Operating instructions
14
0
50
100
150
200
250
300
350
400
450
0 50000 100000 150000 200000 250000
BOILER OUTPUT (BTU/hr)
FIRST HOUR RATING (GAL/hr)
Figure 4d: MT100G Ratings at Different Boiler Outputs
3.0 5.0 7.5 9.0 12.0 15.0
MT040G
Time (min.) 11.9 6.8 4.2 3.2 103149
Gallons. 35.6 33.9 31.2 29.2
MT050G
Time (min.) Ind. 9.3 5.7 4.5 116094
Gallons. 46.7 42.8 40.9
MT079G
Time (min.) Ind. 13.2 8.5 6.1 3.8 2.5 137604
Gallons. 65.8 64.0 54.8 46.2 37.3
MT100G
Time (min.) Ind. Ind. 10.6 8.4 5.7 4.0 200038
Gallons. 79.3 75.2 68.1 59.4
Notes:
2) “Gallons” – The total volume of water drawn from the tank during this time.
4) All valves shown are approximate.
3) "Ind."- Draw may be made at this flow rate indefinitely with the outlet temperature falling less than 25
degrees from the outlet temperature at the beginning of the draw.
1) “Time (min.)” – The time water may be drawn from a fully recovered tank before the outlet temperature
falls 25 degrees.
Draw Rate (GPM)
Model
Boiler Output
(BTU/hr)
Table 4: 135F Water Available at Various Flow Rates Starting with a Fully Recovered