Reference Manual 00809-0100-4026, Rev HA November 2014 Rosemount 5400 Series Superior Performance Two-Wire Non-Contacting Radar Level Transmitter
Reference Manual 00809-0100-4026, Rev HA November 2014 Rosemount 5400 Series Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure you thoroughly understand the contents before installing, using, or maintaining this product. Within the United States, Emerson Process Management has two toll-free assistance numbers. Customer Central: Technical support, quoting, and order-related questions.
Reference Manual November 2014 iv 00809-0100-4026, Rev HA
Reference Manual Contents 00809-0100-4026, Rev HA November 2014 Contents 1Section 1: Introduction 1.1 Manual overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.2 Service support. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1.3 Product recycling/ disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.
Reference Manual Contents 00809-0100-4026, Rev HA November 2014 3.4.6 Bracket mounting on wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41 3.4.7 Bracket mounting on pipe. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42 4Section 4: Electrical Installation 4.1 Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43 4.2 Wiring and power supply requirements. . .
Reference Manual Contents 00809-0100-4026, Rev HA November 2014 5Section 5: Basic Configuration/Start-up 5.1 Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73 5.2 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .74 5.2.1 Basic configuration parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .74 5.2.
Reference Manual Contents 00809-0100-4026, Rev HA November 2014 6Section 6: Operation 6.1 Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119 6.2 Viewing measurement data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120 6.2.1 Using the display panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120 6.2.2 Specifying display panel variables . . . . . . . .
Reference Manual Contents 00809-0100-4026, Rev HA November 2014 7.15Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163 7.15.1Resource block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164 7.15.2Transducer block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165 7.15.3Analog Input (AI) function block . . . . . . . . . . . . . . . . . . .
Reference Manual Contents 00809-0100-4026, Rev HA November 2014 A.2 Performance specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189 A.2.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189 A.2.2 Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190 A.2.3 Beam angle and beam width . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Contents 00809-0100-4026, Rev HA November 2014 B.6 Approval drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230 CAppendix C: Advanced Configuration C.1 Tank geometry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237 C.1.1 Distance offset (G) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237 C.1.
Reference Manual Contents 00809-0100-4026, Rev HA November 2014 FAppendix F: Register Transducer Block F.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265 F.1.1 Register access transducer block parameters . . . . . . . . . . . . . . . . . . . . . . 265 GAppendix G: Advanced Configuration Transducer Block G.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Section 1: Introduction 00809-0100-4026, Rev HA November 2014 Section 1 Introduction Manual overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1 Service support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3 Product recycling/ disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Section 1: Introduction 00809-0100-4026, Rev HA November 2014 Section 5: Basic Configuration/Start-up Configuration instructions Configuration using the Rosemount Radar Master (RRM) software Configuration using a Field Communicator Configuration using AMS® Suite Configuration using DeltaV™ FOUNDATIONTM fieldbus overview Section 6: Operation Viewing measurement data with a display panel Viewing measurement data in RRM Viewing measurement data in AMS Sui
Reference Manual Section 1: Introduction 00809-0100-4026, Rev HA November 2014 Appendix C: Advanced Configuration Advanced tank geometry Advanced transmitter settings Advanced functions in RRM Appendix D: Performing Proof Test Describes the process of performing proof test Appendix E: Level Transducer Block Describes the operation and parameters of the Level Transducer Block Appendix F: Register Transducer Block Describes the operation and parameters of the Register Transducer Blo
Section 1: Introduction Reference Manual 00809-0100-4026, Rev HA November 2014 Emerson Process Management Instrument and Valves Response Center representatives will explain the additional information and procedures necessary to return goods exposed to hazardous substances. 1.3 Product recycling/ disposal Recycling of equipment and packaging should be taken into consideration and disposed of in accordance with local and national legislation/regulations. 1.
Reference Manual Section 1: Introduction 00809-0100-4026, Rev HA November 2014 Failure to follow safe installation and service guidelines could result in death or serious injury. Make sure the transmitter is installed by qualified personnel and in accordance with applicable code of practice. Use the equipment only as specified in this manual. Failure to do so may impair the protection provided by the equipment.
Section 1: Introduction November 2014 6 Reference Manual 00809-0100-4026, Rev HA Introduction
Reference Manual Section 2: Transmitter Overview 00809-0100-4026, Rev HA November 2014 Section 2 Transmitter Overview Theory of operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7 Application examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 8 System architecture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Section 2: Transmitter Overview 00809-0100-4026, Rev HA November 2014 2.
Reference Manual Section 2: Transmitter Overview 00809-0100-4026, Rev HA November 2014 Reactor vessels The innovative design of the Rosemount 5400 Series makes it an excellent choice for the most difficult applications, such as reactor vessels: Unique circular polarization provides greater mounting flexibility – no tank wall clearance distance is needed Direct measurement – independent of most variations in process conditions, such as density, dielectric, vapor, temperature, and pressure Can han
Reference Manual Section 2: Transmitter Overview 00809-0100-4026, Rev HA November 2014 2.3 System architecture The Rosemount 5400 Series Radar Transmitter is loop-powered, and uses the same two wires for power supply and output signal. The output is a 4-20 mA analog signal superimposed with a digital HART®, FOUNDATION™ fieldbus or Modbus® signal. By using the optional HART Tri-Loop™, the HART signal can be converted up to three additional 4-20 mA analog signals.
Reference Manual Section 2: Transmitter Overview 00809-0100-4026, Rev HA November 2014 Figure 2-3. FOUNDATION fieldbus System Architecture Host / DCS system (e.g. DeltaV) Maintenance FOUNDATION fieldbus H2 - High Speed Field Bus H1 - Low Speed Field Bus Fieldbus Modem Field Communicator Note Intrinsically safe installations may allow fewer devices per I.S. barrier due to current limitations.
Section 2: Transmitter Overview 2.4 Reference Manual 00809-0100-4026, Rev HA November 2014 Process characteristics Dielectric constant A key parameter for measurement performance is reflectivity. A high dielectric constant of the media provides better reflection and enables a longer measuring range. Foam Rosemount 5400 Series Radar Transmitter measurement in foamy applications depends on the foam properties; light and airy or dense and heavy, high or low dielectrics, etc.
Reference Manual Section 2: Transmitter Overview 00809-0100-4026, Rev HA November 2014 Table 2-1. Sample Solids Applications(1) Common characteristics Particle size Dust or Powder Small (<1 in.) Larger (>1 in.
Reference Manual Section 2: Transmitter Overview 00809-0100-4026, Rev HA November 2014 2.5 Components of the transmitter The Rosemount 5400 Series Radar Transmitter is available with a die-cast aluminum or stainless steel (SST) housing containing advanced electronics for signal processing. The radar electronics produces an electromagnetic pulse that is emitted through the antenna. There are different antenna types and sizes available for various applications.
Reference Manual Section 2: Transmitter Overview 00809-0100-4026, Rev HA 2.6 November 2014 Antenna selection guide/measuring range The measuring range depends on the microwave frequency, antenna size, the dielectric constant (r) of the liquid, and process conditions. A higher dielectric constant value produces a stronger reflection. The figures in the tables below are guidelines for optimum performance. Larger measuring ranges may be possible.
Reference Manual Section 2: Transmitter Overview 00809-0100-4026, Rev HA November 2014 Table 2-3. Rosemount 5401, Maximum Recommended Measuring Range, ft (m) Low Frequency Antennas Dielectric Constant(1) a b c a b c a b c 3-in. Cone(2) NA NA NA 82 (25) 115 (35) 115 (35) NA NA NA 4-in. Cone / Rod(3) 23 (7) 39 (12) 49 (15) 82 (25) 115 (35) 115 (35) 13 (4) 26 (8) 39 (12) 6-in. Cone 43 (13) 66 (20) 82 (25) 82 (25) 115 (35) 115 (35) 20 (6) 33 (10) 46 (14) 8-in.
Reference Manual Section 2: Transmitter Overview 00809-0100-4026, Rev HA November 2014 Table 2-4. Model and Antenna Guide 5402 Model and antenna guide This table gives guidelines on which model and antenna to select, depending on application. 5401 Cone (preferred) Process seal Cone (preferred) Rod Best choice for a broad range of applications, free propagation and pipe installations. Ideal for small tanks and corrosive applications. Also good for heavy antenna condensation/build-up.
Section 2: Transmitter Overview Reference Manual November 2014 00809-0100-4026, Rev HA 18 Transmitter Overview
Reference Manual Section 3: Mechanical Installation 00809-0100-4026, Rev HA Section 3 November 2014 Mechanical Installation Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 19 Installation procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 21 Mounting considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Section 3: Mechanical Installation Reference Manual 00809-0100-4026, Rev HA November 2014 Failure to follow safe installation and service guidelines could result in death or serious injury. Make sure only qualified personnel perform installation or service. Use the equipment only as specified in this manual. Failure to do so may impair the protection provided by the equipment. Any substitution of non-recognized spare parts may jeopardize safety. Repair, e.g. substitution of components etc.
Reference Manual Section 3: Mechanical Installation 00809-0100-4026, Rev HA 3.
Reference Manual Section 3: Mechanical Installation 00809-0100-4026, Rev HA November 2014 3.3 Mounting considerations Before installing a Rosemount 5400 Series transmitter, consider specific mounting requirements, vessel, and process characteristics. 3.3.
Reference Manual Section 3: Mechanical Installation 00809-0100-4026, Rev HA November 2014 A metal still-pipe can be used to avoid disturbing objects, turbulence, and foam (G) Figure 3-2. Mounting in Still-Pipe (G) The walls in non-metallic tanks are invisible to the radar signal, so nearby objects outside of the tank may be detected Choose the largest possible antenna diameter for installation.
Reference Manual Section 3: Mechanical Installation 00809-0100-4026, Rev HA November 2014 3.3.2 Special considerations in solids applications The transmitter should be mounted as close to the center of the tank as possible, but not in the center of the tank. A general practice is to mount the transmitter at 2/3 tank radius from the tank wall, see Figure 3-4. Figure 3-4.
Reference Manual Section 3: Mechanical Installation 00809-0100-4026, Rev HA 3.3.3 November 2014 Mounting in pipes Still-pipe mounting is recommended for tanks with extremely turbulent surface conditions. All cone antenna sizes for the Rosemount 5400 Series of transmitters can be used for Still-pipe installations. The 3 in. (75 mm) antenna for the 5401 is designed for use in Still-pipes only. Rod antennas are not recommended for Still-pipes. Max. 0.
Section 3: Mechanical Installation Reference Manual 00809-0100-4026, Rev HA November 2014 Figure 3-7. Recommended Hole Size for Pipe Installations min. 6 in. (150 mm) max. Ø: D/10. D 3.3.4 Installation considerations Generally, the radar signal is unaffected by condensation and low pressure steam. If affected, the lower microwave frequencies are less affected. The critical point is the tank penetration, which acts as a cold spot, where the condensation will form.
Reference Manual Section 3: Mechanical Installation 00809-0100-4026, Rev HA 3.3.5 November 2014 Nozzle considerations Special considerations may have to be taken because of the nozzle, depending on the selection of transmitter model and antenna. 5402 with cone antenna The antenna can be recessed in smooth nozzles up to 6 ft (2 m). If the inside of the nozzle contains disturbing objects, use the extended cone (I). Figure 3-9.
Reference Manual Section 3: Mechanical Installation 00809-0100-4026, Rev HA November 2014 5401 with cone antenna The antenna should extend 0.4 in. (10 mm), or more, below the nozzle (L). If required, use the extended cone solution. Figure 3-11. Nozzle Considerations for 5401 with Cone Antenna (L) 0.4 in. (10 mm) or more 5401 with rod antenna The active part of the rod antenna should protrude below the nozzle (M). Figure 3-12.
Reference Manual Section 3: Mechanical Installation 00809-0100-4026, Rev HA November 2014 Note Match antenna size to the stilling well diameter. Figure 3-13. Nozzle Considerations for Still-Pipes in Metallic Materials (N) Max. 0.2 in.
Reference Manual Section 3: Mechanical Installation 00809-0100-4026, Rev HA November 2014 3.3.6 Nozzle recommendations and requirements The Rosemount 5400 Series is mounted on a nozzle by using appropriate flanges. For best performance, it is recommended that the nozzle meets the following recommendations for height (L) and diameter: Figure 3-14. Mounting of the Rosemount 5400 Series Transmitter Process seal antenna Rod antenna Cone antenna L Extended cone antenna L L > 0.4 in.
Reference Manual Section 3: Mechanical Installation 00809-0100-4026, Rev HA November 2014 (1) For Rosemount 5402, the values for maximum nozzle height are recommendations. Note that the Rosemount 5402 with cone antenna can be recessed in smooth nozzles up to 6 ft (2m). Table 3-2. Minimum Nozzle Diameter and Maximum Nozzle Height for Rod Antennas Model Antenna L max in. (mm) Min. diameter in. (mm) 5401(1) Rod (short) 4.0 (100) 1.5 (38) Rod (long) 10 (250) 1.
Reference Manual Section 3: Mechanical Installation 00809-0100-4026, Rev HA November 2014 3.3.7 Service space For easy access to the transmitter, mount it with sufficient service space. There is no requirement on clearance distance from the tank wall, provided it is flat and free of obstructions such as heating coils and ladders. The optimal location is often 1/4 of the tank diameter. Figure 3-15.
Reference Manual Section 3: Mechanical Installation 00809-0100-4026, Rev HA 3.3.8 November 2014 Beamwidth The following recommendations should be considered when mounting the transmitter: The transmitter should be mounted with as few internal structures as possible within the beam angle The flat tank wall can be located within the antenna beam angle if there is a minimum distance from the transmitter to the tank wall (see Figure 3-15 for preferred installation) Figure 3-16.
