User Manual

Cells Per Unit 3
Voltage Per Unit 6
Capacity 7.2Ah @ 20hr-rate to 1.75V per cell
Weight Approx. 1.22 kg(2.69 lbs)
Maximum Discharge Current 100A/130A(5sec)
Internal Resistance Approx. 15.5 mΩ
Operating Temperature Range
Nominal Operating Temperature Range
Float Charging Voltage 6.75 to 6.9 VDC/unit Average at
Recommended Maximum Charging 2.16A
Current Limit
Equalization and Cycle Service 7.2 to 7.5 VDC/unit Average at
Self Discharge CSB Batteries can be stored for more than 6 months at
Please charge batteries before using. For
higher temperatures the time interval will be shorter.
Terminal F1/F2-Faston Tab187/250
Container Material ABS(UL 94-HB) & Flammability resistance of
(UL 94-V0) can be available upon request.
Discharge:
Charge:
Storage:
Constant Current Discharge Characteristics Unit:A (25°C,77°F)
GP 672
6V 7.2Ah
Specification
Powered by
Width (W)
Dimensions :
Unit: mm (inch)
Overall Height (H) Container height (h) Length (L)
100±1 (3.94±0.04) 94±1 (3.7±0.04) 151±2 (5.94±0.08) 34±1 (1.34±0.04)
GP 672 is a general purpose battery up to 5 years in standby
service or more than 260 cycles at 100% discharge in cycle
service. As with all CSB batteries, all are rechargeable, highly
efficient, leak proof and maintenance free.
CSB-manufactured
VRLA batteries are UL-
recognized components
under UL1989.
CSB is also certified by
ISO 9001 and ISO 14001.
by TUV CERT according to ISO 9001,ISO 14001.
The system of manufacturer was certified
(http://www.csb-battery.com)
F.V/Time 5MIN 10MIN 15MIN 30MIN 60MIN 90MIN 2HR 3HR 5HR 8HR 10HR 20HR
1.60V
35.6 22.0 16.5 9.61 5.51 3.92 3.08 2.13 1.34 0.92 0.77 0.45
1.67V
33.1 21.0 15.9 9.36 5.41 3.85 3.02 2.08 1.31 0.90 0.76 0.44
1.70V
31.9 20.5 15.6 9.24 5.37 3.82 3.00 2.06 1.30 0.89 0.75 0.43
1.75V
29.6 19.6 15.1 9.03 5.30 3.77 2.96 2.02 1.27 0.88 0.74 0.42
1.80V
27.2 18.6 14.4 8.77 5.23 3.71 2.91 1.98 1.25 0.87 0.73 0.42
1.85V
24.5 17.4 13.7 8.44 5.14 3.66 2.87 1.95 1.22 0.86 0.71 0.40
F.V/Time 5MIN 10MIN 15MIN 30MIN 60MIN 90MIN 2HR 3HR 5HR 8HR 10HR 20HR
1.60V
180 123 91.4 53.9 32.2 23.5 18.8 13.3 8.62 5.87 4.90 2.68
1.67V
170 118 88.7 52.9 31.8 23.2 18.5 13.2 8.50 5.80 4.84 2.63
1.70V
165 115 87.2 52.4 31.6 23.1 18.4 13.1 8.45 5.76 4.77 2.61
1.75V
157 111 85.0 51.6 31.2 22.8 18.2 13.0 8.36 5.70 4.73 2.57
1.80V
147 106 82.3 50.6 30.9 22.5 18.0 12.8 8.27 5.65 4.70 2.53
1.85V
138 101 79.2 49.5 30.4 22.1 17.7 12.6 8.16 5.60 4.64 2.49
@25°C (77°F)
25°C (77°F)
25°C (77°F)
25°C (77°F).
-15°C~50°C ( 5°F~122°F).
-15°C~40°C ( 5°F~104°F).
-15°C~40°C ( 5°F~104°F).
25°C±3°C (77°F±5°F).
Constant Power Discharge Characteristics Unit:W (25°C,77°F)
RA1308
Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.

Summary of content (2 pages)