16) Checkthemanifoldpressureandadjustifnecessary.Todothis,usethefollowingprocedure:
a) Connectamanometertotheinletpressuretaponthegasvalve(seeFigure20).
b) Checktheinletpressurewithallgasappliancesonandoff.Theinletpressureattheboilermustbewithinthe
followinglimitsregardlessofwhatcombinationofappliancesisring:
InletPress(inchesw.c.) NaturalGas LPGas
Min. 5.0 11.0
Max.  14.0 13.0
Iftheinletpressurefallsoutsideoftheselimits,ndandcorrectthecauseoftheproblembeforeproceedingfurther.
c) Connectamanometertothemanifold(outlet)pressuretaponthegasvalve(seeFigures23and24).
d) Readthemanifoldpressure.Itshouldbesetat:
NaturalGas LPGas
ManifoldPress.(inchesw.c.) 3.5  10.0
e) Ifamanifoldpressureadjustmentisneeded,maketheadjustmentbyturningthepressureregulator(seeFigures23
and24)screwclockwisetoraisethepressureandcounterclockwisetoreducethepressure.Ifamanifoldpressure
adjustmentismade,recheckthelinepressuretobecertainthatitisstillwithinacceptablelimits.Replacethecover
screwontheregulator.
WARNING
FAILURE TO FOLLOW THE FOLLOWING PROCEDURE EXACTLY COULD RESULT IN OVER-
FIRING OF THE BOILER AND A CARBON MONOXIDE HAZARD.
FIGURE18:INTERMITTENTIGNITION
 PILOTBURNERFLAME