Reference Manual Section 3: Mechanical Installation 00809-0100-4026, Rev HA November 2014 Table 3-6. Beamwidth for the Rosemount 5401 Model (in ft [m]) Antenna Distance 4 in. (DN 100) cone /rod 6 in. (DN 150) cone 8 in. (DN 200) cone 16 ft (5 m) 9.8 (3..0) 6.6 (2.0) 4.9 (1.5) 33 ft (10 m) 21.3 (6.5) 13.1 (4.0) 9.8 (3.0) 49 ft (15 m) 32.8 (10) 19.7 (6.0) 14.8 (4.5) 66 ft (20 m) 41 (12.5) 26.2 (8.0) 19.7 (6.0) Figure 3-17. Beam Angle Beam angle Table 3-7.
Reference Manual Section 3: Mechanical Installation 00809-0100-4026, Rev HA 3.3.9 November 2014 Vessel characteristics Heating coils, agitators and other objects in the tank may lead to disturbing echoes and noise in the measurement signal. Vertical structures cause minimal effect since the radar signal is scattered rather than directed back to the antenna. The shape of the tank bottom affects the measurement signal when the product surface is close to the tank bottom.
Reference Manual Section 3: Mechanical Installation 00809-0100-4026, Rev HA November 2014 3.4 Mounting Mount the transmitter on a nozzle on top of the tank making sure only qualified personnel perform the installation. The transmitter housing must not be opened. If the transmitter housing must be removed for service, make sure the PTFE sealing is carefully protected against dust and water. 3.4.1 Cone antenna flange connection Figure 3-18.
Reference Manual Section 3: Mechanical Installation 00809-0100-4026, Rev HA 3.4.2 November 2014 Process seal antenna(1) Figure 3-19. Mounting the Rosemount 5400 with Process Seal and Flange A D B E A. Transmitter housing B. Nut, 40 Nm (30 Lbft) C. Nut D. Locking screw (ATEX) E. Bolt F. Flange G. Process Seal antenna H. Tank flange I. Nozzle F G H C I (1) 1. Place the antenna on top of the nozzle. 2. Mount the flange and tighten the bolts cross-wise. For torque information, see Table 3-9. 3.
Reference Manual Section 3: Mechanical Installation 00809-0100-4026, Rev HA November 2014 Table 3-9. Tightening Torque for Process Seal Flanges Flange 3.4.3 Torque (Nm) Torque (Lbft) 2 in. (50 mm), 150 lb. 40 30 2 in. (50 mm), 300 lb. 40 30 3 in. (75 mm), 150 lb. 60 44 3 in. (75 mm), 300 lb. 60 44 4 in. (100 mm), 150 lb. 50 37 4 in. (100 mm), 300 lb.
Reference Manual Section 3: Mechanical Installation 00809-0100-4026, Rev HA 3.4.4 November 2014 Rod antenna flanged connection Figure 3-21. Mounting the Rosemount 5400 with Rod Antenna and Flange A E B F C D G A. Transmitter housing B. Bolt C. Gasket (optional for the All PFA version) D.Nut E. Locking screw (ATEX) F. Flange G. PFA plate (only All PFA version, 1R, 2R) H. Tank flange I. Nozzle J. Rod antenna H I J (1) 1. Place a gasket on top of the tank flange (1).
Reference Manual Section 3: Mechanical Installation 00809-0100-4026, Rev HA November 2014 3.4.5 Tri-Clamp™ tank connection Figure 3-22. Mounting the Rosemount 5400 using a Tri-Clamp A. Nut B. Rod antenna C. Gasket D. Tank connection E. Tri-Clamp F. Clamp A E B F C D 40 1. Place a gasket on top of the tank flange. 2. Lower the transmitter and antenna into the tank. 3. Fasten the Tri-Clamp to the tank with a clamp. 4. To rotate the transmitter housing, loosen the nut. 5.
Reference Manual Section 3: Mechanical Installation 00809-0100-4026, Rev HA 3.4.6 November 2014 Bracket mounting on wall Figure 3-23. Bracket Mounting the Rosemount 5400, on Wall A A. Transmitter housing B. Antenna C. Bracket C B Mechanical Installation 1. Mount the bracket directly to the wall with screws suitable for the purpose. 2. Mount the transmitter with antenna to the bracket, then secure the installation with the three supplied screws.
Reference Manual Section 3: Mechanical Installation 00809-0100-4026, Rev HA November 2014 3.4.7 Bracket mounting on pipe Figure 3-24. Bracket Mounting the Rosemount 5400, on Pipe E A. U-bolts B. Bracket C. Clamping bracket D. Screws E. Transmitter housing F. Screw G. Antenna A B F C G D 42 1. Put the two U-bolts through the holes of the bracket. Holes are available for both vertical and horizontal pipe mounting. 2. Put the clamping brackets on the U-bolts and around the pipe. 3.
Reference Manual Section 4: Electrical Installation 00809-0100-4026, Rev HA Section 4 November 2014 Electrical Installation Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wiring and power supply requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable/conduit entries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Section 4: Electrical Installation 00809-0100-4026, Rev HA November 2014 Failure to follow safe installation and service guidelines could result in death or serious injury. Make sure only qualified personnel perform installation or service. Use the equipment only as specified in this manual. Failure to do so may impair the protection provided by the equipment. Any substitution of non-recognized spare parts may jeopardize safety. Repair, e.g. substitution of components etc.
Reference Manual Section 4: Electrical Installation 00809-0100-4026, Rev HA 4.3 November 2014 Cable/conduit entries The electronics housing has two entries with ½ - 14 NPT threads. Optional M20×1.5 adapters are also available. The connections shall be according to national, local, and plant electrical codes. Properly seal unused ports to prevent moisture or other contamination from entering the terminal compartment of the electronics housing.
Section 4: Electrical Installation 4.4 Reference Manual 00809-0100-4026, Rev HA November 2014 Grounding When wiring the transmitters, the grounding should be completed such that: The loop is grounded at the power supply. When transmitters are installed on metal tanks, ensure there is a metal-to-metal connection between the device and the tank. If the tank is non-metallic, the housing must be grounded to an earth ground that is separate from the power supply.
Reference Manual Section 4: Electrical Installation 00809-0100-4026, Rev HA November 2014 Note Avoid running instrument cable next to power cables in cable trays or near heavy electrical equipment. It is important that the instrument cable shield be: - trimmed close and insulated from touching the transmitter housing - continuously connected throughout the segment - connected to a good earth ground at the power supply end 4.
Reference Manual Section 4: Electrical Installation 00809-0100-4026, Rev HA November 2014 Figure 4-3. Terminal Compartment and External Ground Screw Blind plug Supplied for unused conduit opening. Terminals for signal and power supply External ground screw Cable entry NPT ½ in.-14, or M20 X 1.5 adapter Cable entry NPT ½ in.-14, or M20 X 1.5 adapter Internal ground screw Locking screw Note Remove the orange, protective, plastic plugs, used for transportation.
Reference Manual Section 4: Electrical Installation 00809-0100-4026, Rev HA November 2014 4.8 HART 4.8.1 Power requirements The Rosemount 5400 Series transmitter operates with a power supply ranging from 16 - 42.4 Vdc (16 - 30 Vdc in IS applications, 20 - 42.4 Vdc in explosion-proof / flameproof applications and in non-sparking / energy-limited applications).
Reference Manual Section 4: Electrical Installation 00809-0100-4026, Rev HA November 2014 Figure 4-5. Intrinsically Safe Installations Maximum Load Resistance R(W) Operating region External Power Supply Voltage UE(V) Figure 4-6. Explosion-Proof / Flameproof Installations Maximum Load Resistance R(W) 1400 1200 1148 1000 800 600 400 Operating region 348 200 24 10 20 42.
Reference Manual Section 4: Electrical Installation 00809-0100-4026, Rev HA 4.8.3 November 2014 Non-intrinsically safe power supply With a non-intrinsically safe power supply in non-hazardous installations or explosion-proof/flameproof installations, wire the transmitter as shown in Figure 4-7. Note Make sure the power supply is off when connecting the transmitter. Figure 4-7.
Reference Manual Section 4: Electrical Installation 00809-0100-4026, Rev HA November 2014 4.8.4 Intrinsically safe power supply With an intrinsically safe power supply, wire the transmitter as shown in Figure 4-8. Note Make sure the instruments in the loop are installed according to intrinsically safe field wiring practices. Installation also needs to comply with the applicable installation/control drawing. See “Approval drawings” on page 230. Figure 4-8.
Reference Manual Section 4: Electrical Installation 00809-0100-4026, Rev HA 4.8.5 November 2014 Type N approvals: non-sparking / energy-limited power supply With a non-sparking / energy- limited power supply, wire the transmitter as shown in Figure 4-9. Figure 4-9. Wiring Diagram for Non-Sparking / Energy-Limited Power Supply (HART) Rosemount 5400 Series Radar Level Transmitter Power Supply Load Resistance 250 W HART modem PC Field Communicator HART: Un=42.
Reference Manual Section 4: Electrical Installation 00809-0100-4026, Rev HA November 2014 4.8.6 Transient protection terminal block For a terminal block with transient protection, wire the transmitter as shown in Figure 4-10. Figure 4-10.
Reference Manual Section 4: Electrical Installation 00809-0100-4026, Rev HA November 2014 4.9 FOUNDATION fieldbus 4.9.1 Power requirements Terminals in the transmitter housing provide connections for signal wiring. The Rosemount 5400 transmitter is powered over FOUNDATION fieldbus with standard fieldbus power supplies.
Reference Manual Section 4: Electrical Installation 00809-0100-4026, Rev HA November 2014 Connecting fieldbus devices Figure 4-11. Rosemount 5400 Series Radar Transmitter Field Wiring 6200 ft (1900 m) max (depending upon cable characteristics) Integrated power conditioner and filter Terminators fieldbus segment (Spur) (Spur) (Trunk) Power supply (The power supply, filter, first terminator, and configuration tool are typically located in the control room.
Reference Manual Section 4: Electrical Installation 00809-0100-4026, Rev HA 4.9.2 November 2014 Non-intrinsically safe power supply With non-intrinsically safe power supply in Non-hazardous installations or Explosion-proof/Flameproof installations, wire the transmitter as shown in Figure 4-12. Rosemount 5400 Series Transmitters with Explosion-proof/Flameproof Output have a built-in barrier; no external barrier needed. Note Make sure that the power supply is off when connecting the transmitter.
Reference Manual Section 4: Electrical Installation 00809-0100-4026, Rev HA November 2014 4.9.3 Intrinsically safe power supply When your power supply is intrinsically safe, wire the transmitter as shown in Figure 4-13. Note Make sure that the instruments in the loop are installed in accordance with intrinsically safe field wiring practices. Installation also needs to comply with the applicable installation/control drawing. See “Approval drawings” on page 230. Figure 4-13.
Reference Manual Section 4: Electrical Installation 00809-0100-4026, Rev HA 4.9.4 November 2014 Type N approvals: non-sparking / energy-limited power supply With a non-sparking / energy-limited power supply, wire the transmitter as shown in Figure 4-14. Figure 4-14.
Section 4: Electrical Installation 4.10 Reference Manual 00809-0100-4026, Rev HA November 2014 HART to Modbus Converter (HMC) The Rosemount 5400 Series RS-485 with Modbus communication transmitter version operates using a power supply ranging from 8-30 Vdc (max. rating). See the Rosemount 5300/5400 Series with HART to Modbus Converter Manual Supplement (Document No. 00809-0500-4530) for details. Power consumption: < 0.5 W (with HART address = 1) < 1.2 W (incl. four HART slaves) 4.10.
Reference Manual Section 4: Electrical Installation 00809-0100-4026, Rev HA November 2014 Figure 4-15.
Reference Manual Section 4: Electrical Installation 00809-0100-4026, Rev HA November 2014 4.10.2 Connection terminals The connection terminals are described in Table 4-2 below: Table 4-2. Connection Terminals Connector label Description Comment HART + Positive HART connector HART - Negative HART connector Connect to PC with RRM software, Field Communicator, or other HART configurators.
Reference Manual Section 4: Electrical Installation 00809-0100-4026, Rev HA 4.10.3 4.10.
Reference Manual Section 4: Electrical Installation 00809-0100-4026, Rev HA November 2014 Alternatively, the Rosemount 5400 Series Transmitter can be installed as shown in Figure 4-18. If this wiring layout is used, there is an increased risk for communication disturbances due to differences in potential between grounding points. By using the same grounding point for Modbus Master and Power Supply, this risk is reduced. Figure 4-18.
Reference Manual Section 4: Electrical Installation 00809-0100-4026, Rev HA 4.10.5 November 2014 External HART devices (slaves) The HMC supports up to four external HART devices. The external devices are separated by using the HART address. The address must be different between the external devices and only addresses 1 to 5 are allowed for multiple slaves.
Reference Manual Section 4: Electrical Installation 00809-0100-4026, Rev HA November 2014 4.11 Establish HART communication The Rosemount 5400 Series can be configured using the RRM PC software or a Field Communicator. Configuration is done by sending HART commands through the HMC to the Rosemount 5400 transmitter electronics. To establish HART communication, connect to the MA/MB terminals, or to the HART terminals. Both alternatives are described below. 4.11.
