Dew point
Dew point set DS 52
consisting of:
Special features
 System ready for plug-in
  Everything completely wired 
 No time-consuming studying of the 
  instruction manual
 2 alarm contacts (230 VAC, 3 A)
  pre- and main-alarm freely adjustable
 4...20 mA analogue output
 Option alarm unit: 
  Buzzer and continuous red light
The measuring range of -20...50 °Ctd makes the dew point set DS 52 with alarm the 
ideal dew point monitor with analogue output 4...20 mA. 
The dew point sensor FA 415 is extremely long-term stable and can be installed 
and removed quickly and easily under pressure by means of the screwable measuring 
chamber including quick coupling. The dew point set is supplied ready for plug-in, 
i. e. everything is completely wired. The alarm values can be freely adjusted.
Description      Order no. 
Dew point set DS 52 for refrigeration dryers, consisting of:   0600 0425
DS 52 LED digital process meter in wall housing  0500 0007
FA 415 dew point sensor (-20...50 °Ctd)  0699 0415
Standard measuring chamber up to 16 bar  0699 3390
Connection cable for VA/FA Series, 5 m with M12 plug  0553 0104
Options:
Power supply 24 VDC (instead of 230 VAC)    Z500 0001
Power uspply 110 VAC (instead of 230 VAC)    Z500 0002
Alarm unit mounted at wall housing    Z500 0003
Alarm unit for external mounting with 5 m lead    Z500 0004
Additional accessory:
Precision calibration at 3°Ctd including ISO certificate  3200 0003
Technical data 
dew point sensor FA 415
Measuring range:  -20...50 °Ctd
Accuracy:  ± 1 °C at 0...20 °Ctd
  ± 2 °C remaining range
Pressure range:  -1...16 bar
Protection class:  IP 65
EMV:  according to DIN EN 61326
Operating temp.:  -20...70 °C
Connection: M12, 5 pole
PC connection:  SDI interface
Burden analogue 
output: < 500 Ohm
Screw-in thread:  G 1/2" without meas.chamber
Technical data 
display DS 52
Dimensions:  118 x 92 x 93 mm
Display:  LED red, 7 segments, 
  height: 13 mm, 5 digits,
  2 LED for alarm relay
Keypad:  4 keys
Input:   dew point sensor FA 415
Power supply:  230 VAC, 50/60 Hz; 
  Option: 24 VDC or 
  110 VAC 50/60 Hz
Alarm outputs:   2 x relay output, changeover
  contact, 250 VAC, max. 3 A
Operating  -10...+60 °C (storage temp.
temperature:  -20 °C...+80 °C)
Alarm thresholds:  freely adjustable
Hysteresis:   2 °Ctd
Analogue output:  4...20 mA = -20...50 °Ctd
• Digital process meter DS 52
• Dew point sensor FA 415
• Standard measuring 
• chamber
Option: Alarm unit (buzzer 
and continuous red light)
Dew point set DS 52 for refrigeration dryers