Specifications

Programming 17
Programming Menus
In the programming mode all keys are active. Repeatedly pressing the “Program” key until the desired programm option is
displayed enters the standard programming mode. The value is then set by using the “Up” and “Down” keys to increase or
decrease the value. Pressing the “Program” key, after value selection, saves the programmed value to EEPROM (unless otherwise
specified; some settings are temporarily stored before they are saved). To exit the programming mode, repeatedly press the
“Program” key until the display returns to time of day display. The following table outlines all of the programming functions, range
limits and default settings:
Settings Display Range Limits Default Comments
Inputs
Beeper Toggle Y / N Y Enables/disables the key press beeper (ERR/Alert
code beeps can’t be disabled)
Time of Day 12:00 am-11:59
pm (12hr) 00:00-
23:59 (24hr)
12:00 pm 12:00 12 / 24 hour function set with dip # 8.
Time of Regen 12:00 am-11:59
pm (12hr) 00:00-
23:59 (24hr)
2:00 am 02:00 Adjustable in 30 minute increments only.
Regen Interval Days - 1 to 99
days
3 days Active in Time Clock Mode OR Flow Meter - A/S with
dip#10 on (Time Clock back-up).
Pre-Rinse Mode
Toggle Y or N
N Only active if dip # 9 is on
Pre-Rinse
Duration
01 – 15 05 Only active if dip # 9 is on with Pre-Rinse mode is
set to “Yes”
Pre-Rinse Hours 1 – 240 24 Only active if dip # 9 is on with Pre-rinse mode set to
“Yes” AND flow meter connected
Pre-Rinse Time 12:00 am-11:30
pm (12hr) 00:00-
23:30 (24hr)
5:00 am 05:00 Only active if dip # 9 is on with Pre-rinse set to
“Yes”; Adjustable in 30 minute increments only;
Available only in TimeClock and AquaSensor mode
(not flow meter mode)
View Toggle Y or N N Only active if dip # 4 is off. If custom output settings
are being used, then pressing the “Information” key
will recalculate outputs based on current inputs, and
exit from the inputs menu