ; 112.90 Hz ; 225.80 Hz ; 451.59 Hz ; 1758.24 Hz
PWM cyclic ratio
0 100 % 100 steps
PWM Max. error
y 2 % (from 10 % 90 %)
Status indicator On LCD screen
Cable length y 10 m with shielded twisted cable
Distance between the power source and the static outputs y 30 m
6 A relay output - 2 outputs from O3 to O4
Breaking voltage 250 VAC max
Breaking current 6 A, Derating: UL: u 45°C (113°F): 4 A max
Maximum breaking current in the common IEC @ 25°C (77°F): 12 A
IEC @ 60°C (140°F) or UL: 10 A
Mechanical life 5 000 000 operations (cycles)
Electrical durability for 50 000 operating cycles 24 VDC tau = 0 ms: 6 A, tau = 7 ms: 3 A, tau = 15 ms: 1.8 A
Usage category DC-12: 24 V, 6 A
Usage category DC-14: 24 V, 1.8 A
250 VAC cos phi = 1: 6 A, cos phi = 0.7: 5 A, cos phi = 0.4: 2.5 A
Usage category AC-12: 250 V, 6 A
Usage category AC-13: 250 V, 5 A
Usage category AC-15: 250 V, 2 A
Minimum switching capacity 100 mA (at minimum voltage of 12V)
Maximum operating rate Off load: 10 Hz
At operating current: 0.1 Hz
Voltage for withstanding shocks In accordance with IEC/EN 60947-1 and IEC/EN 60664-1: 4 kV
Response time Make = 1 cycle time + 8 ms typical
Release = 1 cycle time + 4 ms typical
Built-in protections Against short-circuits: None
Against over voltages and overload: None
Status indicator On LCD screen
Cable length y 30 m