Instruction manual
36
www.cs-instruments.com
Flow station DS 300 
with consumption counter
Consumption
DS 300 displays the actual value (m
3
/h, 
m
3
/min) and the total consumption.
A 4...20 mA output for m
3
/h and a pulse 
output for m
3 
are available for routing to a 
superior building management system 
(PLC) 
Special features
 Usable from 1/2” to 12” (DN 300)
 All-in-one solution, small 
 installation expenditure
 2 displays, actual flow and total
 consumption
 Easy installation and removal of the
  sensor under pressure
 Highest accuracy due to 5 point 
 precision calibration
 Output 4 to 20 mA for m
3
h,
  pulse output for m
3
 Easy handling:
  – Inner diameter freely adjustable
  – in DS 300
  – 2 alarm values freely adjustable
  – Optical display in case of alarm
  – Consumption counter resettable
 Dew point sensor connectable
Flow measuring ranges VA 400 for compressed air (ISO 1217: 1000 mbar, 20°C)
The large measuring range of the 
consumption sensors enable the 
recordings of high consumptions 
(e. g. on weekdays) and the determination 
of leakages of a few litres/min 
(e. g. weekends).
Flow station DS 300 with 
consumption counter 
consisting of:
 Multifunction measuring
  instrument DS 300
 Consumption probe VA 400
 Available with and without 
 measuring section
Installation even under pressure via 
customary 1/2” ball valve
Inner diameter of pipe  VA 400 Standard  VA 400 Max.  VA 400 HighSpeed
  (92.7 m/s)  (185.0 m/s)  (224.0 m/s)
Inch  mm    Meas. ranges  Meas. ranges  Meas. ranges
      from ... to  from ... to  from ... to
1/2”  16.1  DN 15  2.5...760 l/min  3.5...1516 l/min  6.0...1836 l/min
3/4”  21.7  DN 20  0.3...89 m
3
/h 0.4...178 m
3
/h 0.7...215 m
3
/h
1”  27.3  DN 25  0.5...148 m
3
/h 0.6...295 m
3
/h 1.1...357 m
3
/h
1 1/4”  36.0  DN 32  0.9...280 m
3
/h 1.2...531 m
3
/h 2.5...644 m
3
/h
1 1/2”  41.8  DN 40  1.2...365 m
3
/h 1.5...728 m
3
/h 3.0...882 m
3
/h
2”  53.1  DN 50  2...600 m
3
/h 2.5...1198 m
3
/h 4.6...1450 m
3
/h
2 1/2”  71.1  DN 65  3.5...1096 m
3
/h 5...2187 m
3
/h 7...2648 m
3
/h
3”  84.9  DN 80  5...1570 m
3
/h 7...3133 m
3
/h 12...3794 m
3
/h
4” 110.0 DN 100 9...2645 m
3
/h 12...5279 m
3
/h 16...6391 m
3
/h
5”  133.7  DN 125  13...3912 m
3
/h 18...7808 m
3
/h 24...9453 m
3
/h
6”  159.3  DN 150  18...5560 m
3
/h 25...11097 m
3
/h 43...13436 m
3
/h
8”  200.0  DN 200  26...8786 m
3
/h 33...17533 m
3
/h 50...21230 m
3
/h
10”  250.0  DN 250  40...13744 m
3
/h 52...27429 m
3
/h 80...33211 m
3
/h
12”  300.0  DN 300  60...19815 m
3
/h 80...39544 m
3
/h 100...47881 m
3
/h
engraved
depth scale
safety ring
mounting depth 
= x + y
d
A
 =  outer diameter
x =
y
쑿
쑼
쑼
쑿
쑿
쑼
x
d
A
d
A
2