Feeder Wiring for Boilers Equipped with McDonnell & Miller #67 Low Water Cut-offs
Figures14aand14bshowfeederwiringforMcDonnell&Miller#101A,McDonnell&MillerWF2-U-24andHydrolevel
VXT-24feedersonboilersequippedwith#67lowwatercutoffs.Thefollowingpointsapplytoallfeederwiringto#67low
watercut-offs:
Useaseparatetransformertopowerthefeeder.Donotusethetransformerontheboiler.
Itisnotnecessarytotouchanyofthe24voltfactoryboilerwiringwhenconnectingafeedertoa#67equipped
boiler.
Do NOTinstallajumperbetweenterminals2and3onthe#67lowwatercutoff.
Indirect Water Heater Wiring
Figure15showseldwiringforanindirectwaterheater.AHoneywellR845AorequivalentDPSTrelayandtransformer
isrequired.ThehighlimitdescribedinPartIXmustalsobesuppliedbytheinstaller.Acallforheatfromtheindirectwater
heaterthermostatwillenergizetherelaymakingbothsetsofcontacts.Onesetofthesecontactsthenenergizesthecirculator.
Theothersetofcontactswillmakethe“T”and“T”contactsontheburnerprimarycontrol,ringtheburner.Iftheboiler
watertemperatureexceedsthehighlimitsettingof180F,thehighlimitwillopenthe“T”-“T”circuitandtheburnerwill
shutdown.
Ifthereisacallforspaceheat,theheatingthermostatwillmakethe“T”-”T”circuitandtheboilerwillrewithoutregard
tothestatusoftheindirectwaterheater.Thelowwatercut-offandpressurelimitcontrolwillinterrupt120voltpowertothe
burnerintheeventofalowwaterorexcessivepressurecondition.
FIGURE14a:WIRINGMCDONNELL&MILLER101AORTWO-WIRE H Y D R O L E V E L V X T- 2 4 F E E D E R 
TOBOILEREQUIPPEDWITH#67L.W.C.O.
CAUTION
DO NOT INSTALL
JUMPERBETWEEN2&3
ON #67 L.W.C.O.