Data Sheet
11/2018
›
Logic Controller em4 expansion
EM4ED
Digital expansion E10R
› Up to two digital / analog expansions can be added to
the em4 nanoPLC to expand up to 46 I/Os
› Upto6digital/analogcongurableinputs(0-10Vc,
0-28.8Vc, Potentiometer) allowing the use of NTC tem-
perature sensors without using an additional converter
› 4relayoutputs(2x6A/250Va&2X8A/250Va
allowingcontrollingpoweractuators(valves,pumps...)
Digital expansion E10R
Speciccharacteristics
Part number 88982113
Finish Glossy Black
On front panel color Black RAL 9011
On terminal block color Blue RAL 5017
Protection rating (in accordance with IEC/EN 60529) IP 40 on front panel
IP 20 on terminal block
Weight Without packing: 130 g
With packing: 170 g
Dimensions Without packing: 60.4 x 90 x 60.6 mm / 2.37 x 3.54 x 2.38 inch
With packing: 93 x 103 x 65 mm / 3.66 x 4.06 x 2.56 inch
General characteristics
Products certication CE, cULus Listed
Conformity with the low voltage directive
(in accordance with BT 2006/95/EC)
IEC/EN 61131-2 (Open equipment)
Conformity with the EMC directive
(in accordance with 2004/108/EC)
IEC/EN 61000-6-1 (Residential, commercial and light-industrial environments)
IEC/EN 61000-6-2 (Industrial)
IEC/EN 61000-6-3 (Residential, commercial and light-industrial environments)
IEC/EN 61000-6-4 (Industrial)
Earthing None
Overvoltage category 3 in accordance with IEC/EN 60664-1
Pollution Degree: 2 in accordance with IEC/EN 61131-2
Maximum utilization altitude Operation: 2000 m
Transport: 3000 m
Mechanical resistance Immunity to vibrations IEC/EN 60068-2-6, Fc test
Immunity to shock IEC/EN 60068-2-27, Ea test
Resistance to electrostatic discharge Immunity to ESD IEC/EN 61000-4-2, level 3
Resistance to HF interference (Immunity) Immunity to radiated electrostatic elds IEC/EN 61000-4-3, level 3
Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3
Immunity to shock waves IEC/EN 61000-4-5
Radio frequency in common mode IEC/EN 61000-4-6, level 3
Conducted and radiated emissions
(in accordance with EN 55022/11 group 1)
Class B
Operation temperature -20 °C (-4 °F) → +60 °C (140 °F) (+40 °C (104 °F) in a non-ventilated
enclosure)
Storage temperature -40 °C (-40 °F) → +80 °C (176 °F)
Relative humidity 95% max. (no condensation or dripping water)