Crown Bermuda Installation Manual

21
21
BlockedVent(“Spill”)Switch-Automaticallyinterruptsburneroperationintheeventthatuegasspillsfromthedraftdiverter
opening.Thisswitchisequippedwitharesetbuttonwhichmustbepressedtorestorenormalburneroperation.Anopenblocked
ventswitchisindicativeofaproblemwiththeventsystem.Iftheblockedventswitchopens,thecauseoftheventingproblem
mustbefoundandcorrectedbyaqualiedgasservicetechnicianbeforetheblockedventswitchisreset.
FlameRoll-outSwitch-Automaticallyinterruptsburneroperationwhenamesorexcessiveheatarepresentinvestibule.The
ameroll-outswitchisasingleusedevicewhichmustbereplacedbyanidenticalswitchinordertorestorenormaloperation.
Anopenameroll-outswitchisusuallyindicativeofapluggedheatexchanger.Thecauseoftheameroll-outmustbefound
andcorrectedbyaqualiedgasservicetechnician,andtheswitchreplacedwithanidenticalone,beforetheboilerisreturnedto
operation.
FIGURE16:WIRINGDIAGRAM,INTERMITTENTIGNITIONANDHYDROLEVELCG-400ALOWWATERCUTOFF
“BURNER”
“BURNER”
TH
TR
+
ROBERTSHAW
7000DERHC
GAS VALVE
(BSI380)
HONEYWELL
VR8204/VR8304
SERIES GAS VALVES
(BSI069 - 346)
VENT DAMPER (NOTE 2)
NOTE 3
LESS VENT
DAMPER
2. VENT DAMPER REQUIRED ON BSI069 - BSI276, OPTIONAL ON BSI311 - BSI380
3. ON BOILERS LESS VENT DAMPER, DAMPER HARNESS NOT USED. RED AND BLUE
LEADS ARE JUMPED TOGETHER USING RED JUMPER WIRE.