XI Start-up and Checkout
Usethefollowingprocedureforinitialstart-upoftheboiler:
1) Makesurethattheboilerislledwithwatertothenormalwaterline(283/4inchesabovetheoororpadonwhichthe
boilerisinstalled)
2) Checkallnewgaspipingforleaksandpurgepipingsectionsthatarelledwithair.SeePart4oftheNational Fuel Gas
Codeforadditionalinformationontestingandpurginggaslines.
3) Verifythatventsystemiscompleteandfreeofobstructionsbeforeattemptingtoreboiler.
4) Inspectallwiringforlooseoruninsulatedconnections.
5) Makesurethemainburnersareseatedproperlyintherearofburnertrayandonorices.
6) Adjuststeampressurelimitcontrolforacut-inpressureof0.5psiandadifferentialpressureof1psi.
7) Adjustthermostattothehighestsetting.
8) Starttheboilerusingtheappropriatelightinginstructionsforthegasvalveontheboileronpages25-26.
9) Uponinitialstart-up,thegastrainwillbelledwithair.Evenifthegaslinehasbeencompletelypurgedofair,it
maytakeseveraltriesforignitionbeforeaameisestablished.Onceaamehasbeenestablishedforthersttime,
subsequentcallsforburneroperationshouldresultinaameonthersttry.
10) Observepilotburnerame.Pilotburnerproducesthreeames.Thecenteroneshouldbeasteadymediumblueame
coveringaround3/8”to½”ofsparkelectrode/amerod.
12) Makesureventdamperisinopenpositionwhenmainburnersarering.
13) Inspectthemainburneramesvisiblethroughtheobservationportinburneraccesspanel.Theameshouldbestable
andmostlyblue(seeFigure19).Noyellowtippingshouldbepresent;however,intermittentecksofyellowandorange
intheamearenormal.
14) Checkentiregastrainforleaksusingsoapandwaterorotherapprovedleakdetectionmethodwhileboilerisring.Fix
anyleaksfoundimmediately.
15) Rungasvalvesafetyshutdowntest.Withmainburnersring,disconnectignitioncablefromignitionmodule.Both
pilotburnerandmainburnersshouldstopring.
NOTE
SAFELIGHTINGANDOTHERPERFORMANCECRITERIAWEREMETWITHTHEGASMANIFOLD
ANDCONTROLASSEMBLYPROVIDEDONTHEBOILERWHENTHEBOILERUNDERWENTTHE
TESTSSPECIFIEDINZ21.13.
WARNING
NEVERUSEAFLAMETOCHECKFORGASLEAKS.
MAKESURETHATTHEAREAAROUNDTHEBOILERISCLEARANDFREEFROM
COMBUSTIBLEMATERIALS,GASOLINE,ANDOTHERFLAMMABLEVAPORSANDLIQUIDS.
DAMPERMUSTBEINOPENPOSITIONWHENAPPLIANCEMAINBURNERISOPERATING.