Reference Manual Section 4: Electrical Installation 00809-0100-4026, Rev HA November 2014 3. Enable HART communication and make sure the port for the RS-485 Converter is selected. Use the following settings: 4. Connect the power wires (or cycle power) to the transmitter. 5. Wait 20 seconds and then open the Search Device window in RRM (also see Note on page 68). Make sure HART address 1 is being scanned. 6. Connect to the transmitter and perform the necessary configuration. 7.
Section 4: Electrical Installation Reference Manual 00809-0100-4026, Rev HA November 2014 Note Take the following into consideration if there are multiple Rosemount 5400 Modbus units on the bus: By default, the transmitters have HART address 1. It will not be possible to establish communication on HART address 1 if several transmitters have the same address. In this case, there are alternative solutions to establish communication: 4.11.2 1.
Reference Manual Section 4: Electrical Installation 00809-0100-4026, Rev HA November 2014 4.12 Optional devices 4.12.1 Tri-Loop™ HART to analog converter The Rosemount 5400 Series transmitter outputs a HART signal with four process variables. The Model 333 HART Tri-Loop provides up to three additional analog 4-20 mA outputs. Figure 4-22. Wiring Diagram for HART Tri-Loop DIN rail mounted HART Tri-Loop Ch. 3 Ch. 2 Ch.
Reference Manual Section 4: Electrical Installation 00809-0100-4026, Rev HA November 2014 4.12.2 751 Field Signal Indicator Figure 4-23.
Reference Manual Section 4: Electrical Installation 00809-0100-4026, Rev HA 4.12.3 November 2014 Smart Wireless THUM™ Adapter The Rosemount 5400 Series can be combined with the Smart Wireless THUM Adapter. For more information, see the Smart Wireless THUM™ Adapter for Rosemount Process Level Transmitter Applications Technical Note (Document No. 00840-0100-4026) and the Smart Wireless THUM™ Adapter Reference Manual (Document No. 00809-0100-4075). Figure 4-24.
Section 4: Electrical Installation November 2014 72 Reference Manual 00809-0100-4026, Rev HA Electrical Installation
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 Section 5 Basic Configuration/Start-up Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Basic configuration parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Section 5: Basic Configuration/Start-up 5.2 Reference Manual 00809-0100-4026, Rev HA November 2014 Overview The configuration of a Rosemount 5400 Series transmitter is normally a simple and straightforward task. If the transmitter is pre-configured at the factory according to ordering specifications in the Configuration Data Sheet, no further basic configuration is required, unless tank conditions have changed.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 To communicate with the transmitter using RRM, a HART modem (part number 03300-7004-0001 or 03300-7004-0002) or a FOUNDATION fieldbus modem (part number 03095-5108-0001 for PCMCIA) is required. For FOUNDATION fieldbus communication you will also need the National Instruments Communication Manager software (see “Installing the RRM software for FOUNDATION fieldbus” on page 88). 5.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 Figure 5-2. Upper Reference Point Rod antenna with threaded tank connection Rod antenna with flange Cone antenna Process seal antenna Flange Adapter Upper reference point Tank type and tank bottom type The Rosemount 5400 Series transmitter is optimized according to the Tank Type and Tank Bottom Type configuration by automatically setting some parameters to predefined default values.
Reference Manual 00809-0100-4026, Rev HA Section 5: Basic Configuration/Start-up November 2014 Pipe diameter When the transmitter is mounted in a still-pipe, the inner diameter of the pipe must be specified. The pipe diameter is used to compensate for the lower microwave propagation speed inside the pipe. An incorrect value gives a scale factor error. If locally supplied still-pipes are used, make sure the inner diameter is noted before the pipe is installed.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 5.3.4 Volume configuration For volume calculations, choose one of the standard tank shapes or the strapping option. Select None if volume calculation is not used. For the standard tanks, a Volume Offset parameter can be specified which can be used for a non-zero volume that corresponds to the zero level. This may be useful, for example, if the user wants to include the product volume below the zero level.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 Standard tank shapes Figure 5-4. Standard Tank Shapes Vertical cylinder Diameter Height Vertical cylinder tanks are specified by diameter, height, and volume offset. Horizontal cylinder Diameter Horizontal cylinder tanks are specified by diameter, height, and volume offset. Height Vertical bullet Diameter Height Vertical bullet tanks are specified by diameter, height, and volume offset.
Section 5: Basic Configuration/Start-up Reference Manual 00809-0100-4026, Rev HA November 2014 Strapping table The Strapping Table option is used when the tank shape deviates significantly from an ideal sphere or cylinder, or when high volume accuracy is required. The Strapping Table divides the tank into segments. Level values and corresponding volumes are entered at the bottom of the tank.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA 5.3.5 November 2014 Analog output (HART) For the analog output, the output source (primary value), range values, and alarm mode are specified. Figure 5-6.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 Freeze Current: the output current is set to the last valid value at the time when the error occurs. Default settings for alarm mode: Measurement errors: Output current = High Measured value out of range: transmitter enters saturation mode (if Limit Alarm is disabled) Table 5-2. Analog Output: Standard Alarm Value vs. Saturation Value Level 4–20 mA saturation value 4–20 mA alarm value Low 3.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 Distance calibration 1. Measure the actual distance between the Upper Reference Point and the product surface. 2. Adjust the Calibration Distance so that the Distance measured by the transmitter corresponds to the actual distance. The Calibration Distance parameter is available via HART command [2, 3, 2, 4, 1], or RRM: a. Select the Tank icon under Device Config/Setup in the RRM workspace. b.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 5.3.8 ATC Setting up an ATC makes tracking of the product surface more robust in the presence of noise and weak disturbing echoes. The ATC is normally used for filtering out disturbances with an amplitude smaller than the amplitude of the product surface echo. The ATC is designed as a number of individually adjustable amplitude threshold points. Amplitude, mV Figure 5-8.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 Software Operating Systems supported: 5.4.2 Windows XP Windows 7 Help in RRM From the Help menu, select the Contents option to access help information. Help is also available from a Help button in most windows. 5.4.3 Installing the RRM software for HART communication To install the RRM: 1. Insert the installation CD into the CD-ROM drive. 2.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 Getting started 1. From the Start menu, select Programs > Rosemount > Rosemount Radar Master or select the RRM icon in the Windows workspace. 2. If the Search Device window did not appear automatically, select menu option Device > Search. 3. In the Search Device window, select communication protocol HART and select the Start Scan button (select the Advanced button to specify start and stop address).
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA 5.4.4 November 2014 Specifying the COM port If communication is not established, open the Communication Preferences window and check that the correct COM Port is selected: 1. From the View menu, select Communication Preferences in RRM. Figure 5-9. Communication Settings 2. Make sure that HART communication is enabled. 3. Check which COM port is connected to the modem. 4.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 5.4.5 To set the COM port buffers The COM port Receive Buffer and Transmit Buffer need to be set to 1 by doing the following: 5.4.6 1. In the Microsoft® Windows Control Panel, open the System option. 2. Select the Hardware tab and click the Device Manager button. 3. Expand the Ports node in the tree view. 4. Click the right mouse button on the selected COM port and then select Properties. 5.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 Getting started 1. Before starting RRM make sure that appropriate settings are made with the National Instruments Interface Configuration Utility: Use the following settings: Device address = Visitor Device Type = Link Master Device Usage = NI-FBUS 2. Start RRM: from the Start menu click Programs > Rosemount > Rosemount RadarMaster or click the RRM icon in the Microsoft Windows workspace. 3.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 6. Select the desired transmitter and click OK to connect. In the RRM Status Bar, verify that RRM communicates with the transmitter: RRM communicates with the transmitter No communication with the transmitter 5.4.8 Specifying measurement units Measurement units for data presentation in RRM can be specified when the RRM program is installed. Units can also be changed as follows: 90 1.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA 5.4.9 November 2014 Using the Setup functions Use the Setup function if you are already familiar with the configuration process for the Rosemount 5400 Series transmitter or for changes to the current settings: Figure 5-10. Setup Functions in RRM 1. Start the RRM software. 2.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 5.4.10 Guided setup The following description tells how to use the RRM Guided Setup. The corresponding HART commands (Field Communicator Fast Key Sequence) are also shown. The Guided Setup is useful for those unfamiliar with the Rosemount 5400 Series transmitter. Guided Setup and Configuration Wizard Run Wizard 1. Start the RRM program. RRM automatically presents a list of available transmitters.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 Device Information 4. The Tag, Message, Descriptor, and Date information is entered in this window. This information is not required for the operation of the transmitter and may be left out, if desired. HART command: [2, 2, 1]. Digital Units 5. Basic Configuration/Start-up The Length Unit, Level Rate Unit, Volume Unit, and Temperature Unit information is entered in this window.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 Tank Geometry 6. Select the Tank Type corresponding to the actual tank. If none of the available options matches the tank, select Unknown. HART command: [2, 1, 2, 1]. FOUNDATION fieldbus parameter: TRANSDUCER_1100 > GEOM_TANK_TYPE. Tank Bottom Type is important for the measurement performance close to the tank bottom. HART command: [2, 1, 2, 2].
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 Tank Environment 7. In the Process Condition box, select the check-boxes that correspond to the conditions of the tank. Select as few options as possible and no more than two. See “Process conditions” on page 77 for more information. FOUNDATION fieldbus parameter: TRANSDUCER_1100 > ENV_ENVIRONMENT.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 Analog output 9. Typically, the Primary Variable (PV) is configured to be Product Level or Volume. Set the analog output range by inputting the Lower Range Value (4 mA) and the Upper Range Value (20 mA) to the desired values. The Alarm Mode specifies the output state when a measurement error occurs. HART command: [2, 1, 5].
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 Measure and Learn function 12. Select the Yes button to run the Measure and Learn function. If No is selected, this function can be run at a later stage using the Spectrum Analyzer in RRM. Make sure there is no filling or emptying occurring when the Measure and Learn function is used. Tank precondition settings 13. The Measure and Learn function creates an ATC automatically and suggests False Echo Areas.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 Restart the transmitter 15. Restart the transmitter to activate all of the configuration changes. It may take up to 60 seconds after the restart button is pressed before measurement values are updated. Verify Level 16. Run the Verify Level tool to match the product level reported by the device to a reference measurement (measured by using for example hand gauging).
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 Guided Setup complete 18. The Guided Setup is now complete. To exit the Guided Setup, select the Close button.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 5.4.11 Using the Setup functions Use the Setup function if you are already familiar with the configuration process for the Rosemount 5400 Series transmitter or to change the current settings: Figure 5-11. Setup Functions in RRM 1. Start the RRM software. 2.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA 5.5 November 2014 Configuration using a Field Communicator This section describes the configuration of a Rosemount 5400 Series transmitter with a Field Communicator. The menu tree with the various configuration parameters is shown in Figure 5-14 on page 103. Section “Basic configuration parameters” on page 75 describes the basic configuration parameters.
Section 5: Basic Configuration/Start-up Reference Manual 00809-0100-4026, Rev HA November 2014 To make a basic setup of the transmitter, do the following: 1. Check that the desired Measurement Units are selected. HART command: [2, 1, 1, 5]. 2. Enter configuration parameters for the following: Device info. HART command: [2, 2, 1] Geometry. HART command: [2, 1, 2] Environment. HART command: [2, 1, 3] Volume. HART command: [2, 1, 4] Analog Out. HART command: [2, 1, 5] 3.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 Figure 5-14.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 Table 5-4.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA 5.7 November 2014 Basic configuration using AMS Suite The Rosemount 5400 Series transmitter can be configured using the AMS Suite software: 1. Start the AMS Device Manager making sure the transmitter is connected. The transmitter is displayed in the Device Connection View window (pictures correspond to AMS version 9.0). 2. In the Device Connection View, right click the transmitter icon. 3. Select the Configure option. 4.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 5.8 Configuration using DeltaV The following description shows how to configure a Rosemount 5400 Series transmitter using DeltaV with the AMS application. The corresponding FOUNDATION fieldbus parameters are also shown. The Rosemount 5400 Series supports DD Methods for DeltaV in order to facilitate transmitter configuration. 1. Select DeltaV > Engineering > DeltaV Explorer from the Start menu. 2.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 5. Select the Level Measurement setup button. 6. Choose the Tank Type which corresponds to the actual tank. If none of the available options matches the actual tank, choose Unknown. FOUNDATION fieldbus parameter: TRANSDUCER_1100 > GEOM_TANK_TYPE. 7. Tank Bottom Type is important for the measurement performance close to the tank bottom.
Section 5: Basic Configuration/Start-up Reference Manual 00809-0100-4026, Rev HA November 2014 10. Select the Environment tab. 11. In the Process Conditions box select the check-boxes that correspond to the conditions in your tank. You should select as few options as possible and not more than two. See “Process conditions” on page 77 for more information. FOUNDATION fieldbus parameter: TRANSDUCER_1100 > ENV_ENVIRONMENT. Choose the Product Dielectric Constant that corresponds to the current product.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 12. To configure volume calculation, select the ADV_CONFIG_TB_1300 block and choose the Volume tab.
Section 5: Basic Configuration/Start-up Reference Manual 00809-0100-4026, Rev HA November 2014 13. Choose a pre-defined calculation method based on a tank shape that corresponds to the actual tank. A. Choose None if volume calculation is not desired. B. Use Volume Offset if you do not want zero volume and zero level to match (for example, if you want to include the product volume below the zero level).
