Datasheet

Multi
-
function phase control relay
-
17.5 mm MWU Part number 84873023
Control of 3-phase networks: phase sequence, phase failure, imbalance (asymmetry), over and undervoltage
Range includes mono-function product and multi-function product
Multi
-voltage from 3 x 208 to 3 x 480 V AC
Controls its own supply voltage
True RMS measurement
LED status indication
Type
Functions
Nominal voltage (V)
84873022
MWG
Phase sequence and failure
3x208→3x480VAC
84873023
MWU
Phase sequence, failure, undervoltage
3x208→3x480VAC
84873024
MWA
Phase sequence, failure and imbalance
3x208→3x480VAC
84873025
MWUA
Phase sequence, failure, imbalance, under and overvoltage in window mode
3x208→3x480VAC
Supply
3x208→3x480VAC*
-12% / +10%
183→528VAC
50 / 60 Hz
±
10%
No
1.8 VA in AC
10 ms
Inputs and measuring circuit
183→528VAC
208 - 220 - 380 - 400 - 415 - 440 - 480 V
50→60Hz
±
10%
150 ms/True RMS measurement
2→20%ofselectedUn
(-2 to -12% across the 3 x 208 V AC range / -2 to -17% across the 3 x 220 V AC range / 2 to 10% across the 3 x 480 V AC range)
2% of fixed Un
2% of fixed Un
5 to 15% of selected Un
±
3% of the displayed value
±
0,5%
< 1% across the whole range
< 0,05%/ °C
70%
Timing
0.1 to 10 s 0 +10%
±
3%
1500 ms
500 ms
< 200 ms
Output
1 single pole changeover relay
No cadmium
250 V AC/DC
5 A
AC/DC
10 mA / 5 V DC
1 x 10
5
1250 VA AC
360 operations/hour at full load
AC 12, AC 13, AC 14, AC 15, DC 12, DC 13, DC 14
30 x 10
6
Insulation
400 V
Overvoltage category III: degree of pollution 3
4 KV (1,2 / 50
μ
s)
2 kV AC 50 Hz 1 min
> 500 M
Ω
/
500 V DC
General characteristics
Green LED
Yellow LED - This LED flashes during the threshold delay
17,5 mm
On 35 mm symmetrical DIN rail, IEC/EN 60715
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
13/03/2012 www.crouzet.com

Summary of content (3 pages)