Data Sheet

42
Analog or digital inputs (IB to IG)
12 V
c
24 V
c
CB12-CD12-XD10-XB10 4 inputs IB IE 4 inputs IB IE
CB20-CD20-XB26-XD26 6 inputs IB
IG 6 inputs IB IG
Inputs used as analog inputs only in FBD
Measurement range (0 10 V) or (0 V power supply) (0 10 V) ou (0 V power supply)
Input impedance 14 k 12 k
Input voltage
14.4 V
c
max. 30 V
c
max.
Value of LSB 14 mV 29 mV
Input type Common mode Common mode
Resolution 10 bit at max. input voltage 10 bit at max. input voltage
Conversion time Controller cycle time Controller cycle time
Accuracy at 25 °C ± 5 % ± 5 %
Accuracy at 55 °C ± 6.2 % ± 6.2 %
Repeat accuracy at 55 °C ± 2 % ± 2 %
Isolation between analog channel and power supply None None
Cable length 10 m maximum, with shielded cable
(sensor not isolated)
10 m maximum, with shielded cable
(sensor not isolated)
Protection against polarity inversions Yes Yes
Potentiometer control 2.2 k / 0.5 W (recommended)
10 k max.
2.2 k / 0.5 W (recommended)
10 k max.
Inputs used as digital inputs
Input voltage
12 V
c
(-13 % / +20 %) 24 V
c
(-20 % / +25 %)
Input current
0.7 mA @ 10.44 V
c
0.9 mA @ 12.0 V
c
1.0 mA @ 14.4 V
c
1.6 mA @ 19.2 V
c
2.0 mA @ 24.0 V
c
2.5 mA @ 30.0 V
c
Input impedance 14 k 12 k
Logic 1 voltage threshold
7 V
c
15 V
c
Making current at logic state 1 0.5 mA 1.2 mA
Logic 0 voltage threshold
3 V
c
5 V
c
Release current at logic state 0 0.2 mA 0.5 mA
Response time 1 2 cycle times 1 2 cycle times
Maximum counting frequency in FBD In accordance with cycle time (Tc)
and input response time (Tr):
1/ ( (2 x Tc) + Tr)
In accordance with cycle time (Tc)
and input response time (Tr):
1/ ( (2 x Tc) + Tr)
Sensor type Contact or 3-wire PNP Contact or 3-wire PNP
Conforming to IEC/EN 61131-2 Type 1 Type 1
Input type Resistive Resistive
Isolation between power supply and inputs None None
Isolation between inputs None None
Protection against polarity inversions Yes Yes
Status indicator On LCD screen for CD and XD On LCD screen for CD and XD
Characteristics of relay outputs common to the entire range
Max. breaking voltage
5 30 V
c
24 250 V
a
Max. Output Common Current 12 A (10 A UL) for O8, O9, OA
Breaking current CB-CD-XD10-XB10-XR06-XR10: 8 A
XD26-XB26: 8 x 8 A relay, 2 x 5 A relay
XE10: 4 x 5 A relay
XR14: 4 x 8 A relay, 2 x 5 A relay
Electrical durability for 500 000 operating cycles Utilization category DC-12: 24 V, 1.5 A
Utilization category DC-13: 24 V (L/R = 10 ms), 0.6 A
Utilization category AC-12: 230 V, 1.5 A
Utilization category AC-15: 230 V, 0.9 A
Minimum switching capacity 10 mA (at minimum voltage of 12 V)
Minimum load 12 V, 10 mA
Maximum rate Off load: 10 Hz
At operating current: 0.1 Hz
Mechanical life 10.000.000 (operations)
Voltage for withstanding shocks In accordance with IEC/EN 60947-1 and IEC/EN 60664-1: 4 kV
Off-cycle response time Make 10 ms
Release 5 ms
Built-in protections Against short-circuits: None
Against overvoltages and overloads: None
Status indicator On LCD screen for CD and XD