Data Sheet

Multi-function or mono-function
Multi-range (12 function)
Multi-voltage 12 →240 V AC/DC
LED status indicator (relay version)
Possibility of external load connection in parallel to the
control input
3-wire PNP sensor compatible
Specifications
Functions Delay Output Nominal rating Connections Supply voltage Code
A-At 0,1 s →10 days 1 changeover relay 16 A Screw terminals 12 →240 V ∿/⎓ BA1R16MV1
Output relay
Contact arrangement 1 CO (SPDT) (Changeover -Single Pole Double Throw-)
Maximum switching voltage 250 VAC/ 16 A resistive / 250 VDC / 0.3 A resistive
Switching current rate (resistive) NO / NC: 16 A 250 V AC / 16 A 30 VDC @ 25°C
NO / NC: 8 A 250 V AC / 8 A 30 VDC @ 60°C
Minimum switching contact 10 mA / 5 VDC
Maximum switching power (resistive) 4000 VA / 90 W @ 25°C
Electrical life 30x10
3
cycles (NO) at 250 VAC/ 16 A resistive
Maximum rate (at max switching power) 360 cycles /hour
Mechanical life 30 x 10
6
cycles
Rated impulse voltage 5 kV (1.2/50µs)
Dielectric strength between coil / contacts IEC 60664-1: 5 kV /1 min / 1 mA / 50 Hz
Dielectric strength between open contacts 1 kV /1 min / 1 mA / 50 Hz
Timing
Timing ranges (7 ranges) 0.5→10s, 0.05→1min, 0.5→10min, 0.05→1h,
0.5→10h, 0.05→1day, 0.5→10days
Minimum pulse duration typically (relay version) IEC 1812-1: 30 ms / 100 ms with load
Maximum reset time by de-energisation typically (relay version) IEC 1812-1: 120 ms
Repeatability
IEC 1812-1: ≤ ± 0,5 %
Repetition accuracy with constant parameters IEC 1812-1: ≤ ± 10 %
Drift Temperature ≤ ± 0.05 % / °C
Voltage-dependent drift ≤ ± 0.2 % / V
Supply
Multi-voltage power supply 12→240 V∿/⎓
Operating range
15 %, +10 %
Operating frequency (Hz) 50 / 60 Hz ± 5 %
Galvanic isolation No
Max. absorbed power Approx. 3 VA (V∿) 1.5 W (V⎓)
Immunity from micro power cuts 10 ms
BA1R
Timers
Syrline
17.5 mm - 1 Relay 16A

Summary of content (4 pages)