Datasheet

Rev. 060216
AGENCY APPROVALS, CONFORMANCES AND EMC
Certification in accordance with:
United States Standard for Industrial Control Equipment - UL 508 and
Canadian Standard Association for Industrial Control Equipment – C22.2 No. 14.
Certification in accordance with:
Electromagnetic Compatibility
Generic
Standard
Inmunity Tests Test Specification
Level
IEC 61000-6-2
Immunity for
Industrial
Environments
Electrostatic Discharge
IEC 61000-4-2
Fast transients (burst)
IEC 61000-4-4
Surge
IEC 61000-4-5
4kV air discharge
4kV contact discharge
Output 2kV, 5kHz, 100kHz
Input 1kV, 5kHz, 100kHz
1kV Line to Line
2kV Line to Earth
Performance
Criterion A
Criterion A
Criterion B
Criterion B
Criterion B
Criterion B
Output
E116949
(1) All parameters at 25°C unless otherwise specified.
(2) Low current loads and high ambient temperature can affect turn-on time.
(3) 8 VDC Minimum control voltage. Resistive loads only . Consider switching losses; at maximum frequency reduce to 75% output current.
Recommended suppressor diode connected at load side, see wiring diagram.
(4) Increase minimum voltage by 1 V for operations from -20 to -40°C.
(5) Minimum spacing to obtain max. current is 22.5mm between adjacent units.
GENERAL NOTES
ID Marker
Recommended Accessories
CNLB
CNLN
CNL2
ACCESSORIES
Datasheet
DIN Rail Mount
Do not forget to visit us at: www.crydom.com