Crown Aruba 5 Installation Manual

40
TABLE 13.1 - FAULTS WITHOUT ERROR CODE PRESENT
Displayed
Codes Problem Possible Cause
StA 1
tt OFF
dh OFF
Burners and
Circulator O
Thermostat/s not calling for heat
Loose connection in thermostat, zone valve end switch, or zone panel wiring.
Thermostat, zone valve, or zone panel miswired
Defective thermostat, zone valve, or zone panel
StA 1
tt On
Burners O
Circulator On
Boiler Warm
Boiler o on high limit (normal operation)
Boiler o on thermal purge (normal operation - See Table 11.6)
tt On
Heating Circulator
O
Heating Circulator is being forced o on DHW priority (normal operation if Pt=ON - see
Table 11.7).
See causes for “DHW Circulator o “ below
dh On
DHW Circulator O
Loose connection in circulator wiring
Defective circulator
Circulator is running, but system problem is preventing circulation
StA 15
Burners O and
Damper is closed.
Green LWCO light
is on. Yellow light
is o.
External limit connected to Option Plug is open.
No option is connected at Option Plug and jumper plug (PN 9601830 ) is missing.
Blocked vent switch (BVS) open due to problem with vent system, such as a blocked
chimney, or a combustion air supply problem. Correct and press reset button on BVS.
Flame roll-out switch (FRS) open due to blocked heat exchanger. Correct problem and
replace FRS with exact replacement (see parts list)
StA 15
Burners O and
Damper Closed.
Both Green and
Yellow lights are on.
Low water condition exists in boiler. Verify that boiler and heating system are completely
lled with water.
Temperature probe is not inserted into well.
StA 6
No spark at pilot
Loose connection in ignition cable or pilot ground
Damaged electrode porcelain or ignition wire insulation (replace pilot)
Pilot electrode or Ground strap damaged (replace pilot)
If you cannot hear spark at all , replace control
StA 6
Spark, but no pilot
ame
Low inlet gas pressure
Plugged, kinked, or leaking pilot tubing
Plugged pilot orice
Gas line not purged of air
Defective pilot assembly
Defective gas valve (before replacing, conrm that there is 24VAC between PV and MV/
PV. If there is not, control harness is loose or the control itself is defective).
Loose connection in harness between control and gas valve.
StA 6
Pilot ame present,
but spark does not
shut o
Low inlet gas pressure
Partially plugged, kinked, or leaking pilot tubing
Partially plugged pilot orice
Loose connection in ignition cable or pilot ground
Damaged electrode porcelain or ignition wire insulation (replace pilot)
Pilot electrode or Ground strap damaged (replace pilot)
Defective Control
STA 8
Pilot ame present,
spark o, but Main
Burner does not light
at all
Loose connection in harness between control and gas valve
Defective gas valve (before replacing, conrm that there is 24VAC between MV and MV/
PV. If there is not either there is a loose connection in the control harness or the control
itself is defective).
StA 10
Main burner
lights, but shuts o
immediately
Low inlet gas pressure
Partially plugged, kinked, or leaking pilot tubing
Partially plugged pilot orice
StA 10
or StA 13
No spark or pilot
Pilot was either never established or proof of pilot was lost after it was lit. Cycle power to
the boiler and look for symptoms above.