Technical data

11
CTC EcoHeat 400
General Information
1. Technical Data
1.1 Three-phase 400V 3N~
EcoHeat 406 EcoHeat 408 EcoHeat 410 EcoHeat 412
400V 3N~
kW 11.7 12.6 13.4 14.1
A 16.6 17.7 19.8 23.5
kW 0 - 9.0
kW 6.9 / 7.8 / 9 2.1 / 7.8 / 9 2.1 / 7.2 / 9 2.1 / 6.9 / 9
IPX1
EcoHeat 406 EcoHeat 408 EcoHeat 410 EcoHeat 412
kg 2.1 2.1 2.1 2.5
MPa 3.1 (31 bar)
kg 267 270 272 279
mm 595 x 1904 x 672
mm 1925
dB(A) 44,9 43,9 46,0 47,2
EcoHeat 406 EcoHeat 408 EcoHeat 410 EcoHeat 412
l 2.3 2.9 2.9 3.4
°C -5/20
bar 0.2/3.0
3
l/s 0.27 0.31 0.38 0.44
l/s 0.37 0.51 0.64 0.73
TOP-S 25/7 TOP-S 25/10
EcoHeat 406 EcoHeat 408 EcoHeat 410 EcoHeat 412
l 223
bar 2.5
°C 110
l/s
l/s 0.14 0.20 0.24 0.28
EcoHeat 406 EcoHeat 408 EcoHeat 410 EcoHeat 412
@ -5/45 kW 4.68 6.84 8.33 9.88
COP
1)
@ -5/45 - 3.09 3.34 3.30 3.30
@ 0/35 | 0/45
0/55
kW 5.90 | 5.48
5.17
8.19 | 7.87
7.55
9.97 | 9.55
9.28
11.75 | 11.24
10.97
COP
1)
@ 0/35 | 0/45
0/55
- 4.57 | 3.54
2.76
4.58 | 3.64
2.99
4.60 | 3.68
2.98
4.60 | 3.66
2.96
@ 5/35 | 5/45
5/55
kW 6.81 | 6.49
6.08
9.44 | 9.05
8.65
11.42 | 10.99
10.58
13.53 | 12.95
12.57
COP
1)
@ 5/35 | 5/45
5/55
- 5.24 | 4.15
3.18
5.02 | 4.04
3.30
5.20 | 4.16
3.28
5.11 | 4.11
3.35
A 4.5 5.2 6.8 8.2
EcoHeat 406 EcoHeat 408 EcoHeat 410 EcoHeat 412
l
bar 10
°C 110
Electrical Data
Electrical data
Rated power
Max starting current
Immersion heater (steps of 0,3 kW)
Max immersion heater output
@ fuse size 16 / 20 / 25 A
IP class
Other data
Refrigerant quantity (R407C)
Interrupt value switch HP
Weight
Width x Height x Depth
Minimum ceiling height
Noise level
Brine system
Water volume (V)
Brine system min./max. temp. (TS)
Brine system min./max. pressure (PS)
Brine pump speed adjustment
Brine system min. flow, ∆t = 5 °K
Brine system nominal flow, ∆t = 3 °K
Brine system pump
Pump capacity See diagram in the Pipe installation chapter
Heating system
Water volume. thermal store (V)
Max. operating pressure. thermal store (PS)
Max. temperature. thermal store (TS)
Heating system. min. flow Unlimited
Heating system. nominal flow
2)
Pressure drop for mixing valve heating See pressure drop diagram in the Pipe installation chapter
2)
∆t = 10 K and 0/35 °C heat pump operation
Operational data for heat pump
Output from compressor
1)
Output from compressor
1)
Output from compressor
1)
Max. operating current Compressor
1)
EN14511:2007, incl. heating medium pump and brine pump
Hot water system
Water volume, hot water coil (V) 5.7
Max. operating pressure, hot water coil (PS)
Max. temperature, hot water coil (TS)