Data Sheet

23
Sandwich communication extensions
*Also see Millenium 3 Smart and Essential General characteristics
Standard Modbus RS485 or TCP/IP protocol
Connects one or several Millenium 3 to a touch screen,
a supervision PC or a network gateway
Exchange of the input/output state and/or of internal
values
Updating date and time of a group of Millenium 3
Power supply via the controller
XN06
XN05
Type Description Supply Code
XN06 Modbus RS-485 (slave) communication extension
Via the 24 V
c
controller
88972250
XN05 Ethernet protocol TCP/IP Modbus extension (Server)
Via the 24 V
c
controller
88970270
Specific characteristics*
88972250 88970270
Certifications UL, CSA UL, CSA
Earthing Yes, refer to the quick reference guide
supplied with the product
Yes, refer to the quick reference guide
supplied with the product
Operating temperature -20 +55 °C (+40 °C in a non-ventilated
enclosure) in accordance with IEC/EN
60068-2-1 and IEC/EN 60068-2-2
0 +55 °C (+40 °C in a non-ventilated
enclosure) in accordance with IEC/EN
60068-2-1 and IEC/EN 60068-2-2
Cable length Maximum length of the network: 1000 m
(9600 Baud maxi, AWG 26)
Maximum length between 2 controllers:
100 m
Communication parameters
88972250 88970270
Type of link 2 or 4-wire; RTU or ASCII -
Transmission rate (Bauds) 1200, 2400, 4800, 9600, 19200, 28800,
38400, 57600
-
Parity None; even; odd -
Addressing 1 247 Static or dynamic (BootP server)
Characteristics of exchanges
88972250 88970270
Ladder programming
Image of smart relay I/O 4 -
Status 1 -
Function blocks programming
Read-words 8 8
Read/Write 8 8
Clock words 12 4
"Status" words 1 1
XN05 - XN06
Millenium 3 Smart and Essential
Part numbers
Dimensions (mm)
10
57,5
67,5
52,5
44
15
25
90
35 27,5 27,5
108
35
100
112-UK_Millenium 3 Essential_Sandwich communication extensions_5955.fm Page 23 Jeudi, 5. décembre 2013 12:27 12