Specifications
Programming
Programming 15
Switch Definitions
The circuit board is shipped with all DIPswitches in the off position. Prior to programming the controller some DIPswitches may
need to be moved to the ON position. Because each switch serves a specific purpose, please review the following information,
moving the required switches to an ON position as necessary for each controller in the system. The definitions and purpose are as
follows:
Switch # Abbreviation Definition Purpose
1 R/T Run / Test Off- Allows controller to function in a normal, operational mode.
On - Places controller in test mode to verify operation of the board
components.
2 SO/FI Softener / Filter Off - The unit shall be operated as a softener.
On - The unit shall function as a filter. The default time programmed for
cycle #2 shall be 2 minutes
3 CTRL Control Selection See DIPswitch settings below for control selection.
4 CTRL Control Selection See DIPswitch settings below for control selection.
5 S/F Standard Refill /
Fast Refill
Off - The 0.45 gpm refill flow control is used to control the refill flow rate.
Set in the off position for 9” and 10” units.
On - The 0.80 gpm refill flow control is used to control the refill flow rate.
Set in the on position for 12” and 14” units.
6 D/I Demand /
Immediate
Off - Regeneration of a unit will occur at a user-selected time of day.
On - Regeneration shall occur immediately upon a controller receiving a
valid regeneration initiation signal, regardless of the time of day.
7 E/M English / Metric Off - The unit will function in standard English dimensions.
On - The unit will function in standard metric dimensions.
8 12/24 12 Hour Clock /
24 Hour Clock
Off - All time keeping functions shall be based on an AM/PM basis. The AM
or PM icon shall be lit in the display as appropriate.
On - Time keeping functions shall work on a 24-hour clock (military time).
The AM/PM display icons will be disabled.
9 -/ADV Advanced Off /
Advanced On
Off - The Predict Mode and Pre-Rinse Mode will not be activated.
(Efficiency will be active)
On - The Predict Mode and Pre-Rinse Mode will be activated. (Efficiency
will not be active)
10 -/TCB Time Clock
Backup Disabled
/ Enabled
Off - The time clock backup option is not enabled.
On - Allows the user to enable the time clock function of the control as a
backup regeneration initiation option. This feature is used as a back up to a
primary device such as a flow meter, Aqua-Sensor.
Table 4
Dip #3 Dip #4 Control
Off Off Gold
On Off Platinum Plus
Off On Old Platinum
On On Other
Table 5
Note: DIPswitch #2 must be set to the “ON” Position for filter operation. Dipswitches 3 and 4 are off for Iron-Cleer Plus.