Datasheet

40
Multi-function current control relay - 35 mm
Control of AC and DC currents
Automatic recognition of AC/DC
Measurement ranges from 2 mA to 10 A
Choice between over and undercurrent
True RMS measurement
Selectable latching (memory) function
HIL HIH
Functions Over or undercurrent Over or undercurrent
Measurement range 2 mA
500 mA 0.1 A 10 A
Nominal voltage (V)
24
240 V 24 240 V
Part numbers 84871120 84871130
Customisable colours and labels
Measuring ranges within the generic limits
Fixed threshold in the generic measurement range
Fixed or adjustable time delay
Adjustable hysteresis
Description Code
Removable sealable cover for 35 mm casing 84800001
HIL HIH
Inputs and measuring cicuit
Measurement range 2 500 mA
E1 - M: 2 20 mA
E2 - M: 10
100 mA
E3 - M: 50
500 mA
0.1
10 A
E1 - M: 0.1 1 A
E2 - M: 0.5
5 A
E3 - M: 1
10 A
Input resistance E1 - M: 5 Ω
E2 - M: 1 Ω
E3 - M: 0.2 Ω
E1 - M: 0.1 Ω
E2 - M: 0.02 Ω
E3 - M: 0.01 Ω
Permanent overload at 25°C E1 - M: 0.4 A
E2 - M: 1 A
E3 - M: 2 A
E1 - M: 2 A
E2 - M: 11 A
E3 - M: 11 A
Pulse overload < 1 sec at 25°C E1 - M: 1 A
E2 - M: 5 A
E3 - M: 8 A
E1 - M: 17 A
E2 - M: 20 A
E3 - M: 50 A
Current control
HIL
HIH
Part numbers
Product adaptations
Accessories
General characteristics