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA 5.8.1 November 2014 Advanced configuration False echo registration 1. In the AMS/DeltaV Explorer select the desired transmitter icon, click the right mouse button and choose the Configure option. 2. Select Manual Setup and choose the Echo Tuning tab. 3. Click the Register False Echo button and follow the wizard to choose and register echoes which can be identified as disturbing objects in the tank.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 5.9 FOUNDATION fieldbus overview The configuration of a Rosemount 5400 Series transmitter is normally a simple and straightforward task. If the transmitter is pre-configured at the factory according to the ordering specifications in the Configuration Data Sheet, no further Basic Configuration is required unless tank conditions have changed.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA 5.9.1 November 2014 Assigning device tag and node address A Rosemount 5400 Series transmitter is shipped with a blank tag and a temporary address (unless specifically ordered with both) to allow a host to automatically assign an address and a tag. If the tag or address need to be changed, use the features of the configuration tool. The tool basically does the following: 1.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 Resource block There are no linkable inputs or outputs to the Resource block. Analog-Input Block Figure 5-16. Analog-Input Block OUT_D AI OUT OUT = The block output value and status OUT_D = Discrete output that signals a selected alarm condition The AI function block processes field device measurements and makes them available to other function blocks.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 5.10 Application examples 5.10.1 Radar level transmitter - level value Situation A level gauge is measuring the level in a 33 ft (10 m) high tank. Figure 5-17. Situation Diagram 100 % 33 ft (10 m) 0% Solution Table 5-5 lists the appropriate configuration settings, and Figure 5-18 illustrates the correct function block configuration. Table 5-5.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 5.10.2 Radar level transmitter - level value in percent (%) Situation The level of a tank is to be measured using the Rosemount 5400 Series mounted on a nozzle on the top of the tank. The maximum level in the tank is 46 ft (14 m). The level value will be displayed in percentage of the full span (see Figure 5-19). Figure 5-19.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA 5.11 November 2014 Tri-Loop™ HART to Analog Converter The Rosemount 333 HART Tri-Loop HART-to-Analog Signal Converter is capable of converting a digital HART burst signal into three additional 4-20 mA analog signals. To set the Rosemount 5400 Series transmitter up for the HART Tri-Loop: 1. Make sure the Rosemount 5400 transmitter is properly configured. 2.
Reference Manual Section 5: Basic Configuration/Start-up 00809-0100-4026, Rev HA November 2014 5. Select Burst option 3 = Process variables and current (Process vars/crnt). HART command [2, 2, 4, 2, 2]. 6. Install the Tri-Loop. Connect Channel 1 wires, and optionally wires for Channel 2 and Channel 3. 7. Configure Tri-Loop Channel 1: a. Assign variable: Tri-Loop HART command [1, 2, 2, 1, 1]. Make sure that the SV, TV, and QV match the configuration of the Rosemount 5400 Series transmitter. b.
Reference Manual Section 6: Operation 00809-0100-4026, Rev HA Section 6 November 2014 Operation Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Viewing measurement data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LCD display error messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LED error messages . .
Reference Manual Section 6: Operation 00809-0100-4026, Rev HA November 2014 6.2 Viewing measurement data 6.2.1 Using the display panel The Rosemount 5400 Series transmitter uses an optional display panel to present measurement data.
Reference Manual Section 6: Operation 00809-0100-4026, Rev HA November 2014 Using RRM The LCD tab in the General window allows variables to be specified for view on the Display Panel screen: 1. Choose the General option from the Setup menu, or click the General icon in the Device Configuration window. Device Config General 2. Select the LCD tab. Figure 6-2. RRM lets you Specify Variables for the Rosemount 5400 Series Display Panel Operation 3.
Reference Manual Section 6: Operation 00809-0100-4026, Rev HA November 2014 Using AMS and DeltaV The LCD tab in the Configure window specifies which variables will be shown on the Display Panel screen: 1. Select the transmitter icon in the AMS and DeltaV explorer. 2. Click the right mouse button and choose the Configure option. 3. Select Manual Setup and choose the Display tab to set the desired LCD display parameters and LCD display measurement units.
Reference Manual Section 6: Operation 00809-0100-4026, Rev HA November 2014 LCD display parameters Table 6-1. LCD Display Parameters and Presentation on Display Operation Parameter Presentation on display Description Level LVL Product level. Distance DST Distance from the upper reference point to the product surface. Level Rate LR The speed of level movement up or down. Signal Strength AMP The signal amplitude of the surface echo. Volume Only measurement unit is shown.
Section 6: Operation 6.2.3 Reference Manual 00809-0100-4026, Rev HA November 2014 Viewing measurement data in RRM To view measurements, such as level, signal strength, etc. in RRM, choose the Tools > Device Display option and select the Level tab: Figure 6-4. Presentation of Measurement Data in RRM To view the Analog Output signal, choose the Tools > Device Display option and select the Analog Out tab: Figure 6-5.
Reference Manual Section 6: Operation 00809-0100-4026, Rev HA 6.2.4 November 2014 Viewing measurement data in AMS Suite and DeltaV To view measurements, such as level, signal strength, etc. in the AMS Suite: 1. Select the transmitter icon in the AMS Suite Device Connection View window. 2. Click the right mouse button and choose the Overview option. Figure 6-6.
Reference Manual Section 6: Operation 00809-0100-4026, Rev HA November 2014 6.3 LCD display error messages Figure 6-7. The Rosemount 5400 Series Display Panel Displaying an Error Message Error message Table 6-2. Error Messages Displayed on the Rosemount 5400 Series Display Panel Error message Description RAM FAIL An error in the gauge data memory (RAM) has been detected during the startup tests. NOTE: this resets the gauge automatically.
Reference Manual Section 6: Operation 00809-0100-4026, Rev HA 6.4 November 2014 LED error messages For Rosemount 5400 Series transmitters without a display, a flashing Light Emitting Diode (LED) is used to present error messages. Figure 6-8. Rosemount 5400 Series Transmitters without Display use a LED for the Presentation of Error Messages Flashing LED In normal operation, the LED flashes orange once every other second.
Section 6: Operation November 2014 128 Reference Manual 00809-0100-4026, Rev HA Operation
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA Section 7 November 2014 Service and Troubleshooting Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Troubleshooting overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Service overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Section 7: Service and Troubleshooting Reference Manual 00809-0100-4026, Rev HA November 2014 Failure to follow safe installation and service guidelines could result in death or serious injury. Make sure only qualified personnel perform installation or service. Use the equipment only as specified in this manual. Failure to do so may impair the protection provided by the equipment.
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA 7.2 November 2014 Troubleshooting overview Table 7-1 below gives information on the possible causes of system malfunctions. It also lists the symptoms and necessary actions to be taken. Table 7-1.
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA November 2014 7.3 Service overview The functions mentioned in this section are available in the RRM configuration program. 7.3.1 Analyzing the measurement signal RRM, and other tools using enhanced EDDL, has powerful functions for advanced troubleshooting. By using the Echo Curve plot function, an instant view of the tank signal is displayed.
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA November 2014 The surface thresholds should be set to approximately 20 % of the measured signal amplitude of the product surface. False echo area. False Echo Areas are set during the Measure and Learn function (see “Guided setup” on page 92), when the disturbing object is larger than the surface echo. The False Echo Area can be adjusted manually. Hold off distance - upper null zone.
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA November 2014 Figure 7-3. Example 2: Surface Threshold is Too Low Amplitude, mV Reference Actual surface P1 - Disturbing echo misinterpreted as product surface Surface threshold = ATC Distance, m By adjusting the surface threshold, the product surface is properly detected, as illustrated in Figure 7-4: Figure 7-4.
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA 7.3.3 November 2014 Registration of false echoes The False Echo function improves the performance of the gauge when the surface is close to a horizontal surface of a static object in the tank. The object causes an echo when it is above the surface. When the echoes from the surface and the object are close to each other, they may interfere and cause a decrease in performance. Figure 7-5.
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA November 2014 Figure 7-6. Disturbing Echoes can be Filtered Out by Registration as False Echoes Amplitude, mV Registered false echo Distance, m The False Echo Registration function is available in the RRM program, in the AMS Suite, as well as for the Field Communicator.
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA 7.3.4 November 2014 Using the Echo Curve Analyzer The Echo Curve in RRM shows the measurement signal amplitude in the tank and includes the Echo Tuning functionality (see “Echo tuning” on page 83 for more information on false echo handling). To plot the measurement signal: 1. Start the RRM program. 2. Open Device Config/Tools (or Device Config/Setup). 3. Click the Echo Curve icon (see Figure 7-7). Figure 7-7.
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA November 2014 The Configuration Mode tab The Configuration Mode tab allows for adjustment of the different amplitude thresholds. When clicking the Echo Curve icon under Device Config/Setup, the Echo Curve Analyzer window appears with the Configuration Mode tab selected: Figure 7-8.
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA November 2014 The View/Record Mode tab The View/Record Mode tab presents a plot of the current tank conditions where each radar echo is displayed as a peak in the signal plot. When clicking the Echo Curve icon under Device Config/Tools, the Echo Curve Analyzer window appears with the View/Record Mode tab selected: Figure 7-9.
Section 7: Service and Troubleshooting 7.3.5 Reference Manual 00809-0100-4026, Rev HA November 2014 Using the Echo Curve Analyzer with a Field Communicator The Field Communicator supports the EDDL with enhancements that allows viewing of the Echo Curve, creating an ATC, and specifying amplitude thresholds, such as the Surface Threshold. Viewing the Echo Curve To view the Echo Curve: 1. Select HART command [2, 5, 2, 3].
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA November 2014 Register false echoes To register false echoes: 1. Select HART command [2, 5, 1]. Peaks 1 2 3 4 5 Found Echo Peaks Measurement Output Registered False Echoes Add False Echo... Remove False Echo... 2. Select option 1 Found Echo Peaks to display found echoes. 3. Select option 2 Add False Echo... to register false echoes based on distance. Threshold settings To adjust the amplitude thresholds: 1.
Section 7: Service and Troubleshooting 7.4 Reference Manual 00809-0100-4026, Rev HA November 2014 Analog Output calibration This function calibrates the Analog Output by comparing the actual output current with the nominal 4 mA and 20 mA currents. Calibration is done at the factory and normally the transmitter does not need to be recalibrated. The Analog Output calibration function is available via the HART command [2, 7, 1]. In RRM, this function is available via Setup > Output.
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA 7.5 November 2014 Logging measurement data By using the Log Device Registers function in the RRM software, Input and Holding registers are logged over time. It is possible to choose from different pre-defined sets of registers. This function is useful for verifying that the transmitter is working properly.
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA November 2014 7.6 Backing up the transmitter configuration Use this RRM option to make a backup copy of the configuration parameters in the transmitter database. The backup file can be used to restore the transmitter configuration. It can also be used for configuration of a transmitter in a similar application. Parameters in the saved file can be uploaded directly to the new device.
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA 7.7 November 2014 Diagnostics The following information about the device can be retrieved: “Device status” on page 153 “Errors” on page 154 “Warnings” on page 155 “Measurement status” on page 155 “Volume calculation status” on page 157 “Analog Output status” on page 158 RRM To open the Diagnostics window in RRM, choose the Diagnostics option from the Tools menu.
Section 7: Service and Troubleshooting Reference Manual 00809-0100-4026, Rev HA November 2014 AMS and DeltaV To view the Diagnostics window in AMS Suite, click the right mouse button on the desired transmitter and choose the Configure option. Select Service Tools and the tab Active Alerts.
Reference Manual 00809-0100-4026, Rev HA 7.8 Section 7: Service and Troubleshooting November 2014 Configuration report This RRM function shows the configuration changes made to the transmitter compared to the factory configuration. The report compares a specified backup file with the default transmitter configuration.
Section 7: Service and Troubleshooting 7.9 Reference Manual 00809-0100-4026, Rev HA November 2014 Viewing input and holding registers Measured data is continuously stored in the Input Registers and by viewing the contents, advanced users can check if the transmitter is working properly. The Holding Registers store various transmitter parameters, such as configuration data, used to control the measurement performance.
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA 7.10 November 2014 Reset to factory settings This function resets all, or a specific part, of the holding registers to the factory settings. It is recommended that a backup of the configuration be made before resetting, so the old transmitter configuration can be loaded, if necessary. RRM: choose menu option Tools > Factory Settings. AMS Suite: Tools / Service > Factory Settings. HART Command: [1, 2, 8]. AMS and DeltaV 1.
Section 7: Service and Troubleshooting 7.11 Reference Manual 00809-0100-4026, Rev HA November 2014 Surface search The Surface Search command triggers a search for the product surface and can be used, for example, if the measured level is locked onto a disturbing object in the tank (see “Configuration report” on page 147). AMS and DeltaV 1. In the AMS and DeltaV explorer select Configure/Manual setup, choose the Echo Tuning tab, and select Search for Surface. Search for Surface 2.
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA 7.12 November 2014 Using the Simulation Mode This function can be used to simulate measurements and alarms. RRM: choose menu option Tools > Simulation Mode: AMS Suite: Tools > Service > Simulation Mode. HART Command: [3, 2, 1, 3]. AMS and DeltaV 1.
Section 7: Service and Troubleshooting 7.13 Reference Manual 00809-0100-4026, Rev HA November 2014 Write protecting a transmitter A Rosemount 5400 Series transmitter can be password protected from unintentional configuration changes. The default password is 12345 and it is recommended that this password not be changed to facilitate service and maintenance of the transmitter. RRM: Tools > Lock / Unlock Configuration Area. AMS Suite: Tools > Service > Lock / Unlock Device. HART Command [3, 2, 1, 2].
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA November 2014 7.14 Diagnostic messages 7.14.1 Troubleshooting If there is a malfunction, despite no diagnostic messages, see Table 7-1 on page 131 for information on possible causes. Note If the transmitter housing needs to be removed for service, make sure the antenna PTFE sealing is carefully protected against dust and water. 7.14.
