Datasheet

35 mm
-
2 Relays 8A PU2R3 Part number 88867303
Multi
-function or mono-function
Multi
-range
Multi
-voltage
Relay output 1 or 2 : 8 A - 250 V (10 A UL)
LED status indicator
Option of connecting an external power supply to the control input
3-wire sensor control option
Part numbers
Specifications
Type
Functions
Timing
Output
Connections
Supply voltage
88 867 303
PU2R3
A - At -
B
-
C
-
Ht
-
Di
-
D
- Ac - Bw
0,1s→100h
2 timed changeover relays
11-
pin
12→240VAC/DC
Timing
Timing ranges (7 ranges)
1 s - 10 s -
1 min
-
10 min
- 1 h - 10 h - 100 h
TK2R1 : 0.6s
- 2.5s - 20s - 160 s
Repetition accuracy with constant parameters
±
0.5 % (IEC/EN 1812
-1)
Drift Temperature
±
0,05 % / °C
Drift Voltage
±
0.2 % / V
Display accuracy according to IEC/EN 61812
-1
±
10 % / 25 °C
Minimum pulse duration typically (relay version)
30 ms
Minimum pulse duration typically (solid state version)
50 ms
Minimum pulse duration typically (relay version under
load)
100 ms
Maximum reset time by de
-energisation typically (relay
version)
100 ms
Maximum reset time by de
-energisation typically (solid
state version)
350 ms
Immunity from micro power cuts : typical
> 10 ms
Supply
*** TRADUCTION MANQUANTE ***
Multi
-voltage power supply
Depending on version
Frequency (Hz)
50 / 60
Operating range
85 to 110 % Un
(85 to 120 % Un for 12V AC/DC)
Operating factor
100 %
Max. absorbed power
0,6 W 24 V AC/DC
1,5 W 230 V AC
32 VA 230 V AC
Output specification
1 or 2 changeover relays, AgNi (cadmium-free)
2000 VA/80 W
Rated power
2000 VA/80 W
Maximum breaking current
8 A AC 8A DC
Minimum breaking current
10 mA / 5 V DC
Voltage breaking capacity
250 V AC/ DC
Electrical life (operations)
10
5
operations 8 A 250 V resistive
Mechanical life (operations)
5x10
6
Breakdown voltage acc. to IEC/EN 61812
-1
2.5 kV /1 min / 1 mA / 50 Hz
Impulse voltage acc. to IEC/EN 60664
-
1, IEC/EN 61812
-1
5 kV, wave 1.2 / 50
μ
s
Solid state output
Rated power
0,7 A AC/DC
20 °C (0,5 A UL)
Derating
5 mA / °C
Maximum admissible current
20A≤10ms
Minimum breaking current
10 mA
Leakage current
< 5 mA
Voltage breaking capacity
250 V AC/ DC
Maximum voltage drop at terminals
3 wire 4V - 2 wire 8V
Electrical life (operations)
10
8
Mechanical life (operations)
10
8
Breakdown voltage acc. to
IEC/EN 60664
-
1, IEC/EN
60255-5
2.5 kV to 1 mA / 1 min
Input type
Volt-free contact
3-wire PNP output control option residual voltage : 0.4V whatever the timer power supply
General characteristics
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
04/12/2014 www.crouzet.com

Summary of content (6 pages)