Operating instructions

METHOD A: “QUICK” RESIDENTIAL
Table 2 shows some typical applications into which many “residential” applications can be classified. This
procedure will provide satisfactory results most of the time. Where greater accuracy is desired, use Method B.
1) Find the description that best fits the installation and select the Maxi-Therm called for. Also note the
required boiler output under column (f).
2) The Maxi-Therm must be installed with a boiler having an output GREATER THAN OR EQUAL to that
shown in column (f) of Table 2. If the Maxi-Therm is to be used with a boiler having an output LESS
than that shown in Table 2, use Method B.
a) If a new boiler is to be installed with the Maxi-Therm, first find a boiler that will handle the space
heating load alone. If this boiler has an output GREATER than that shown in column (f), do not add
anything to the size of the boiler selected for the Maxi-Therm.
b) If the boiler required for space heating alone has an output LESS than that called for in column (f)
of Table 2, increase the size of the boiler selected to one with an output equal to that shown in
column (f).
5
Table 2: Maxi-Therm “Quick Sizing” Table
(a) (b) (c) (d) (e) (f)
Description Occupants Baths Dishwasher Maxi-Therm
*No showers. If a clothes washer is present, it is a residential model.
Yes
Yes
MT040G
MT040G1-1 ½
1-1 ½
2-2 ½
80,000
80,000
116,000Yes
Yes
Yes
Yes
MT040G
MT050G
Apartment
House
House
<10
1-2
1-3
3-5
Clothes
Washer Boiler Output
Small Office ½-1* Yes * 30,000Yes