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA November 2014 7.14.3 Errors Error messages that may be displayed on the Integral Display, on a Field Communicator, in AMS, or in the RRM program, are shown in Table 7-3. Errors normally result in an Analog Output alarm. Errors are indicated in RRM in the Diagnostics window. Table 7-3.
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA 7.14.4 November 2014 Warnings Table 7-4 is a list of diagnostic messages that may be displayed on the Integral Display, on the Field Communicator, or in the RRM program. Warnings are less serious than errors, and in most cases, do not result in Analog Output alarms. Warnings are indicated in RRM in the Diagnostics window. Table 7-4. Warning Messages 7.14.
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA November 2014 Message Description Action Tank signal clip warning The last Tank Signal was clipped. No surface echo The Surface Echo Pulse cannot be detected. Predicted level The presented level is predicted. The surface echo could not be detected. The sampling of the last tank signal failed. The given volume value is invalid. The simulation mode is active. The presented measurement values are simulated.
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA 7.14.6 November 2014 Volume calculation status Volume calculation status messages that may appear on the integral display, on the Field Communicator, or in the RRM program are shown in Table 7-6. Table 7-6. Volume Status Message Description Action Level is below lowest strapping point. Level is above highest strapping point. The measured level is below the lowest point in the given strapping table.
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA November 2014 7.14.7 Analog Output status Analog Output status messages that may appear on the integral display, on the Field Communicator or in the RRM program are shown in Table 7-7. Table 7-7. Analog Output Status Message Description Action Not connected Analog output hardware is not connected. Alarm mode The analog output is in Alarm Mode. Contact Emerson Process Management Service Department.
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA 7.14.8 November 2014 Application errors When product surface is near the tank bottom, the transmitter enters alarm mode (see “Alarm mode” on page 81). May be caused by reduction of projected surface area close to sloping tank bottom.
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA November 2014 Measured value is locked. May be caused by a disturbing object in the tank Action: • Remove the disturbing object • Move the transmitter to another position • Use the Echo Tuning function in RRM to register the false echo causing the transmitter to lock at the wrong level, see “Echo tuning” on page 83 • Put an inclined metal plate on top of the disturbing object Measured value drops to zero level.
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA November 2014 Incorrect measurement level when the product surface is above the 50 % level.
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA November 2014 Alarm The transmitter displays “measurement error” and activates Measurement Alarm when the product level is close to the antenna. May be caused by: The measured level is unstable.
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA 7.15 November 2014 Troubleshooting If there is a malfunction despite the absence of diagnostic messages, see Table 7-8 for information on the possible causes. Note If the transmitter housing must be removed for service, make sure that the PTFE seal is carefully protected against dust and water. Table 7-8.
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA November 2014 Symptom Possible cause Configuration Reg Password Enabled Action Information, Ready Write Data DB Error/ Microwave Unit Error/ Configuration Error/ Other Error • Restart transmitter • Download Application Software • Set database to default; load default Database • Call Service Center SW Error/ Display Error/ Analog Out Error • Restart transmitter • Call Service Center (1) A malfunctioning display panel
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA November 2014 Table 7-11. Resource Block DETAILED_STATUS with Recommended Action Messages Condition name LOI transducer block error Sensor transducer block error Mfg. block integrity error Non-volatile memory integrity error ROM integrity error 7.15.2 Recommended action 1. Restart processor 2. Check display connection 3. Call service center 1. Restart processor 2. Check Rosemount 5400 cable 3. Call service center 1.
Reference Manual Section 7: Service and Troubleshooting 00809-0100-4026, Rev HA November 2014 Condition number Condition name and description 7 Input failure/process variable has bad status: The hardware is bad, or a bad status is being simulated Power up Out of service: The actual mode is out of service 14 15 Table 7-15.
Reference Manual Section 8: Safety Instrumented Systems (4-20 mA Only) 00809-0100-4026, Rev HA Section 8 November 2014 Safety Instrumented Systems (4-20 mA Only) Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Functional specifications . . . . . . . . . . . . . . . . . . . . .
Reference Manual Section 8: Safety Instrumented Systems (4-20 mA Only) 00809-0100-4026, Rev HA November 2014 Any substitution of non-authorized parts or repair, other than exchanging the complete transmitter head or antenna assembly, may jeopardize safety and is prohibited. Unauthorized changes to the product are strictly prohibited as they may unintentionally and unpredictably alter performance and jeopardize safety.
Reference Manual Section 8: Safety Instrumented Systems (4-20 mA Only) 00809-0100-4026, Rev HA 8.2.2 November 2014 Skill level of personnel It is assumed that the personnel installing, configuring, and operating the system have the knowledge equal or greater than that of a qualified Instrument Technician familiar with safety-related systems, process control applications, and general instrument use.
Reference Manual Section 8: Safety Instrumented Systems (4-20 mA Only) 00809-0100-4026, Rev HA November 2014 The HART loop must be referenced to ground in one point located between the power supply and the load resistor. Either the negative or the positive pole of the power supply can be ground referenced, depending on the placement of the load resistor. See Figure 8-1 as an example. Figure 8-1.
Reference Manual Section 8: Safety Instrumented Systems (4-20 mA Only) 00809-0100-4026, Rev HA 8.5 November 2014 Configuration Use a HART-compliant master, such as RRM or a Field Communicator, to communicate with and verify configuration of the Rosemount 5400 Series. A full review of configuration methods is available in Section 5: Basic Configuration/Start-up. These instructions are applicable to the 5400 QS option with any differences noted.
Reference Manual Section 8: Safety Instrumented Systems (4-20 mA Only) 00809-0100-4026, Rev HA November 2014 8.5.3 Amplitude threshold For amplitude thresholds, verify that: the Amplitude Threshold is at least 50 % greater than the amplitude of disturbances. For example, if the amplitude of disturbance is 1000 mV, the Amplitude Threshold should be at least 1500 mV.
Reference Manual Section 8: Safety Instrumented Systems (4-20 mA Only) 00809-0100-4026, Rev HA November 2014 Proof test This test detects approximately 95 % of the possible Dangerous Undetected (DU) failures of the transmitter. Note that prior to conducting the test, the echo curve should be inspected to ensure that no disturbing echoes affecting the measurement performance are present in the tank. Required Tools: HART host/communicator and mA meter. 1.
Reference Manual Section 8: Safety Instrumented Systems (4-20 mA Only) 00809-0100-4026, Rev HA November 2014 8.7 References 8.7.1 Specifications The Rosemount 5400 Series must be operated in accordance with the functional and performance specifications provided in Appendix A: Reference Data. 8.7.2 Failure rate data The FMEDA report includes failure rates and common cause Beta factor estimates. The full report is accessible at www.emersonprocess.com/rosemount/safety/PriorUse.htm. 8.7.
Reference Manual Section 8: Safety Instrumented Systems (4-20 mA Only) 00809-0100-4026, Rev HA November 2014 SIS Safety Instrumented System – Implementation of one or more Safety Instrumented Functions. A SIS is composed of any combination of sensor(s), logic solver(s), and final element(s).
Section 8: Safety Instrumented Systems (4-20 mA Only) November 2014 176 Reference Manual 00809-0100-4026, Rev HA Safety Instrumented Systems (4-20 mA Only)
Reference Manual Appendix A: Reference data 00809-0100-4026, Rev HA November 2014 Appendix A Reference Data Functional specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Performance specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Physical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Appendix A: Reference data 00809-0100-4026, Rev HA November 2014 A.1.2 4-20 mA HART® (output option code H) Output Two-wire 4–20 mA, HART Revision 5. Digital process variable is superimposed on 4–20 mA signal, and available to any host that conforms to the HART protocol. The HART signal can be used in a multidrop mode. Figure A-1.
Reference Manual Appendix A: Reference data 00809-0100-4026, Rev HA November 2014 Smart Wireless THUM™ Adapter The optional Smart Wireless THUM adapter can be mounted directly on the transmitter or by using a remote mounting kit. IEC 62591 (WirelessHART®) enables access to multi-variable data and diagnostics, and adds wireless to almost any measurement point.
Reference Manual Appendix A: Reference data 00809-0100-4026, Rev HA November 2014 Saturation levels Standard: Low=3.9 mA, High=20.8 mA Namur NE43: Low = 3.8 mA, High = 20.5 mA Figure A-5. Alarm Levels Rosemount alarm level Normal operation 3.75 mA(1) 4 mA 21.75 mA(2) 20 mA 3.9 mA low saturation 20.8 mA high saturation (1) Transmitter Failure, hardware or software alarm in Low position. (2) Transmitter Failure, hardware or software alarm in High position.
Reference Manual Appendix A: Reference data 00809-0100-4026, Rev HA November 2014 Figure A-8. Explosion-Proof/Flameproof Installations Maximum Load Resistance R() 1400 1200 1148 1000 800 600 400 Operating region 348 200 24 10 20 42.4 30 40 50 External Power Supply Voltage UE(V) Note The diagram is only valid if the HART load resistance is at the + side and if the - side is grounded, otherwise the load resistance value is limited to 435 . A.1.
Reference Manual Appendix A: Reference data 00809-0100-4026, Rev HA November 2014 External power supply The input voltage UI for FOUNDATION fieldbus is 9-32 Vdc (9-30 Vdc in IS applications, 9-17.5 Vdc in FISCO applications, and 16-32 Vdc in Explosion-proof / flameproof applications).
Reference Manual Appendix A: Reference data 00809-0100-4026, Rev HA November 2014 Figure A-10.
Reference Manual Appendix A: Reference data 00809-0100-4026, Rev HA November 2014 Figure A-11. RS-485 with Modbus Communication Rosemount 5400 Series Transmitter Power Modbus, Levelmaster Emulation / RS-485 Control system HART modem RS-232 / RS-485 converter 475 Field Communicator PC 5400 Setup in Rosemount Radar Master via Tunneling PC 5400 Setup in Rosemount Radar Master External power supply The input voltage Ui for Modbus is 8-30 Vdc (max. rating). Power consumption: < 0.
Reference Manual 00809-0100-4026, Rev HA Appendix A: Reference data November 2014 Signal wiring Two-wire half duplex RS-485 Modbus. Use shielded twisted pair wiring, preferably with an impedance of 120 (typically 24 AWG), in order to comply with EIA-485 standard and EMC regulations. Ground (common mode) voltage limit ±7V Bus termination Standard RS-485 bus termination per EIA-485 A.1.5 Display and configuration Integral display (option code M1) 5-digit integral display.
Appendix A: Reference data Reference Manual 00809-0100-4026, Rev HA November 2014 Output units Level and distance: ft, in., m, cm, or mm Volume: ft3, in.
Reference Manual Appendix A: Reference data 00809-0100-4026, Rev HA A.1.7 November 2014 Temperature and pressure limits Ambient temperature Verify that the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations certifications, see Table A-1. Table A-1.
Reference Manual Appendix A: Reference data 00809-0100-4026, Rev HA November 2014 Figure A-14. Rosemount 5401 with Rod Antenna (Model Code: 1R-4R) Pressure psig (bar) Rod Antennas 145 (10) Operating range The final rating may be limited by flange and O-ring selection. -14 (-1) -40 (-40) 302 (150) Flange temperature °F (°C) Figure A-15. Rosemount 5402 with Process Seal Antenna (Model Code: 2P-4P) Pressure psig (bar) 120 (8.2) Process Seal Antennas 90 (6.
Reference Manual Appendix A: Reference data 00809-0100-4026, Rev HA November 2014 Flange connection rating See Table A-3 for the conditions used for flange strength calculations. Table A-2. Temperature Restrictions due to O-ring Selection (Not Applicable for 1R-2R or 2P-4P Where no Process O-ring is Present) Tank seal with different O-ring materials(1) Min. temperature °F (°C) in air Max.
Reference Manual Appendix A: Reference data 00809-0100-4026, Rev HA November 2014 Ambient temperature effect 0.05%/10 K in temperature range -40 °F to 176 °F (-40 °C to 80 °C) Update interval 1 second A.2.2 Measuring range Measuring range and minimum dielectric constant Maximum measuring range from flange: 115 ft (35 m) The measuring range depends on: Microwave frequency Antenna size The dielectric constant (r) of the liquid (min. r=1.
Reference Manual Appendix A: Reference data 00809-0100-4026, Rev HA November 2014 Table A-5. Rosemount 5401, Maximum Recommended Measuring Range, ft (m) Low frequency antennas Dielectric constant(1) A B C A B C A B C N/A N/A N/A 82 (25) 115 (35) 115 (35) N/A N/A N/A 4-in. cone / rod(3) 23 (7) 39 (12) 49 (15) 82 (25) 115 (35) 115 (35) 13 (4) 26 (8) 39 (12) 6-in. Cone 43 (13) 66 (20) 82 (25) 82 (25) 115 (35) 115 (35) 20 (6) 33 (10) 46 (14) 8-in.
Reference Manual Appendix A: Reference data 00809-0100-4026, Rev HA November 2014 Table A-6. Beam Angle for the Rosemount 5400 Series Antenna size Beam angle 5402 Beam angle 5401 19° N/A 14° (pipe only) 4-in. Cone / Process Seal , Rod 9° 37° 6-in. Cone N/A 23° 8-in. Cone N/A 17° 2-in. Cone / Process Seal(1) (1) 3-in. Cone / Process Seal (1) (2) (1) Only with Rosemount 5402. (2) Only with Rosemount 5401. Table A-7.
