Data Sheet
3 | AUTOMATION.CROUZET.COM 11/2018 | Logic Controller em4 expansion
Mechanical life 5 000 000 operations (cycles)
Electrical durability for 50 000 operating cycles
24 Vc tau = 0 ms: 6 A, tau = 7 ms: 3 A, tau = 15 ms: 1.8 A
Usage category DC-12: 24 V, 6 A
Usage category DC-14: 24 V, 1.8 A
250 Va cos phi = 1: 6 A, cos phi = 0.7: 5 A, cos phi = 0.4: 2.5 A
Usage category AC-12: 250 V, 6 A
Usage category AC-13: 250 V, 5 A
Usage category AC-15: 250 V, 2 A
Minimum switching capacity 100 mA (at minimum voltage of 12V)
Maximum operating rate Off load: 10 Hz
At operating current: 0.1 Hz
Voltage for withstanding shocks In accordance with IEC/EN 60947-1 and IEC/EN 60664-1: 4 kV
Response time Make = 1 cycle time + 8 ms typical
Release = 1 cycle time + 4 ms typical
Built-in protections Against short-circuits: None
Against over voltages and overload: None
Status indicator On LCD screen
Cable length ≤ 30 m
8Arelayoutput-2outputsfromO3toO4
Breaking voltage
250 Va max
Breaking current 8 A, ≥ 55 °C: 6 A
Mechanical life 20 000 000 operations (cycles)
Electrical durability for 50 000 operating cycles
24 Vc tau = 0 ms: 8 A, tau = 7 ms: 3 A, tau = 15 ms: 1.5 A
Usage category DC-12: 24 V, 8 A
Usage category DC-14: 24 V, 1.5 A
250 Va cos phi = 1: 8 A, cos phi = 0.7: 4.75 A, cos phi = 0.4: 3 A
Usage category AC-12: 250 V, 8 A
Usage category AC-13: 250 V, 4.3 A
Usage category AC-15: 250 V, 1.5 A
Minimum switching capacity 100 mA (at minimum voltage of 12V)
Maximum operating rate Off load: 10 Hz
At operating current: 0.1 Hz
Voltage for withstanding shocks In accordance with IEC/EN 60947-1 and IEC/EN 60664-1: 4 kV
Response time Make = 1 cycle time + 10 ms typical
Release = 1 cycle time + 5 ms typical
Built-in protections Against short-circuits: None
Against over voltages and overload: None
Status indicator On LCD screen
Cable length ≤ 30 m