User`s guide
21-0381E v4.7.4 
Welcome Report 
Control  Admin Sys Config Tech-Ref 
55
- Momentary Normal Unlock: This unlocks the 
door for a duration equal to the standard "unlock 
duration". This is the same as someone gaining 
entry with an access card or token. 
- Momentary Extended Unlock: This unlocks 
the door for a duration equal to the "extended 
unlock duration". This is the same as a user 
who is set for "extended unlock/challenged" 
gaining entry with an access card or token. 
- Pending Unlock: This is an unlock command 
that waits for one person to enter the facility at 
the specific door. 
- Grant Last User -- Reader 1 (or 2): If the last 
user at a reader was denied access, this will 
issue a 'Momentary Unlocking', and log that 
card/user as being granted entry. 
  Cards can be denied due to being expired, locked 
out, wrong time, wrong door class, etc. -- as long as 
they are defined in the system. 
  This feature will be unavailable if someone else is 
granted entry, or after 5 minutes from the time the 
person was denied access (although they can 
simply present their card/token again). 
  This may be used in conjunction with an event-
triggered camera-view for the door (so a remote 
attendant can see the person). 
Related Topics
: "Initial Set Up of: Views, Maps, 
Cameras" (step 3b). 
  This can also be used in conjunction with the pop-
up "Photo-Verification" feature (if it is set to trigger 
on 'Access Denied' events). 
Related Topics
: Visually Verifying Users (Photo-
Verification)" 
 This cannot
 be used (or does not apply) with: 
- Cards being enrolled or disabled at a reader set to 
 do this (although it will apply for cards denied due 
 to wrong area/time, etc.); 
- Access being denied due to door interlock 
violations or area/disarm authority issues. 
___________________________________________ 
Input-Point Commands 
(After right-clicking a Sensor)
Also See: "Common Commands", previous/above. 
------------------------------------------------------------------------- 
- Bypass / Remove Bypass: "Bypass" allows 
arming an area with a tripped or faulty input 
point (sensor). "Remove Bypass" allows 
monitoring the input point again (for a sensor 
that is "OK"). 
____________________________________________ 
Output-Point Commands 
(After right-clicking an Output/Device)
Also See: "Common Commands", previous/above. 
-------------------------------------------------------------------------- 
Tips
: First, select "Manual Output Control". 
Additional parameters appear when applicable 
(duration, etc.). 
- Normal: No manual control (i.e., return to 
normal operation); 
- Always: Allows setting the output as On
 or Off 
continuously (until manual control is removed); 
- Momentary: Allows setting the output to 
pulse/toggle once. Additional selections will 
appear for:  Whether it is to be triggered On
(high), or Off (Low);  The state it will be left in 
afterwards (Off
, On, or Normal);  How long the 
relay will remain triggered (1 second to 1 week). 
- Duty Cycle (1 sec. On/1 sec. off):  The output 
will be pulsed on and off continuously for a 
selected duration (1 second to 1 week). 
___________________________________________ 
Elevator Commands 
(After right-clicking an Elevator)
Also See: "Common Commands", previous/above. 
------------------------------------------------------------------------- 
- Secure / Desecure: This allows applying or 
removing controlled-access for all floors as 
accessed from the specific elevator (lift). 
(Secure: An access card or token provides access to 
specific floors;  Desecure
: Anyone can access any 
floor without a card or token.
Controlling a Floor (as accessed from all cabs): Refer 
to "Checking Status or Controlling Floors" 
Camera Status/Control and 
Adjustments 
Introduction 
A number of camera controls are provided, 
allowing you to:  Aim or zoom PTZ cameras;  
 Check connection status;  Adjust  image 
quality, etc. These features are provided 
through the video toolbar in each camera-