Datasheet

DRH Series
Ratings up to 18 & 20 Amps at 600VAC
Fits standard 35mm DIN Rail
Integrated over-temperature protection
Alarm output in case of over-temperature
Multicolor LED with input status and alarm indicator
AC or DC control
Zero Voltage (resistive loads) or instantaneous (inductive loads) turn-on output
C-UL-US Listed,
IEC Rated, CE & RoHS Compliant, Horsepower Rated
Built-in Overvoltage Protection
Fan controlled through thermistor and microprocessor to optimize fan operation
PRODUCT SELECTION
Control Voltage 18A
90-280 VAC/VDC DRH3P60A18
4-32 VDC DRH3P60D18
20A
DRH3P60A20
DRH3P60D20
AVAILABLE OPTIONS
Required for valid part number
For options only and not required for valid part number
Function
3P: Contactor
Switching Type
Blank: Zero Voltage Turn-On
R: Instantaneous Turn-On
Operating Voltage
60: 48-600 VAC
Series
DRH 3P 60 R
Control Voltage
A: 90-280 VAC/VDC
D: 4-32 VDC
U
Rated Load Current
18: 18 Amps (3 Controlled legs)
20: 20 Amps (2 Controlled legs)
18
A
OUTPUT SPECIFICATIONS
(1)
Description
Operating Voltage (47-63Hz) [VRMS]
Transient Overvoltage [Vpk]
(2)
Maximum Off-State Leakage Current @ Rated Voltage [mARMS]
Minimum Off-State dV/dt @ Maximum Rated Voltage [V/μsec]
Load Current, General Use UL508/IEC62314 @ 40°C [A
RMS] (3)
Minimum Load Current [A
RMS]
Maximum Surge Current [Apk] 1Cycle 60Hz
Maximum Surge Current [Apk] 1Cycle 50Hz
Maximum I²t for Fusing (8.33 msec) [A²sec]
20A18A
48-600 48-600
1200 1200
3 3
500 500
18 20
Load Current, Motor Starting UL508 FLA/IEC62314 @ 40°C [ARMS] (3)
7.6 7.6
0.15 0.15
750 750
716 716
2330 2330
Maximum I²t for Fusing (10 msec) [A²sec]
2560 2560
Maximum On-State Voltage Drop @ Rated Current [Vpk]
1.35 per channel 1.35 per channel
Minimum Power Factor (with Maximum Load)
0.5 0.5
Motor Rating UL 508/ IEC60947-4-2 [HP/kW] :240 VAC
2/1.5 2/1.5
Motor Rating UL 508/ IEC60947-4-2 [HP/kW] :380 VAC
3/2.2 3/2.2
Motor Rating UL 508/ IEC60947-4-2 [HP/kW] :480 VAC
5/3.7 5/3.7
INPUT SPECIFICATIONS
(1)
Description DRH3P60Ax
Control Voltage Range 90-280 VAC/VDC
Minimum Turn-On Voltage 90 VAC/VDC
Must Turn-Off Voltage 10 VAC
Minimum Input Current (for on-state) 1 mA
Maximum Input Current 3 mA
Nominal Input Impedance [Ohms] 100k
Maximum Turn-On Time [msec] 30
Maximum Turn-Off Time [msec] 40
DRH3P60Dx
4-32 VDC
4 VDC
1 VDC
2 mA
17 mA
2k
1 Cycle
1 Cycle
(4)