Data Sheet

57
NTC probes
Direct connection with no converter on
analog input
Easy-to-use and low-cost temperature
control solution
Fields of application: HVAC, compressors,
geothermal systems, swimming pools,
fountains
Analog input configured as a potentiometer
via the NTC functions in the M3 Soft
(minimum AC5)
NTC PVC probe NTC probe NTC stainless probe
POM probe Silicone probe
Type Description Ohmic value Measurement range Code
PVC
NTC2 probe PVC for Millenium 3 (24 V
c
, ± 10 %)
10 k @ 25 °C -25 +85 °C 89750174
AS
NTC1 probe (batch of 10) for Millenium 3 (24 V
c
, ± 10 %)
10 k @ 25 °C -25 +85 °C 89750180
Stainless
NTC2 probe stainless 305 for Millenium 3 (24 V
c
, ± 10 %)
10 k @ 25 °C -35 +120 °C 89750182
POM
NTC2 probe silicone for Millenium 3 (24 V
c
, ± 10 %)
MOQ 25 pcs
10 k @ 25 °C -20 +105 °C 89750185
Silicone
NTC3 probe silicone for Millenium 3 (24 V
c
, ± 10 %)
100 k @ 25 °C
0 +180
°C
89750186
Accessories Operating temperature Operating pressure Code
316 stainless steel protective sleeve -20 +400 °C 16 bar 89750147
General characteristics 89750174 89750180 89750182 89750185 89750186
Precision
(Repetability)
Precision
(Repetability)
Precision
(Repetability)
Precision
(Repetability)
Precision
(Repetability)
Environmental characteristics
-35 +40 °C ± 0.8 °C
( ± 0.5 °C)
-25 +40 °C ± 0.8 °C
( ± 0.5 °C)
± 0.8 °C
( ± 0.5 °C)
-20 +40 °C ± 0.8 °C
( ± 0.5 °C)
0 +40 °C ± 3 °C
( ± 1 °C)
+40 +50 °C ± 1.2 °C
( ± 1 °C)
+40 +70 °C ± 2 °C
( ± 1 °C)
± 2 °C
( ± 1 °C)
± 2 °C
( ± 1 °C)
+40 +140 °C ± 2 °C
( ± 1 °C)
+50 +60 °C ± 1.4 °C
( ± 1.4 °C)
+60 +70 °C ± 2 °C
( ± 2 °C)
+70 +85 °C ± 3 °C
( ± 2 °C)
± 3 °C
( ± 2 °C)
+70 +105 °C ± 3 °C
( ± 2 °C)
+70 +120 °C ± 3 °C
( ± 2 °C)
+140 +180 °C ± 3 °C
( ± 1 °C)
Millenium 3 accessories
Part numbers
Accessories
141-UK_Millenium 3 accessories_NTC probe_7531.fm Page 57 Jeudi, 5. décembre 2013 3:36 15