User`s guide
94  Guardall Director V4.74 User's Guide  21-0381E v4.7.4 
- Output (bottom of form): This is where 
you select an output to control 
manually, or view its status. This 
shows a reference number assigned 
by the system, plus the 
name/description of the output as 
defined under 'Configuration'. 
- Status: "Error" will appear in colour for 
things such as: 
  Output programming done incorrectly at 
a keypad; 
  An output equation that is not supported 
by the panel version; 
  An output equation that is referencing 
undefined or non-supported devices (e.g., 
incompatible feature-set value). 
- State: This shows whether or not the output is 
triggered; 
- Manual Mode: This shows what type of manual 
control the output is under (if any); 
- [Manual Control]: Allows manually controlling 
the output. 
Details to follow / below. 
- Timer: This shows the remaining duration for a 
timed output function that is presently in effect; 
- Equation: This area shows details on the 
programmed function / equation for the output. 
Controlling an Output Manually 
Access the "Outputs" control & status topic as 
described previously, and use the Grid / Form 
toolbar-button to select your preferred 'view'. 
Forms view: Details for one item at a time; 
Grid View
: All items in a list. 
Select the desired output (bottom of the 'forms' 
window), and click [Manual Control] near the 
upper-right corner of the form; 
Then, refer to the selection-descriptions for this 
screen while making your selection(s). 
Control & Status Panel Control & 
Status Outputs[Manual Control] 
Tip
: Additional parameters appear when applicable 
(duration, etc.). 
- Normal: No manual control (i.e., return to 
normal operation); 
- Always: Allows setting the output as On
 or Off 
continuously (until manual control is removed); 
- Momentary: Allows setting the output to 
pulse/toggle once. Additional selections will 
appear for:  Whether it is to be triggered On
(high), or Off
 (Low);  The state it will be left in 
afterwards (Off
, On, or Normal);  How long the 
relay will remain triggered (1 second to 1 week). 
- Duty Cycle (1 sec. On/1 sec. off):  The output 
will be pulsed on and off continuously for a 
selected duration (1 second to 1 week). 
Control & Status Panel Control & Status 
Outputs 