Technical data
INSTALLATION REQUIREMENTS 
5”(125mm) FLUE PIPE AND STARTER BOX 
A DOUBLE WALLED SELKIRK RECESSED FLUE BOX BUILT TO THE 
REQUIRMENTS OF BS 715 WITH AN INSULATED FLUE HAVING A 
MINIMUM DIAMETER OF 125mm(5”) AND A MINIMUM EFFECTIVE 
OVERALL HEIGHT OF 3 METRES (10FT) 
457mm
610mm
c
560mm
143mm
330mm
407mm
330mm
RECESSED GAS FLUE BOX DIMENSIONS(NOT INCLUDING FIBREGLASS 
INSULATION) 
NOTE 
THE METAL FLUE BOX MUST BE INSULATED WITH FIBREGLASS OR 
EQUIVALENT TO A THICKNESS OF 25mm 
NOTE 
WHERE INSTALLATION IS FOR A METAL FLUEBOX.THE SURROUND 
MUST HAVE A TEMPERATURE RATING OF 150 DEGREES C 
NOTE 
IF A FLUE BOX IS TO BE USED WITH A EXISTING BRICK OR STONE 
CHIMNEY A 125mm MINIMUM DIAMETER FLUE LINER CONFORMING TO 
BS 715 CAN BE USED 
NOTE 
A BRICK CHAMBER TO THE SIZES IN FIG 2 .IN AN EXISTING BRICK OR 
STONE CHIMNEY A 125mm (5”) MINIMUM DIAMETER FLUE LINER 
CONFORMING TO BS 715 MAY BE USED,PROVIDING THAT IT IS SEALED 
AT THE TOP AND BOTTOM OF EXISTING BRICK OR STONE CHIMNEY. 
NOTE 
ANY OF THE ABOVE FLUES MUST NOT BE RESTRICTED BY DAMPERS 
OR REGISTER PLATES.THE FLUEMUST SERVE ONLY ONE APPLIANCE 
AND NOT HAVE ANY BRANCHES OR TRAPS WHICH MAY IMPEDE THE 
NATURAL DRAUGHT .IF ANY TERMINAL IS FITTED IT MUST BE 
SUITABLE FOR THE PURPOSE 
ISSUE 2 
7