Reference Manual Appendix A: Reference data 00809-0100-4026, Rev HA A.2.4 November 2014 Transition zone and near zone Transition zones are areas where measurements are not recommended. Near zones are areas where the accuracy is reduced. Figure A-17. Transition Zone and Near Zone Transition zone Near zone Transition zone 6 in. (150 mm) from lower end of the antenna Near zone distance 1.3 ft (0.4 m) from lower end of the antenna Near zone accuracy Reference Data 5402: ± 0.6 in.
Appendix A: Reference data A.2.5 Reference Manual 00809-0100-4026, Rev HA November 2014 Environment Vibration resistance(1) Aluminum housing: IEC 60770-1 Level 1 SST housing: IACS E10 Electromagnetic compatibility(1) Emission and immunity: EMC directive 204/108/EC. EN 61326-1:2006(2). NAMUR recommendations NE21(2). Transient / built-in lightning protection IEC 61000-4-5:2001 T1 option: C62.41.2-2002 (IEEE), C37.90.
Reference Manual Appendix A: Reference data 00809-0100-4026, Rev HA November 2014 A.3 Physical specifications A.3.1 Material selection Emerson provides a variety of Rosemount product with various product options and configurations including materials of construction that can be expected to perform well in a wide range of applications. The Rosemount product information presented is intended as a guide for the purchaser to make an appropriate selection for the application.
Reference Manual Appendix A: Reference data 00809-0100-4026, Rev HA November 2014 A.3.3 Engineered solutions When standard model codes are not sufficient to fulfill requirements, please consult the factory to explore possible Engineered Solutions. This is typically, but not exclusively, related to the choice of wetted materials or the design of a process connection. These Engineered Solutions are part of the expanded offerings and may be subject to additional delivery lead time.
Reference Manual Appendix A: Reference data 00809-0100-4026, Rev HA November 2014 Antenna dimensions Cone antenna: See “Rosemount 5402 and 5401 with SST Cone Antenna (Model Code: 2S-8S)” on page 200 and “Rosemount 5402 and 5401 with Protective Plate Cone Antenna (Model Code: 2H-8H, 2M-8M, and 2N-8N)” on page 201. Rod antenna: See “Rosemount 5401 with Rod Antenna (Model Code: 1R-4R)” on page 202.
Appendix A: Reference data Reference Manual 00809-0100-4026, Rev HA November 2014 Weight Antennas Cone Antenna (Model Code 2S-8S, 2H-8H, 2M-8M, 2N-8N): 2.2 lb (1.0 kg) Process Seal Antenna (Model Code 2P-4P): 4.4 lb (2.0 kg) Rod Antenna (Model Code 1R-4R): 2.2 lb (1.0 kg) Process connections(1) ANSI Flange, 2 in. 150 lb SST (AA): 6.6 lb (3.0 kg) EN (DIN) Flange, DN50 PN40 SST (HB): 8.8 lb (4.0 kg) JIS Flange 50A 10K SST (UA): 6.6 lb (3.0 kg) Bracket mounting (BR): 4.4 lb (2.
Reference Manual Appendix A: Reference data 00809-0100-4026, Rev HA November 2014 Solids applications Rosemount 5402 Non Contacting Radar level transmitter provides industry leading measurement capabilities and reliability on solids. Characteristics include: 4 inch cone antenna (4S, 4H, 4M or 4N) Measurement accuracy: Application dependent Measurement independent of dust (may need air purging(1)) Figure A-18.
Reference Manual Appendix A: Reference data 00809-0100-4026, Rev HA November 2014 A.4 Dimensional drawings and mechanical properties A.4.1 Rosemount 5402 and 5401 with SST Cone Antenna (Model Code: 2S-8S) All dimensions are in inches (mm). 7.1 (180) 3.5 (88) 5.2 (133) 3.6 (92) Process connection availability ● Available as standard 7.3 (185) 9.4 (240) ❍ Available as special, consult factory – Not available Antenna code s60 2S 3S, 4S, 6S, 8S 2 in./DN 50/50A ● ❍ 3 in.
Reference Manual Appendix A: Reference data 00809-0100-4026, Rev HA A.4.2 November 2014 Rosemount 5402 and 5401 with Protective Plate Cone Antenna (Model Code: 2H-8H, 2M-8M, and 2N-8N) All dimensions are in inches (mm). 7.1 (180) 3.5 (88) 5.2 (133) 3.6 (92) 7.3 (185) 9.4 (240) s60 A Protective plate B 5402 Cone Antenna with Protective Plate Cone size (in.) A B Antenna code 2 5.9 (150) 2.0 (50) 2H, 2M, 2N 3 6.9 (175) 2.6 (67) 3H, 3M, 3N 4 9.8 (250) 3.
Reference Manual Appendix A: Reference data 00809-0100-4026, Rev HA November 2014 A.4.3 Rosemount 5401 with Rod Antenna (Model Code: 1R-4R) 3.5 (88) All dimensions are in inches (mm). 5.2 (133) 7.1 (180) 3.6 (92) 7.3 (185) 9.4 (240) s60 Rod Antenna with protective plate (1R, 2R) B Rod Antenna without protective plate (3R, 4R) A Process connection availability ● Available as standard ❍ Available as special, consult factory – Not available 1.5 (38) Rod A B(1) Antenna code Short 14.
Reference Manual Appendix A: Reference data 00809-0100-4026, Rev HA A.4.4 November 2014 Rosemount 5402 with Process Seal Antenna (Model Code: 2P-4P) All dimensions are in inches (mm). 7.1 (180) 3.5 (88) 5.2 (133) 3.6 (92) 7.3 (185) s60 B 1.1 (27) C A Process seal size (in.) A B C Antenna code 2 1.8 (46) 14.2 (360) 0.9 (22) 2P 3 2.8 (72) 17.3 (440) 1.4 (35) 3P 4 3.8 (97) 18.9 (480) 1.
Reference Manual Appendix A: Reference data 00809-0100-4026, Rev HA November 2014 A.4.5 Bracket mounting (Model Code: BR) Bracket mounting is available for the Rosemount 5401 and 5402 with SST Cone Antenna (2S-8S) and Rosemount 5401 with Rod Antenna (3R-4R). All dimensions are in inches (mm). Pipe diameter max 2.5 inches (64 mm) 5.2 (133) Pipe mounting (vertical pipe) Pipe mounting (horizontal pipe) 2.2 (57) 0.3 (7) 2.8 (20) 0.
Reference Manual Appendix A: Reference data 00809-0100-4026, Rev HA A.4.6 November 2014 Process connections Standard flanges Figure A-19. Cone and Rod Antennas (Model Code: 2S-8S and 1R-4R) Designation Mating standard Face style(1) Face surface finish Material ANSI ASME B16.5 0.06 in. raised face Ra = 125-250 ì in 316 / 316L EN (DIN) EN 1092-1 2 mm raised face (Type B1) Ra = 3.2-12.5 ì m EN 1.4404 JIS JIS B2220 2 mm raised face Ra = 3.2-6.3 ì m EN 1.
Appendix A: Reference data A.5 Reference Manual 00809-0100-4026, Rev HA November 2014 Ordering information Specification and selection of product materials, options, or components must be made by the purchaser of the equipment. See page 195 for more information on Material Selection. Table A-10. 5402 High Frequency Radar Level Transmitter Ordering Information The starred options (★) represent the most common options and should be selected for best delivery.
Reference Manual Appendix A: Reference data 00809-0100-4026, Rev HA November 2014 Table A-10. 5402 High Frequency Radar Level Transmitter Ordering Information The starred options (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Appendix A: Reference data Reference Manual 00809-0100-4026, Rev HA November 2014 Table A-10. 5402 High Frequency Radar Level Transmitter Ordering Information The starred options (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Reference Manual Appendix A: Reference data 00809-0100-4026, Rev HA November 2014 Table A-10. 5402 High Frequency Radar Level Transmitter Ordering Information The starred options (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Appendix A: Reference data November 2014 Reference Manual 00809-0100-4026, Rev HA Table A-10. 5402 High Frequency Radar Level Transmitter Ordering Information The starred options (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Reference Manual 00809-0100-4026, Rev HA Appendix A: Reference data November 2014 Table A-11. 5401 Low Frequency Radar Level Transmitter Ordering Information The starred options (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Appendix A: Reference data November 2014 Reference Manual 00809-0100-4026, Rev HA Table A-11. 5401 Low Frequency Radar Level Transmitter Ordering Information The starred options (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Reference Manual 00809-0100-4026, Rev HA Appendix A: Reference data November 2014 Table A-11. 5401 Low Frequency Radar Level Transmitter Ordering Information The starred options (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Appendix A: Reference data November 2014 Reference Manual 00809-0100-4026, Rev HA Table A-11. 5401 Low Frequency Radar Level Transmitter Ordering Information The starred options (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time. RA(8) 1.5-in. NPT Other BR(8) Bracket mounting, 316L / EN 1.
Reference Manual Appendix A: Reference data 00809-0100-4026, Rev HA November 2014 Table A-11. 5401 Low Frequency Radar Level Transmitter Ordering Information The starred options (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Appendix A: Reference data November 2014 216 Reference Manual 00809-0100-4026, Rev HA Reference Data
Reference Manual Appendix B: Product certifications 00809-0100-4026, Rev HA November 2014 Appendix B Product Certifications Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . European Directive information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FCC and ICC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix B: Product certifications Reference Manual 00809-0100-4026, Rev HA November 2014 Failure to follow safe installation and service guidelines could result in death or serious injury. Make sure the transmitter is installed by qualified personnel and in accordance with applicable code of practice. Use the equipment only as specified in this manual. Failure to do so may impair the protection provided by the equipment.
Reference Manual Appendix B: Product certifications 00809-0100-4026, Rev HA B.2 November 2014 European Directive information The EC declaration of conformity for all applicable European directives for this product can be found on the Rosemount website at www.rosemount.com. A hard copy may be obtained by contacting our local sales representative. B.3 FCC and ICC This device complies with Part 15 of the FCC Rules and with Industry Canada license-exempt RSS standard(s).
Appendix B: Product certifications B.5 Reference Manual 00809-0100-4026, Rev HA November 2014 Hazardous locations certifications Other temperature restrictions may apply beside the ones mentioned in the following sections. For more information, see “Reference Data” on page 177. B.5.
Reference Manual Appendix B: Product certifications 00809-0100-4026, Rev HA B.5.2 November 2014 Canadian Standards Association (CSA) Approvals When bearing the “Dual Seal” marking, this product meets the Dual Seal Requirements of ANSI/ISA 12.27.01-2003. Cert. No.: 1514653 E6 Explosion-proof with internal Intrinsically safe circuits [Exia] Class I, Div. 1, Groups B, C, and D; Temp. Code T4. Class II, Div. 1 and 2, Groups E, F, and G; Class III, Div. 1 Ambient temperature limits -50 °C to +70 °C(1).
Reference Manual Appendix B: Product certifications 00809-0100-4026, Rev HA November 2014 B.5.3 European certifications ATEX Approvals 0575 Nemko 04ATEX1073X Specific Conditions for Safe Use (X): 1. The intrinsically safe circuits do not withstand the 500V AC test as specified in EN 60079-11clause 6.4.13. 2. “Potential ignition hazards by impact or friction need to be considered according to EN 60079-0:2012 clause 8.3 (for EPL Ga and EPL Gb) and clause 8.
Reference Manual Appendix B: Product certifications 00809-0100-4026, Rev HA November 2014 Nemko 10ATEX1072 N1 Type n: II 3G Ex nA IIC T4 Gc (-50 °C Ta +70 °C(1)) II 3G Ex nL IIC T4 Gc (-50 °C Ta +70 °C(1)) HART 4-20 mA(2) Maximum input voltage Ui: 42.4 V, Maximum input current Ii: 23 mA Maximum input power Pi: 1.0 W, Maximum internal capacitance Ci: 7.
Appendix B: Product certifications B.5.4 Reference Manual 00809-0100-4026, Rev HA November 2014 IECEx Approval IECEx NEM 06.0001X Specific Conditions for Safe Use (X): 1. The intrinsically safe circuits do not withstand the 500V AC test as specified in IEC 60079-11 clause 6.4.13. 2. “Potential ignition hazards by impact or friction need to be considered according to IEC 60079-0:2011 clause 8.3 (for EPL Ga and EPL Gb) and clause 8.
Reference Manual Appendix B: Product certifications 00809-0100-4026, Rev HA November 2014 IECEx NEM 10.0005 N7 Type n: Ex nA IIC T4 Gc (-50 °C Ta +70 °C(1)) Ex nL IIC T4 Gc (-50 °C Ta +70 °C (1)) HART® 4-20 mA(2) Maximum input voltage Ui: 42.4 V, Maximum input current Ii: 23 mA Maximum input power Pi: 1.0 W, Maximum internal capacitance Ci: 7.
Appendix B: Product certifications B.5.6 Reference Manual 00809-0100-4026, Rev HA November 2014 Brazilian certifications NCC/INMETRO Approvals Special Condition for Safe Use (X): Refer to Certificate NCC 14.
Reference Manual Appendix B: Product certifications 00809-0100-4026, Rev HA B.5.8 November 2014 Japanese certifications Technology Institution of Industrial Safety (TIIS) Approval Special Condition for Safe Use (X): Refer to certificate TC20109-TC20111 (4-20 mA HART) and TC20244-TC20246 FOUNDATION fieldbus) E4(1) Flameproof: 4-20 mA HART model: Transmitter: Ex d [ia] IIC T4x -20 ~ +60 °C DC 20 - 42.4 V Um = 250 V Uo = 22.2 V Io = 177 mA Po = 0.
