Program size function blocks (FBD) 350 typical blocks
64 macros maximum
256 blocks maximum per macro
180 typical blocks
64 macros maximum
256 blocks maximum per macro
Memory size function blocks (FBD) 8 K 4 K
Number of lines in Ladder 120 lines 120 lines
LCD display CD, XD: Display with 4 lines of 18 characters
Programming method Function blocks / SCF (Grafcet) or Ladder
Program memory Flash EEPROM
Removable memory EEPROM
Data memory 368 bit/200 words
Back-up time in the event of power failure Program and settings in the controller: 10 years
Program and settings in the plug-in memory: 10 years
Data memory: 10 years
Cycle time FBD: 6
➞ 90 ms (typically 20 ms)
Ladder: typically 20 ms
Response time Input acquisition time: + 1 to 2 cycle times
Clock data retention 10 years (lithium battery) at 25 °C
Clock drift Drift < 12 min/year (at 25 °C)
6 s/month (at 25 °C with user-definable correction of drift)
Timer block accuracy 1 % ± 2 cycle times
Start up time on power up < 1.2 s
Supply
24 V
a
100 ➞ 240 V
a
Nominal voltage
24 V
a
100 ➞ 240 V
a
Operating limits -15 % / +20 %
or 20.4 V
a
➞ 28.8 V
a
-15 % / +10 %
or 85 V
a
➞ 264 V
a
Supply frequency range 50/60 Hz (+4 % / -6 %) or
47➞ 53 Hz / 57 ➞ 63 Hz
50/60 Hz (+4 % / -6 %) or
47 ➞ 53 Hz / 57 ➞ 63 Hz
Immunity from micro power cuts 10 ms (repetition 20 times) 10 ms (repetition 20 times)
Max. absorbed power CB12-CD12-XD10-XB10: 4 VA
CB20-CD20: 6 VA
XD10-XB10 with extension: 7.5 VA
XD26-XB26: 7.5 VA
XD26-XB26 with extension: 10 VA
CB12-CD12-XD10-XB10: 7 VA
CB20-CD20: 11 VA
XD10-XB10 with extension: 12 VA
XD26-XB26: 12 VA
XD26-XB26 with extension: 17 VA
Isolation voltage
1780 V
a
1780 V
a
Inputs
24 V
a
100 ➞ 240 V
a
Input voltage
24 V
a
(-15 % / +20 %) 100 ➞ 240 V
a
(-15 % / +10 %)
Input current
4.4 mA @ 20.4 V
a
5.2 mA @ 24.0 V
a
6.3 mA @ 28.8 V
a
0.24 mA @ 85 V
a
0.75 mA @ 264 V
a
Input impedance 4.6 k 350 k
Logic 1 voltage threshold
14 V
a
79 V
a
Making current at logic state 1 > 2 mA > 0.17 mA
Logic 0 voltage threshold
5 V
a
20 V
a
( 28 V
a
: XE10, XR06,
XR10, XR14)
Release current at logic state 0 < 0.5 mA < 0.5 mA
Response time with function blocks programming Configurable in increments of 10 ms
50 ms min. up to 255 ms
State 0 ➞ 1 (50/60 Hz)
Configurable in increments of 10 ms
50 ms min. up to 255 ms
State 0 ➞ 1 (50/60 Hz)
Response time with Ladder programming 50 ms
State 0 ➞ 1 (50/60 Hz)
50 ms
State 0 ➞ 1 (50/60 Hz)
Maximum counting frequency In accordance with cycle time (Tc) and
input response time (Tr):
1/ ( (2 x Tc) + Tr)
In accordance with cycle time (Tc) and
input response time (Tr):
1 / ( (2 x Tc) + Tr)
Sensor type Contact or 3-wire PNP Contact or 3-wire PNP
Input type Resistive Resistive
Isolation between power supply and inputs None None
Isolation between inputs None None
Protection against polarity inversions Yes Yes
Status indicator On LCD screen for CD and XD On LCD screen for CD and XD
Processing characteristics of CB, CD, XD & XB product types
Characteristics of products with AC power supplied