Specifications

Test Description Display Information Action Trigger
Start Test Mode All LCD segments lit DIP switch #1 set to on, all others off
Software version Software version # Press a key after entering test mode as
above
Enter test mode Blank Display Press a key after displaying the software
version #.
DIP switch #2 Display to show “2” Turn on DIP switch #2
Display to Blank Turn off DIP switch #2
DIP switch #3 Display to show “3” Turn on DIP switch #3
Display to Blank Turn off DIP switch #3
DIP switch #4 Display to show “4” Turn on DIP switch #4
Display to Blank Turn off DIP switch #4
DIP switch #5 Display to show “5” Turn on DIP switch #5
Display to Blank Turn off DIP switch #5
DIP switch #6 Display to show “6” Turn on DIP switch #6
Display to Blank Turn off DIP switch #6
DIP switch #7 Display to show “7” Turn on DIP switch #7
Display to Blank Turn off DIP switch #7
DIP switch #8 Display to show “8” Turn on DIP switch #8
Display to Blank Turn off DIP switch #8
Status Key Display to show “11” Press Status Key
+ Key Display to show “12” and motor to run for
15 seconds
Press + Key
- Key Display to show “13” (and turns on
Chlorinator output for 15 seconds IF
chlorinator is connected)
Press - Key
Regen Key Display to show “14” Press Regen Key
Home Switch Display to show “H” when Home switch
closed
Close Home Switch
Display to Blank when open Open Home Switch
Position Switch Display to show “P” when Position switch
closed
Close Position Switch
Display to Blank when open Open Position Switch
Flow Meter Display to show “Phone” icon when ow
meter is connected
Connect Flow Meter
Display to blink “Phone” icon when ow
meter is sending pulses
Spin Flow Meter
Chlorinator Display to show “Colon” icon when
chlorinator is connected
Connect Chlorinator
Display to blink “Colon” icon when
chlorinator is turned on
Turn on Chlorinator when the plus key is
pressed.
When exiting test mode, if the dip switches or sensors have not changed, the control is to restore all values from EEPROM, and
resume where it left off after homing. If the dip switch or sensors have change, the values should reset to factory defaults. In either
case the valve should home itself upon exit of test mode.
Circuit Board Troubleshooting 49