Reference Manual Appendix B: Product certifications 00809-0100-4026, Rev HA November 2014 B.5.9 Other certifications Overfill protection Cert. No: Z-65.16-475 U1 TÜV-tested and approved by DIBt for overfill protection according to the German WHG regulations. Approval valid for HART options. Suitability for Intended Use Compliant with NAMUR NE 95, version 07.07.2006 “Basic Principles of Homologation”.
Reference Manual Appendix B: Product certifications 00809-0100-4026, Rev HA November 2014 SLL(1) Lloyd's Register Type Approval Certificate Certificate Number: 09/00034 Application: For use in environmental categories ENV1, ENV2, ENV3 and ENV5 as defined in Lloyd's Register Test Specification No. 1: 2002. Approval valid for HART and FOUNDATION fieldbus options.
Appendix B: Product certifications B.6 Reference Manual 00809-0100-4026, Rev HA November 2014 Approval drawings This section contains a FM Approvals system control drawing and Canadian Standards Association and IECEx/ATEX/TIIS installation drawings. You must follow the installation guidelines presented in order to maintain certified ratings for installed transmitters.
Product Certifications Potential Electrostatic Charging Hazard – The enclosure is a non-metallic construction. To prevent the risk of electrostatic sparking the plastic surface should only be cleaned with a damp cloth. The apparatus enclosure contains aluminum and is considered to constitute a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact or friction. WARNING: WARNING: 5 1 ISSUE 0346 1144 WEEK SME-3446 SME-7120 CH.
232 POWER SUPPLY 0840 Product options bearing the DUAL SEAL marking on the label meets the Dual Seal requirements of ANSI/ISA 12.27.01. No additional process sealing is required. For the in-service limits applicable to a specific model, see Process Pressure/Temperature range in Appendix A of the Reference manual. 5. Connect supply wires to the appropriate terminals as indicated on the terminal block and in the installation documents. 3. Installations should be in accordance with ANSI/ISA-RP12.
Product Certifications BARRIER ROSEMOUNT 5400 SERIES HAZARDOUS LOCATION Control equipment connected to the barrier must not use or generate more than 250 Vrms or Vdc. Connect supply wires to the appropriate terminals as indicated on the terminal block table and in the installation documents. 2. 3. EX-CERTIFIED PRODUCT. No modifications permitted without reference to the Ex-certifying Authorities.
234 POWER SUPPLY POWER SUPPLY Barrier Uo: 42.4 V Io: 23 mA Po: 1 W Lo > 0 Co > 7.25 nF Ui: 42.4 V Ii: 23 mA Pi: 1 W Li: Negligible Ci: 7.25 nF HART: 42.4 VDC , 23 mA FOUNDATION FIELDBUS: 32 VDC, 21 mA Note 1 Note 1 HAZARDOUS LOCATION 2011-06-28 14:34 9240031-958_I02_P01_A3.DOCX SME-5859 1 WEEK 1041 WEEK EAP APPROVED BY EE-VM ISSUED BY FILE 6 DOC. TYPE 5400 PRODUCT CODE Rosemount Tank Radar AB, Sweden The copyright/ownership of this document is and will remain ours.
Reference Manual Appendix B: Product certifications 00809-0100-4026, Rev HA November 2014 Figure B-5. Installation Drawing for Hazardous Location Installation of TIIS Approved Apparatus ᅜෆ(TIIS)㜵⇿ᵝ 1) ᑐ㇟ᶵჾ 㜵⇿グྕ ᐃ ᱁ 㸺5401/5402㸼 ධຊ㒊 Ex d [ia] IIC T4 X, ᮏᏳᅇ㊰ Uo = 22.2V ಙྕኚ㒊ཬࡧࣥࢸࢼ Ex ia IIC T4 X Io = 177mA Po = 0.985W 㠀ᮏᏳᅇ㊰ 㟁※ DC 20~42.
Appendix B: Product certifications Reference Manual November 2014 00809-0100-4026, Rev HA 236 Product Certifications
Appendix C: Advanced configuration Reference Manual November 2014 00809-0100-4026, Rev HA Appendix C Advanced Configuration Tank geometry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 237 Advanced analog output settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 239 Advanced transmitter settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix C: Advanced configuration C.1.2 Reference Manual 00809-0100-4026, Rev HA November 2014 Minimum level offset (C) The Minimum Level Offset (C) defines a lower null zone which extends the measurement range beyond the Lower Reference Point to the tank bottom. The Minimum Level Offset is the distance between the Lower Reference Point (Level = 0) and the minimum accepted level at the tank bottom. Set the Minimum Level Offset to zero to use the tank bottom as the Lower Reference Point.
Appendix C: Advanced configuration Reference Manual November 2014 00809-0100-4026, Rev HA C.2 Advanced analog output settings The 20 mA Upper Range Value should be outside the Hold Off Distance (see “Hold off distance” on page 238) in order to utilize the full range of the analog output. Figure C-2.
Appendix C: Advanced configuration Reference Manual 00809-0100-4026, Rev HA November 2014 Empty tank detection area The Empty Tank Detection Area is the range within a lower limit of 16 in. (400 mm) and a higher limit of 39 in. (1000 mm) above the tank bottom. If the surface echo is lost in this region, the tank is considered empty (the device enters Empty Tank State) and the transmitter presents a zero level reading.
Reference Manual Appendix C: Advanced configuration 00809-0100-4026, Rev HA C.3.3 November 2014 Full tank handling Full tank detection area This parameter defines a range where the surface echo can be lost. If the echo is lost in this range, the tank is considered full (the device enters Full Tank State) and the device presents maximum level indication. When the tank is full, the device searches double the Full Tank Detection Area for the product surface.
Appendix C: Advanced configuration C.3.5 Reference Manual 00809-0100-4026, Rev HA November 2014 Surface echo tracking Slow search This variable controls how to search for the surface when a surface echo is lost. With this parameter set, the transmitter starts searching for the surface at the last known level and gradually increases the search region until the surface is found. If this variable is not set, the transmitter searches the whole tank.
Appendix C: Advanced configuration Reference Manual November 2014 00809-0100-4026, Rev HA C.3.6 Filter settings Damping value The Damping Value parameter determines how quickly the transmitter responds to level changes and how robust the measurement signal is against noise. A damping value of 10 indicates that in 10 seconds the output from the transmitter is approximately 63 % of the new level value.
Reference Manual Appendix C: Advanced configuration 00809-0100-4026, Rev HA November 2014 Amplitude Distance Surface echo Echo from tank bottom Empty tank detection area If the signal from the product surface is lost within the region given by the parameter Empty Tank Detection Area, the tank is considered empty and the product level is presented as zero. If the surface is lost above the Empty Tank Detection Area, the transmitter starts searching the entire tank for the surface.
Appendix C: Advanced configuration Reference Manual November 2014 00809-0100-4026, Rev HA Amplitude Distance If the product surface is lost in this region, the tank is considered empty. See “Empty tank detection area” on page 240 for further information. Extra echo function The Extra Echo Detection function makes for more robust measurements in the bottom region for conical or domed bottom shape tanks.
Reference Manual Appendix C: Advanced configuration 00809-0100-4026, Rev HA November 2014 Amplitude Distance Extra echo min. distance Extra echo max.
Appendix C: Advanced configuration Reference Manual November 2014 00809-0100-4026, Rev HA C.4.2 Full tank handling With the Full Tank Handling function product levels close to the antenna can be reported as a Full Tank. Normally, measurements are not allowed closer to the antenna than specified by the Hold Off Distance parameter. If the product level enters the Hold Off Distance region, the transmitter reports Measurement Error and starts searching for the surface.
Reference Manual Appendix C: Advanced configuration 00809-0100-4026, Rev HA November 2014 C.4.3 Double bounce A double bounce echo is an echo that has been reflected against the tank roof then down to the surface before being detected by the transmitter. Double bounces are commonly present in spherical or horizontal cylinder tanks. In this case, the tank roof can sometimes amplify the double bounce echo amplitude. Normally, double bounce echoes appear when the tank is 60-70 % full.
Appendix C: Advanced configuration Reference Manual November 2014 00809-0100-4026, Rev HA C.4.4 Surface echo tracking The Surface Echo Tracking function can eliminate ghost echo problems below the product surface. This may occur in Still-pipes because of multiple reflections between the pipe wall, flange, and antenna. In the tank spectrum, these echoes appear as amplitude peaks at various distances below the product surface.
Appendix C: Advanced configuration C.4.5 Reference Manual 00809-0100-4026, Rev HA November 2014 Hold off setting The Hold Off parameter is set to a default value that rarely needs any adjustment (see “Hold off distance” on page 238 for definition of Hold Off distance). The Process Seal antenna is slightly more affected by disturbances in the nozzle than the cone and rod antennas. If necessary, a small Hold Off adjustment may be sufficient to solve the problem.
Appendix D: Performing proof test Reference Manual November 2014 00809-0100-4026, Rev HA Appendix D Performing Proof Test Performing proof test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 251 Field communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 251 RRM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Appendix D: Performing proof test 00809-0100-4026, Rev HA November 2014 Figure D-1. Range Values Upper Reference Point Hold Off Distance Product Level Range 0-100 % 20 mA Upper Range Value (URV) 4 mA Lower Range Value (LRV) Min Level Offset (C) 5. Lower Reference Point (Level=0) Perform a two-point calibration check of the transmitter by applying level at two points within the measuring range.
Appendix D: Performing proof test Reference Manual November 2014 00809-0100-4026, Rev HA D.3 RRM Prior to this test, inspect the echo curve to ensure that no disturbing echoes affecting the measurement performance are present. RRM: Tools / Echo Curve 1. Bypass the safety PLC or take other appropriate actions to avoid false trip. 2. Disable write protection if the function is enabled. RRM: Select Tools, Lock / Unlock Configuration Area from the menu.
Appendix D: Performing proof test Reference Manual 00809-0100-4026, Rev HA November 2014 5. Restore the Alarm mode to the original mode used in the loop. Verify that the analog output current is correct. RRM: Set Alarm Mode AOut 1 to original mode. Click Store to save changes. Verify that the output current is correct. 6. Perform a two-point calibration check of the transmitter by applying level at two points within the measuring range.
Appendix D: Performing proof test Reference Manual November 2014 00809-0100-4026, Rev HA D.4 AMS Suite Prior to this test, inspect the echo curve to ensure that no disturbing echoes affecting the measurement performance are present. AMS: Click Configure / Setup / Echo Curve 1. Bypass the safety PLC or take other appropriate actions to avoid false trip. 2. Disable write protection if the function is enabled. AMS: Select Device Diagnostics/ Tools from the left menu, and choose the General tab.
Appendix D: Performing proof test Reference Manual 00809-0100-4026, Rev HA November 2014 Click Loop Test... Select Other and enter the mA value representing the high Analog Output Level and follow the instructions. Verify that the output current is correct. 4. Using loop test, enter the mA value representing the low alarm mode. Verify that the analog output current is correct using the reference meter. This step tests for possible quiescent current related failures.
Appendix E: Level transducer block Reference Manual November 2014 00809-0100-4026, Rev HA Appendix E Level Transducer Block Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 257 Parameters and descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 258 Supported units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Appendix E: Level transducer block 00809-0100-4026, Rev HA November 2014 E.2 Parameters and descriptions Table E-2. Level Transducer Block Parameters and Descriptions Parameter Index number ST_REV 1 TAG_DESC 2 STRATEGY 3 ALERT_KEY 4 MODE_BLK 5 Default value The revision level of the static data associated with the function block. The revision value increments each time a static parameter value in the block is changed.
Appendix E: Level transducer block Reference Manual November 2014 00809-0100-4026, Rev HA Parameter Index number RADAR_LEVEL_RANGE 15 RADAR_ULLAGE RADAR_LEVELRATE 16 17 RADAR_LEVELRATE_RANGE 18 RADAR_LEVEL_SIGNAL_STRENGTH 19 RADAR_LEVEL_SIGNAL_STRENGTH_RANGE 20 RADAR_VOLUME 21 RADAR_VOLUME_RANGE 22 RADAR_INTERNAL_TEMPERATURE 23 RADAR_INTERNAL_TEMPERATURE_ RANGE 24 ANTENNA_TYPE ANTENNA_TCL ANTENNA_PIPE_DIAM DAMP_VALUE SIGN_PROC_CONFIG ANTENNA_EXTENSION 25 26 27 28 29 30 LCD_PARAMETE
Reference Manual Appendix E: Level transducer block 00809-0100-4026, Rev HA November 2014 Parameter Index number ENV_ENVIRONMENT 44 ENV_PRESENTATION 45 ENV_DEVICE_MODE 46 ENV_DIELECTR_CONST ENV_WRITE_PROTECT DIAGN_DEV_ALERT DIAGN_VERSION DIAGN_REVISION DIAGN_DEVICE_ID DIAGN_DEVICE_MODEL DIAGN_COMPL_TANK STATS_ATTEMPTS STATS_FAILURES STATS_TIMEOUTS SENSOR_DIAGNOSTICS P1451_SLAVE_STATS P1451_HOST_STATS FF_SUPPORT_INFO HEART_BEAT_COUNT RADAR_LEVEL_TYPE 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61
Appendix E: Level transducer block Reference Manual November 2014 00809-0100-4026, Rev HA Table E-3.
Reference Manual Appendix E: Level transducer block 00809-0100-4026, Rev HA November 2014 Table E-6.
