Datasheet

CW24 Series
• The newest family to the SSR range; Ratings from 10A to 125A @
12-660 V AC
• SCR output for heavy industrial loads
• EMC Compliant for reliable operation in harsh environments
• Removable IP 20 touch-safe cover
• DBC substrate for superior thermal performance
• LED input status indicator
• AC or DC input
• Zero-crossing (resistive loads) or random-fire (inductive loads) output
PRODUCT SELECTION
Description 10A 25A 50A 90A 125A
3-32 VDC CWD2410 CWD2425 CWD2450 CWD2490 CWD24125
90-280 Vrms CWA2410 CWA2425 CWA2450 CWA2490 CWA24125
18-36 Vrms CWA2410E CWA2425E CWA2450E CWA2490E CWA24125E
OUTPUT SPECIFICATIONS (1)
Description 10A 25A 50A 90A 125A
Operating Voltage (47-63Hz) [Vrms] 24-280 24-280 24-280 24-280 24-280
Transient Overvoltage [Vpk] 600 600 600 600 600
Maximum Off-State Leakage Current @ Rated Voltage [mArms](6) 1 1 1 1 1
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] (2) 500 500 500 500 500
Maximum Load Current (3) [Arms] 10 25 50 90 125
Minimum Load Current [Arms] 0.15 0.15 0.15 0.25 0.25
Maximum Surge Current (16.6ms) [Apk] 400 600 850 1350 2000
Maximum Surge Current (20ms) [Apk] 380 570 810 1290 1900
Maximum On-State Voltage Drop @ Rated Current [Vpk] 1.3 1.3 1.3 1.3 1.25
Thermal Resistance Junction to Case (Rjc) [°C/W] 0.35 0.35 0.2 0.14 0.13
Maximum I
2
t for Fusing (8.3 msec) [A
2
sec]
660 1500 3000 7560 16600
Minimum Power Factor (with Maximum Load) 0.5 0.5 0.5 0.5 0.5

Summary of content (5 pages)