14) VentdamperinstallationismandatoryonallsizesfromtheBSI069toBSI276.TheBSI311throughBSI380maybe
orderedwithorwithoutventdamper.Ifsupplied,installventdamper(seeFigure9)asfollows:
a) Openventdampercartonandremoveinstallationinstructions.Readtheinstructionsthoroughlybeforeproceeding.
Verifythatventdamperissamesizeasdraftdiverteroutlet.SeeFigure1.Unpackventdampercarefully.Do not
force closed damper blade. Forcingventdamperclosedmayresultindamagedgeartrainandvoidwarranty.
b) Ventdamperisfactoryshippedhavingapproximately¾”diameterholeintheventdamperblade,whichmust
be left openforboilersequippedwithstandingpilot,andshouldbepluggedonboilerswithanintermittentpilot
system,usingtheplugsuppliedwiththedamper.
Mounttheventdamperontheuecollarwithoutmodicationtoeitherandsecurewithsheetmetalscrews.Make
surescrewsdonotinterferewithdamperbladeoperation.Ventdamperbladepositionindicatormustbevisibleto
users.
c) Thedamperwireharnessisshippedwiredintotheboilerjunctionbox.Plugthelooseendofthisharnessintothe
damperandsecuretheexibleconduittothedamperusingaconnectornutprovided.
d) Installventconnectorpipeandventttingsfromventdamperoutlettochimneyorgasvent.Securewithsheetmetal
screwsandsupportasrequired.
Removing an Existing Boiler from a Common Chimney
Insomecases,whenanexistingboilerisremovedfromacommonchimney,thecommonventingsystemmaybetoolarge
fortheremainingappliances.Atthetimeofremovalofanexistingboilerthefollowingstepsshallbefollowedwitheach
applianceremainingconnectedtothecommonventingsystemplacedinoperation,whiletheotherappliancesremaining
connectedtothecommonventingsystemarenotinoperation.
a) Sealanyunusedopeninginthecommonventingsystem.
b) Visuallyinspecttheventingsystemforpropersizeandhorizontalpitchanddeterminethereisnoblockageor
restriction,leakage,corrosionandotherdeciencieswhichcouldcauseanunsafecondition.
c) Insofaraspractical,closeallbuildingdoorsandwindowsandalldoorsbetweenthespaceinwhichalltheappliances
remainingconnectedtothecommonventingsystemarelocatedandotherspacesofthebuilding.Turnonclothes
dryersandanyappliancenotconnectedtothecommonventingsystem.Turnonanyexhaustfans,suchasrange
hoodsandbathroomexhausts,sotheywilloperateatmaximumspeed.Donotoperateasummerexhaustfan.Close
replacedampers.
d) Placeinoperationtheappliancebeinginspected.Followthelightinginstructions.Adjustthermostatsotheappliance
willoperatecontinuously.
e) Testforspillageatthedrafthoodreliefopeningafterve(5)minutesofmainburneroperation.Usetheameofa
matchorcandle,orsmokefromacigarette,cigar,orpipe.
f) Afterithasbeendeterminedthateachapplianceremainingconnectedtothecommonventingsystemproperlyvents
whentestedasoutlinedabove,returndoors,windows,exhaustfans,replacedampersandanyothergas-burning
appliancestotheirpreviousconditionofuse.
g) Anyimproperoperationofthecommonventingsystemshouldbecorrectedsotheinstallationconformswiththe
NationalFuelGasCode,ANSIZ223.1.Whenresizinganyportionofthecommonventingsystem,thecommon
ventingsystemshouldberesizedtoapproachtheminimumsizeasdeterminedusingtheappropriatetablesinthe
NationalFuelGasCode,ANSIZ223.1.