Appendix E: Level transducer block Reference Manual November 2014 00809-0100-4026, Rev HA Bit Number Value of ENV_PRESENTATION DESCRIPTION 9 10 11 0x000000200 0x000000400 0x000000800 Bit 8, reserved Bit 9, reserved Bit 10, reserved Table E-8. Tank Type VALUE GEOM_TANK_TYPE 0 1 2 3 4 Unknown Vertical Cylinder Horisontal Cylinder Spherical Cubical Table E-9. Tank Bottom Type VALUE GEOM_TANK_BOTTOM_TYPE 0 1 2 3 4 Unknown Flat Dome Cone Flat Inclined Table E-10.
Reference Manual Appendix E: Level transducer block 00809-0100-4026, Rev HA November 2014 Table E-12. Level Rate Value Display Description 0 Default 1061 1063 1067 1069 M/s M/h Ft/s In/m Unit for LCD is the same as set in the value window Meter per second Meter per hour Feet per second Inch per minute (1) (1) Default only for parameter LCD_VELOCITY_UNIT. Table E-13.
Appendix F: Register transducer block Reference Manual November 2014 00809-0100-4026, Rev HA Appendix F Register Transducer Block Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 265 F.1 Overview The Register Transducer Block allows access to Database registers and Input registers of the Rosemount 5400 transmitter.
Reference Manual Appendix F: Register transducer block 00809-0100-4026, Rev HA November 2014 Parameter Index number UPDATE_EVT 7 This alert is generated by any change to the static data. BLOCK_ALM 8 The block alarm is used for all configuration, hardware, connection failure, or system problems in the block. The cause of the alert is entered in the subcode field. The first alert to become active will set the Active status in the Status parameter.
Appendix F: Register transducer block Reference Manual November 2014 00809-0100-4026, Rev HA Parameter Index number Default value Description INP_REG_7_INT_DEC 35 If the register contains a DWORD value and dec is chosen, it shall be displayed here INP_REG_8_TYPE 36 Register type INP_REG_8_FLOAT 37 If the register contains a float value, it shall be displayed here INP_REG_8_INT_DEC 38 If the register contains a DWORD value and dec is chosen, it shall be displayed here INP_REG_9_TYPE 39
Reference Manual Appendix F: Register transducer block 00809-0100-4026, Rev HA November 2014 Parameter Index number Default value Description DB_REG_7_INT_DEC 65 If the register contains a DWORD value and dec is chosen, it shall be displayed here DB_REG_8_TYPE 66 Register type DB_REG_8_FLOAT 67 If the register contains a float value, it shall be displayed here DB_REG_8_INT_DEC 68 If the register contains a DWORD value and dec is chosen, it shall be displayed here DB_REG_9_TYPE 69 Regis
Appendix G: Advanced configuration transducer block Reference Manual November 2014 00809-0100-4026, Rev HA Appendix G Advanced Configuration Transducer Block Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 269 G.1 Overview The Advanced Configuration Transducer Block contains functions for advanced configuration of the Rosemount 5400 Series transmitter.
Reference Manual Appendix G: Advanced configuration transducer block 00809-0100-4026, Rev HA November 2014 Parameter Index number Default value XD_ERROR 11 N/A COLLECTION_DIRECTORY 12 0 TRANSDUCER_TYPE_VER 13 769 Description A transducer block alarm subcode. Command.
Appendix G: Advanced configuration transducer block Reference Manual November 2014 00809-0100-4026, Rev HA Parameter Index number Default value Description VOL_STRAP_VOL_8 45 0 Strap value volume VOL_STRAP_LEV_9 46 0 Strap value level VOL_STRAP_VOL_9 47 0 Strap value volume VOL_STRAP_LEV_10 48 0 Strap value level VOL_STRAP_VOL_10 49 0 Strap value volume VOL_STRAP_LEV_11 50 0 Strap value level VOL_STRAP_VOL_11 51 0 Strap value volume VOL_STRAP_LEV_12 52 0 Strap value le
Appendix G: Advanced configuration transducer block November 2014 272 Reference Manual 00809-0100-4026, Rev HA Advanced Configuration Transducer Block
Appendix H: Resource block Reference Manual November 2014 00809-0100-4026, Rev HA Appendix H Resource Block Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 273 Parameters and descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 273 H.
Reference Manual Appendix H: Resource block 00809-0100-4026, Rev HA November 2014 Parameter Index number Default value MANUFAC_ID 10 0x00001151 Manufacturer identification number – used by an interface device to locate the DD file for the resource. DEV_TYPE 11 5400 Manufacturer’s model number associated with the resource - used by interface devices to locate the DD file for the resource.
Appendix H: Resource block Reference Manual November 2014 00809-0100-4026, Rev HA Parameter Index number Default value SHED_ROUT 27 640000 Time duration at which to give up on computer writes to function block ROut locations. Shed from ROut shall never happen when SHED_ROUT = 0 FAULT_STATE 28 0x01(Clear) Condition set by loss of communication to an output block, fault promoted to an output block or physical contact.
Reference Manual Appendix H: Resource block 00809-0100-4026, Rev HA November 2014 Parameter Index number FB_OPTIONS Default value Description 45 0x00000000 (0x00000000) Indicates which function block licensing options are enabled. DIAG_OPTIONS 46 0x00000000 (0x00000000) Indicates which diagnostics licensing options are enabled. MISC_OPTIONS 47 0x00000000 (0x00000000) Indicates which miscellaneous licensing options are enabled.
Appendix H: Resource block Reference Manual November 2014 00809-0100-4026, Rev HA Parameter Index number Default value Description SIMULATE_STATE 66 0x01(Jumper off* no simulation) The state of the simulate switch: 0 = Uninitialized 1 = Switch off, simulation not allowed 2 = Switch on, simulation not allowed (need to cycle jumper/switch) 3 = Switch on, simulation allowed download_mode 67 0x01(Run Mode) Gives access to the boot block code for over-the-wire downloads.
Reference Manual Appendix H: Resource block 00809-0100-4026, Rev HA November 2014 Index number Parameter Default value Description ADVISE_MASK 81 0x00000000 (0x00000000) Mask of ADVISE_ALM. Corresponds bit of bit to ADVISE_ACTIVE. A bit on means that the condition is masked out from alarming. ADVISE_ACTIVE 82 0x00000000 (0x00000000) Enumerated list of advisory conditions within a device. ADVISE_ALM 83 HEALTH_INDEX 84 100 PWA_SIMULATE 85 0x00(Simulation off) H.2.
Appendix H: Resource block Reference Manual November 2014 00809-0100-4026, Rev HA FAILED_PRI Designates the alerting priority of the FAILED_ALM, see “Alarm priority” on page 281. The default is 0 and the recommended values are between 8 and 15. FAILED_ACTIVE This parameter displays which of the alarms is active. Only the alarm with the highest priority will be displayed. This priority is not the same as the FAILED_PRI parameter described above.
Appendix H: Resource block Reference Manual 00809-0100-4026, Rev HA November 2014 MAINT_ALM An alarm indicating the device needs maintenance soon. If the condition is ignored, the device will eventually fail. Advisory alarms An advisory alarm indicates informative conditions that do not have a direct impact on the device's primary functions. There are five parameters associated with ADVISE_ALARMS, they are described below.
Appendix H: Resource block Reference Manual November 2014 00809-0100-4026, Rev HA H.2.2 Alarm priority Alarms are grouped into five levels of priority: Priority number 0 1 2 3-7 8-15 Resource Block Priority description The alarm condition is not used. An alarm condition with a priority of 1 is recognized by the system, but is not reported to the operator. An alarm condition with a priority of 2 is reported to the operator.
Reference Manual Appendix H: Resource block 00809-0100-4026, Rev HA November 2014 H.2.3 Recommended actions for PlantWeb alerts RECOMMENDED_ACTION The RECOMMENDED_ACTION parameter displays a text string that will give a recommended course of action to take based on which type and which specific event of the PlantWeb alerts are active. Table H-1.
Appendix H: Resource block Reference Manual November 2014 00809-0100-4026, Rev HA Alarm type Failed/maint/advise/ Description active event Software error The device software has encountered an error. Reasons may be multiple, including too low supplied voltage, or an error being simulated. The status for all variables is BAD, and the device is out of service. Sensor database error The device has found an error in the configuration database. Status for all variables is BAD.
Appendix H: Resource block November 2014 284 Reference Manual 00809-0100-4026, Rev HA Resource Block
Appendix I: Analog-Input block Reference Manual November 2014 00809-0100-4026, Rev HA Appendix I Analog-Input Block Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 288 Damping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 289 Signal conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Appendix I: Analog-Input block 00809-0100-4026, Rev HA November 2014 Parameter Index number Units Description ALERT_KEY 04 None The identification number of the plant unit. This information may be used in the host for sorting alarms, etc. MODE_BLK 05 None The actual, target, permitted, and normal modes of the block.
Appendix I: Analog-Input block Reference Manual November 2014 00809-0100-4026, Rev HA Parameter Index number Units Description The priority of the LO alarm. LO_PRI 29 None LO_LIM 30 EU of PV_SCALE LO_LO_PRI 31 None LO_LO_LIM 32 EU of PV_SCALE HI_HI_ALM 33 None The HI HI alarm data, which includes a value of the alarm, a timestamp of occurrence and the state of the alarm.
Reference Manual Appendix I: Analog-Input block 00809-0100-4026, Rev HA November 2014 I.1 Simulation To support testing, you can either change the mode of the block to manual and adjust the output value, or you can enable simulation through the configuration tool and manually enter a value for the measurement value and its status. With simulation enabled, the actual measurement value has no impact on the OUT value or the status. Figure I-2.
Appendix I: Analog-Input block Reference Manual November 2014 00809-0100-4026, Rev HA I.2 Damping The filtering feature changes the response time of the device to smooth variations in output readings caused by rapid changes in input. You can adjust the filter time constant (in seconds) using the PV_FTIME parameter. Set the filter time constant to zero to disable the filter feature. I.3 Signal conversion You can set the signal conversion type with the Linearization Type (L_TYPE) parameter.
Reference Manual Appendix I: Analog-Input block 00809-0100-4026, Rev HA November 2014 I.4 Block errors Table 2 lists conditions reported in the BLOCK_ERR parameter. Table I-2. BLOCK_ERR Conditions Condition number I.5 Condition name and description 0 Other 1 Block configuration error: the selected channel carries a measurement that is incompatible with the engineering units selected in XD_SCALE, the L_TYPE parameter is not configured, or CHANNEL = zero.
Appendix I: Analog-Input block Reference Manual November 2014 00809-0100-4026, Rev HA I.6 Alarm detection A block alarm will be generated whenever the BLOCK_ERR has an error bit set. The types of block error for the AI block are defined above. Process Alarm detection is based on the OUT value.
Appendix I: Analog-Input block I.6.1 Reference Manual 00809-0100-4026, Rev HA November 2014 Status handling Normally, the status of the PV reflects the status of the measurement value, the operating condition of the I/O card, and any active alarm condition. In Auto mode, OUT reflects the value and status quality of the PV. In Man mode, the OUT status constant limit is set to indicate that the value is a constant and the OUT status is Good.
Appendix I: Analog-Input block Reference Manual November 2014 00809-0100-4026, Rev HA I.7 Configure the AI block A minimum of four parameters are required to configure the AI Block. The parameters are described below with example configurations shown at the end of this section. CHANNEL Select the channel that corresponds to the desired sensor measurement.
Reference Manual Appendix I: Analog-Input block 00809-0100-4026, Rev HA November 2014 XD_SCALE and OUT_SCALE The XD_SCALE and OUT_SCALE each include three parameters: 0 %, 100 %, and, engineering units. Set these based on the L_TYPE: L_TYPE is direct When the desired output is the measured variable, set the XD_SCALE to represent the operating range of the process. Set OUT_SCALE to match XD_SCALE.
Appendix I: Analog-Input block Reference Manual November 2014 00809-0100-4026, Rev HA Table I-6. Temperature Display Description °C Degree Celsius °F Degree Fahrenheit Table I-7. Signal Strength Display Description mV millivolt Table I-8.
Appendix I: Analog-Input block November 2014 296 Reference Manual 00809-0100-4026, Rev HA Analog-Input Block
Reference Manual Index 00809-0100-4026, Rev HA November 2014 Index A Address Temporary Node . . . . . . . . . . . . . . . . . . . . . . . . . . 113 Advanced Configuration. . . . . . . . . . . . . . . . . . . . . . . . 111 Advanced ConfigurationTransducer Block . . . . . . . . . . 113 AI Block Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114 Parameters BLOCK_ERR . . . . . . . . . . . . . . . . . . . . . . . . . . 290 IO_OPTS . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Index 00809-0100-4026, Rev HA November 2014 Disturbing objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Double Bounce . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241 Double Surface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 242 Draft Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 E Echo Curve Analyzer . . . . . . . . . . . . . . . . . . . . . . . . . . . 140 Echo Timeout . . . . . . . . . . . . .
Reference Manual Index 00809-0100-4026, Rev HA November 2014 O S Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112 Optional Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 OSHA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 OUT_SCALE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294 AI Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 289 L_TYPE Direct . . . . . . .
Index November 2014 Reference Manual 00809-0100-4026, Rev HA Volume Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 78 Strapping Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 Volume Offset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 Volume Offset. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110 W Warnings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155 X XD_SCALE . . . . . . . . . . . . . . . . . . . . . .
Reference Manual 00809-0100-4026, Rev HA 2014 Emerson Process Management Rosemount Measurement 8200 Market Boulevard Chanhassen, MN 55317 USA Tel (USA) 1 800 999 9307 Tel (International) +1 952 906 8888 Fax +1 952 906 8889 Emerson Process Management Blegistrasse 23 P.O. Box 1046 CH 6341 Baar Switzerland Tel +41 (0) 41 768 6111 Fax +41 (0) 41 768 6300 Emerson FZE P.O.