Datasheet

ACCESSORIES
Rev. 051716
GENERAL NOTES
(1) All parameters at 25°C unless otherwise specified.
(2) Relay will self trigger between 950-1200V, Not suitable for capacitive loads.
(3) Mounted in the Vertical position.
(4) Turn-on time for Instantaneous turn-on version is 4 msec.
(5) For input to alarm output the dielectric strength is 1.5kV.
(6) UL approval up to 40°C surrounding temperature.
(7) 100kA, 480VAC, when protected with CC class fuses rated 600VAC, 20A or equivalent.
(8) IP20 rating is not associated with the UL approval.
(9) Minimum spacing to obtain max. current is 22mm between adjacent units.
(10) Combination of these Protective Devices and Solid State Contactor have not been evaluated by UL.
ID Marker
ID Marker
CNLB
CNLN
CNL2
Package of 10 plastic strip
comprising 10 individual markers
which can be placed for easy
identification during the use of
multiple units.
E116949
AGENCY APPROVALS
United States Standard for Industrial Control Equipment - UL 508 and
Canadian Standard Association for Industrial Control Equipment – C22.2 No. 14.
DRH series conforms to the harmonized EN standard EN/IEC 60947-4-2
Electromagnetic Compatibility:
IEC 61000-4-2 : Electrostatic Discharge – Level 3
IEC 61000-4-4 : Electrically Fast Transients – Level 3
IEC 61000-4-5 : Electrical Surges – Level 3
Vibration Resistance:
IEC 60068-2-6: Amplitude Range 10-55 Hz, Displacement 0.75mm
Shock Resistance:
IEC 60068-2-27: Peak Acceleration 15g, Duration 11msec.
Certification in accordance with:
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.