Crown Bermuda Installation Manual

12
12
FIGURE10:GASCONNECTIONTOBOILER
*StateofMassachusettsRequiresManual
Shut-offValvetobe“T”HandleType
VII Gas Piping
Gaspipingtotheboilermustbesizedtodeliveradequategasfortheboilertoreatthenameplateinputataline
pressurebetweentheminimumandmaximumvaluesshownontheratingplate.Formoreinformationongaslinesizing,
consulttheutilityorChapter2oftheNational Fuel Gas Code.
Figure10showstypicalgaspipingconnectiontotheBSIboiler.Asedimenttrapmustbeinstalledupstreamofallgas
controls.Installamanualshut-offvalveoutsidethejacketandgroundjointunionasshown.
Theboileranditsgasconnectionmustbeleaktestedbeforeplacingtheboilerinoperation.Whendoingthis,theboilerand
itsindividualshut-offmustbedisconnectedfromtherestofthesystemduringanypressuretestingofthatsystematpressures
inexcessof1/2psi.Whenpressuretestingthegassystematpressuresof1/2psiorless,isolatetheboilerfromthegassupply
systembyclosingitsindividualmanualshut-offvalve.
*