Operating instructions

16
(1) (2) (3) (4)
Fitting Description 8 Gal/min 10 Gal/min
MT040G Coil 2.60
MT050G Coil 2.60
MT079G Coil 4.40
MT100G Coil 5.70
1 ft 1" St. Pipe 0.05 0.08
1 ft 1-1/4" St. Pipe 0.02 0.03
1 ft 1-1/2" St. Pipe 0.01 0.02
1" 90 El 0.16 0.25
1-1/4" 90 El 0.06 0.09
1-1/2" 90 El 0.04 0.06
1" Run of Tee 0.05 0.08
1-1/4" Run of Tee 0.02 0.03
1-1/2" Run of Tee 0.01 0.02
1" Branch in Tee 0.26 0.41
1-1/4" Branch in Tee 0.08 0.13
1-1/2" Branch in Tee 0.05 0.08
1" Std. Ball Valve 0.12 0.19
1-1/4" Std. Ball Valve 0.06 0.09
1-1/2" Std. Ball Valve 0.02 0.03
Taco "Flo-Chek":
#220 (1") 2.18 3.41
#220 (1-1/4") 0.84 1.31
#222 (1-1/2") 0.44 0.69
Taco "Air Scoop":
#431 (1") 0.15 0.23
#432 (1-1/4") 0.05 0.08
Boiler (**)
ft wc.
Notes:
* Includes (2) 1-1/2 x 3/4 Bus hings and (2) 1-1/2 x 1 Trans itions
** The Pressure Drop Through Most Cast Iron and Steel Boilers can be Ignored
1 0.53 0.83
Honeywell V8043F1101 Zone
Valve (Cv = 8) 2.31
WORKSHEET #3: Pre ss ure Drop Calculations Through M axi-The rm Zone
3.61
Total Head Loss Through Manifold Piping and Maxi-Therm Zone =
Pressure Drop (ft head)
at:
Quantity Total
Allowance for Bushings and
Sudden Transitions (*)