Data Sheet

11/2018
Logic Controller em4 expansion
EM4ED
Digital expansion E10R
Up to two digital / analog expansions can be added to
the em4 nanoPLC to expand up to 46 I/Os
Upto6digital/analogcongurableinputs(0-10Vc,
0-28.8Vc, Potentiometer) allowing the use of NTC tem-
perature sensors without using an additional converter
4relayoutputs(2x6A/250Va&2X8A/250Va
allowingcontrollingpoweractuators(valves,pumps...)
Digital expansion E10R
Speciccharacteristics
Part number 88982113
Finish Glossy Black
On front panel color Black RAL 9011
On terminal block color Blue RAL 5017
Protection rating (in accordance with IEC/EN 60529) IP 40 on front panel
IP 20 on terminal block
Weight Without packing: 130 g
With packing: 170 g
Dimensions Without packing: 60.4 x 90 x 60.6 mm / 2.37 x 3.54 x 2.38 inch
With packing: 93 x 103 x 65 mm / 3.66 x 4.06 x 2.56 inch
General characteristics
Products certication CE, cULus Listed
Conformity with the low voltage directive
(in accordance with BT 2006/95/EC)
IEC/EN 61131-2 (Open equipment)
Conformity with the EMC directive
(in accordance with 2004/108/EC)
IEC/EN 61000-6-1 (Residential, commercial and light-industrial environments)
IEC/EN 61000-6-2 (Industrial)
IEC/EN 61000-6-3 (Residential, commercial and light-industrial environments)
IEC/EN 61000-6-4 (Industrial)
Earthing None
Overvoltage category 3 in accordance with IEC/EN 60664-1
Pollution Degree: 2 in accordance with IEC/EN 61131-2
Maximum utilization altitude Operation: 2000 m
Transport: 3000 m
Mechanical resistance Immunity to vibrations IEC/EN 60068-2-6, Fc test
Immunity to shock IEC/EN 60068-2-27, Ea test
Resistance to electrostatic discharge Immunity to ESD IEC/EN 61000-4-2, level 3
Resistance to HF interference (Immunity) Immunity to radiated electrostatic elds IEC/EN 61000-4-3, level 3
Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3
Immunity to shock waves IEC/EN 61000-4-5
Radio frequency in common mode IEC/EN 61000-4-6, level 3
Conducted and radiated emissions
(in accordance with EN 55022/11 group 1)
Class B
Operation temperature -20 °C (-4 °F) → +60 °C (140 °F) (+40 °C (104 °F) in a non-ventilated
enclosure)
Storage temperature -40 °C (-40 °F) → +80 °C (176 °F)
Relative humidity 95% max. (no condensation or dripping water)