Datasheet

I Timers I 02 I www.crouzet-control.com
General characteristics
Insulation voltage, IEC 60664-1 300 V
Installation category (acc. to IEC/EN 60664-1) Overvoltage category III ; pollution degree 2
Impulse voltage CEI/EN 60664-1 4 kV (1,2 / 50 µs)
Clearance / Creepage distances IEC 60664-1: 3 mm / 3.2 mm
Breakdown voltage EN-61812-1: 2,5 kV / 1 min / 1 mA / 50 Hz
Insulation resistance NFC 93 050: > 500 MΩ / 250 V⎓ / 1min
Status indication Un: green LED blinks when count, continuous ON when supplied
R: yellow LED continuous ON when the relay is ON
Casing DIN 43880: 17,5 mm
Fixing: Symmetrical DIN rail EN 50022: 35 mm
Mounting position All positions
Housing material Enclosure plastic type UL94 - V0
Protection (IEC/EN 60529) Housing: IP40 / Terminal block: IP20
Terminal capacity Single-wire without ferrule IEC 60947-1
1 x 0.5 →3.3 mm² (AWG 20 →AWG 12)
2 x 0.5 →1.5 mm² (AWG 20 →AWG 16)
Max. tightening torque (Nm) IEC 60947-1
0,5 N.m / 4,4 lbf.in
Operating temperature range (°C) IEC 60068-2
-20 °C →+60 °C
Storage temperature range (°C) IEC 60068-2
-40 °C →+70 °C
Relative humidity no condensation acc. to IEC/EN 60068-2-30 93 % without condensation
Vibration resistance according to IEC/EN 60068-2-6 ± 0.15 mm from 10 Hz →60 Hz 2g from 60 Hz →150 Hz
Impact resistance IEC 60068-2-27
15gn - 11ms ; 3 x 6 axis (output OFF)
5gn - 11ms ; 3 x 6 axis (Output ON)
Drop to concrete floor IEC 60068-2-32: igh: 0.75m
Weight: casing 17,5 mm 70 g
80 g with packaging
Directives 2014/30/EU: EMC
2014/35/EU: low voltage
Certifications CE - cULus Listed Industrial Control Equipment - CCC
Conformity to standards CEI 60664-1: Insulation coordination for equipment within
low-voltage systems
CEI 61812-1/ Specified time relays for industrial use
UL 60947-4-1/ Industrial Control Equipment (NRNT- Industrial
Control Switches)
Conformity with environmental directives 2015/863/UE: RoHS
1907/2006: Reach
2012/19/UE: WEEE
Electromagnetic compatibility IEC 61000-6-2, IEC 61000-6-3,
IEC 61000-6-4
Immunity for industrial environment
Emission residential environment
Emission industrial environment
Electromagnetic compatibility - Immunity to electrostatic discharges
acc to IEC/EN 61000-4-2
Level III Air ± 8 KV / Contact ± 6 KV
Immunity to radiated, radio-frequency, electromagnetic field acc.
IEC/EN 61000-4-3
Level III
10 V/m (80 M Hz to 1 G Hz) 80 % AM (1 k Hz)
3 V/m (1,4 →2 G Hz) 80 % AM (1K Hz)
1V/m (2 →2.7 G Hz) 80 % AM (1K Hz)
Immunity to rapid transient bursts acc. to IEC/EN 61000-4-4 Level III direct ± 2 kV (power supply) / capacitive coupling clamp
± 1 KV (command input and outputs)
Immunity to shock waves on power supply acc. to IEC/EN 61000-4-5 Level III
line-to-earth ± 2 kV / line-to-line ± 1kV