Datasheet

DR22 Series
AC Output DIN Rail Mount SSRs
Output ratings up to 35 Amps at 600 VAC
Built-in overvoltage protection
Relay or Contactor configuration
Integral heat sink eliminates the need for complex thermal calculations
DBC substrate for superior thermal performance
"Elevator" screw option to allow the use of ring or lug type terminals
IP20 touch-safe housing
AC or DC control
C-UL-US and TUV approved
PRODUCT SELECTION
Control Voltage 20A
90-280 VAC/VDC DR2260A20x
4-32 VDC DR2260D20x
30A
DR2260A30x
DR2260D30x
35A
DR2260A35x
DR2260D35x
AVAILABLE OPTIONS
Required for valid part number
For options only and not required for valid part number
Operating Voltage
60: 48-600 VAC
Switching Type
Blank: Zero Voltage Turn-On
R: Instantaneous Turn-On
(Motor Rating Certified)
Control Voltage (1)
A: 90-280 VAC/VDC
D: 4-32 VDC
Series
DR22 60 A R
Rated Load Current
20: 20 Amps
30: 30 Amps
35: 35 Amps [High I
2
t]
U
Terminal Layout
U: Relay Configuration
V: Contactor Configuration
(std. screw)
W: Contactor Configuration
(elevator screw)
Input Connector
Blank: Screw Terminal
J: Spring Terminal
(V and W suffixes only)
V
20 J
OUTPUT SPECIFICATIONS
(2)
Description 30A
Operating Voltage (47-440Hz) [VRMS] 48-600
Transient Overvoltage [Vpk]
(3) 1200
Maximum Off-State Leakage Current @ Rated Voltage [mA
RMS] 1
Minimum Off-State dV/dt @ Maximum Rated Voltage [V/μsec] 500
Load Current, General Use UL508/LC A IEC62314 @ 40°C [A
RMS] 30
Minimum Load Current [mA
RMS] 100
Maximum 1 Cycle Surge Current (50/60Hz) [Apk] 716/750
Maximum On-State Voltage Drop @ Rated Current [Vpk] 1.35
Maximum 1/2 Cycle I² t for Fusing (50/60Hz) [A² sec] 2563/2343
35A20A
48-600 48-600
1200 1200
1 1
500 500
20 35
Load Current, Motor Starting UL508 FLA/LC B IEC62314 @ 40°C [ARMS] 14/7.6
8.5/4.8 26/14
100 150
286/300 1290/1350
1.35 1.3
409/375 8320/7593
Minimum Power Factor (at Maximum Load)
(4) 0.5
0.5 0.5
Motor Rating UL 508/IEC62314 [HP (kW)]: 120 VAC 1 (0.74)
0.5 (0.37) 2 (1.5)
Motor Rating UL 508/IEC62314 [HP (kW)]: 240 VAC 3 (2.2)
1.5 (1.1) 5 (3.73)
Motor Rating UL 508/IEC62314 [HP (kW)]: 480 VAC 5 (3.7)
3 (2.24) 10 (7.4)
INPUT SPECIFICATIONS
(2)
Description DR2260Axxx
Control Voltage Range 90-280 VAC/VDC
Maximum Reverse Voltage -
Minimum Turn-On Voltage 90 VAC/VDC
Must Turn-Off Voltage 5 VAC/VDC
Minimum Input Current (for on-state) 6 mA
Maximum Input Current 10 mA
Nominal Input Impedance Current Limited
Maximum Turn-On Time [msec] 20
Maximum Turn-Off Time [msec] 30
DR2260Dxxx
4-32 VDC
-32 VDC
4 VDC
1 VDC
10 mA
15 mA
Current Limited
1/2 Cycle
1/2 Cycle
(5) (6)
(7)
Datasheet
DIN Rail Mount
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.