Data Sheet
39
➜ General characteristics
■ Millenium 3 compact range
■ Millenium 3 expandable range
Certifications CE, UL, CSA, GL
Conformity to standards (with the low voltage directive and
EMC directive)
IEC/EN 61131-2 (Open equipment)
IEC/EN 61131-2 (Zone B)
IEC/EN 61000-6-2
IEC/EN 61000-6-3 (*)
IEC/EN 61000-6-4
(*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270) +
88 970 241 class A (class B in a metal enclosure)
Earthing Not included
Protection rating
In accordance with IEC/EN 60529:
IP40 on front panel
IP20 on terminal block
Overvoltage category 3 in accordance with IEC/EN 60664-1
Pollution Degree: 2 in accordance with IEC/EN 61131-2
Max operating Altitude Operation: 2000 m
Transport: 3048 m
Mechanical resistance Immunity to vibrations IEC/EN 60068-2-6, test Fc
Immunity to shock IEC/EN 60068-2-27, test Ea
Resistance to electrostatic discharge Immunity to ESD
IEC/EN 61000-4-2, level 3
Resistance to HF interference
Immunity to radiated electrostatic fields
IEC/EN 61000-4-3
Immunity to fast transients (burst immunity)
IEC/EN 61000-4-4, level 3
Immunity to shock waves
IEC/EN 61000-4-5
Radio frequency in common mode
IEC/EN 61000-4-6, level 3
Voltage dips and breaks (a)
IEC/EN 61000-4-11
Immunity to damped oscillatory waves
IEC/EN 61000-4-12
Conducted and radiated emissions
Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1
(*) Except configuration (88 970 1.1 or 88 970 1.2) + (88 970 250 or 88 970 270)
+ 88 970 241 class A (class B in a metal enclosure)
Operating temperature Millenium 3 Essential and extensions -20 ➞ +55 °C (+40 °C in a non-ventilated enclosure) in
accordance with IEC/EN 60068-2-1 and IEC/EN 60068-2-2
Operating temperature Millenium 3 Smart
-20 ➞ +70 °C except CB and XB versions in V
c
: -30 ➞ +70 °C (+40 °C in a non-
ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-2-2
Storage temperature Millenium 3 Essential and extensions -40 ➞ +70 °C in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-2-2
Storage temperature Millenium 3 Smart -40 ➞ +80 °C in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-2-2
Relative humidity 95 % max. (no condensation or dripping water) in accordance with
IEC/EN 60068-2-30
Mounting
On symmetrical DIN rail, 35 x 7.5 mm and 35 x 15 mm, or on panel (2 x Ø 4 mm)
Screw terminals connection capacity Flexible wire with ferrule =
1 conductor: 0.25 to 2.5 mm
2
(AWG 24 ➞ AWG 14)
2 conductors 0.25 to 0.75 mm
2
(AWG 24 ➞ AWG 18)
Semi-rigid wire =
1 conductor: 0.2 to 2.5 mm
2
(AWG 25 ➞ AWG 14)
Rigid wire =
1 conductor: 0.2 to 2.5 mm
2
(AWG 25 ➞ AWG 14)
2 conductors 0.2 to 1.5 mm
2
(AWG 25 ➞ AWG 16)
Tightening torque =
0.5 N.m (4.5 lb-in) (tighten using screwdriver diam. 3.5 mm)
Millenium 3 Smart and Essential
General environment characteristics for CB, CD, XD, XB, XR and XE product types
123-UK_lpr_Millenium 3 Smart_3718.fm Page 39 Jeudi, 5. décembre 2013 2:18 14