APP Series Fans Installation and Operation Manual PNEG-876 Date: 05-07-14 PNEG-876
APP Series Fans are manufactured, assembled and packaged with the highest standard of quality assurance. Please inspect and notify the factory in the unlikely event you discover defects in workmanship. We appreciate hearing from you and will correct immediately. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information.
Table of Contents Contents Chapter 1 Safety .....................................................................................................................................................4 Safety Guidelines ...................................................................................................................................4 Safety Instructions ..................................................................................................................................
1. Safety Safety Guidelines This manual contains information that is important for you, the owner/operator, to know and understand. This information relates to protecting personal safety and preventing equipment problems. It is the responsibility of the owner/operator to inform anyone operating or working in the area of this equipment of these safety guidelines. To help you recognize this information, we use the symbols that are defined below. Please read the manual and pay attention to these sections.
1. Safety Safety Instructions Our foremost concern is your safety and the safety of others associated with this equipment. We want to keep you as a customer. This manual is to help you understand safe operating procedures and some problems that may be encountered by the operator and other personnel. As owner and/or operator, it is your responsibility to know what requirements, hazards, and precautions exist, and to inform all personnel associated with the equipment or in the area.
1. Safety Unpacking When receiving the unit, inspect carefully for any damage that may have occurred during transit. Shipping damage claim must be filed with carrier. Electrical Safety An adequate and safe power supply to the APP Fan unit is essential for safety. A competent and qualified electrician must undertake all electrical wiring. All wiring is to be installed according to the National Standards and Regulations relevant to your Country and Region.
2. Decals Safety Signs and Warnings The following pages show you exactly where the safety signs and warnings (decals) should be placed on your APP Fan. If a decal is missing, damaged or unreadable, please contact your dealer or AP/Cumberland for a free replacement. WARNING SHEAR POINT DANGER Keep hands clear of moving parts. Do not operate with guard removed. Disconnect and lockout power before servicing. WARNING STAY CLEAR OF ROTATING BLADE Blade may start automatically. May cause serious injury.
2. Decals DANGER WARNING STAY CLEAR OF ROTATING BLADE Blade may start automatically. May cause serious injury. Disconnect and lockout power sources before servicing. HIGH VOLTAGE Will cause serious injury or death. Lockout power before servicing. The GSI Group 217-226-4421 WARNING FLYING OBJECTS HAZARD Danger of eye injury. Wear eye protection. DC-1540 Left side DANGER WARNING STAY CLEAR OF ROTATING BLADE Blade may start automatically. May cause serious injury.
3. Installation Fans should be installed in an exterior wall located where there will be no obstructions to the flow of air into or out of the fan. Once a location has been determined, an opening should be made in the wall and framed to provide enough clearance around the fan housing. (See rough opening chart on Page 10.) Framing must be able to support the weight of the fan assembly. Manual handling of the fans may result in serious injury.
4. Operation Fan Model Width (in.) Inside Height (in.) Outside Height (in.) (B) 4" Wall (A) 6" Wall (A) 8" Wall (A) APP-12* 17 17-1/2 16-1/2 16 15-1/2 APP-14* 20 20 19-1/4 18-7/8 18-1/2 APP-18* 25-1/2 26 25 24-1/2 24 APP-24* 34-1/2 34-1/2 33-1/2 33 32-1/2 APP-36* 44-1/2 44-1/2 43-1/2 43 42-1/2 APPB-36* 44-1/2 44-1/2 43-1/2 43 42-1/2 APPB-50* 56 56 55 54-1/2 54 * Add - BLK suffix to end of fan model for black fans.
5. Maintenance Cleaning It is advisable to clean blade and shutter at regular intervals. This will remove any accumulated dirt, which would cause fan blade to become unbalanced and result in excessive vibration and poor performance. Lubrication Motor is pre-lubricated at factory and will not require any further lubrication.
6. Wiring Electrical Wiring All wiring should be installed in accordance with National, State and Local electrical codes. Fans used to ventilate livestock buildings or other rooms where continuous air movement is essential should be connected to individual electrical circuits, with a minimum of two (2) circuits per room. We strongly recommend the installation of supplementary natural ventilation as well as a back-up thermostat and an alarm system on at least one cooling stage.
6. Wiring Figure 6C Motor overload protection should be provided for each fan. A circuit breaker switch or slow blow motor type fuses must be used. NOTE: A safety cut-off switch should be located adjacent to each fan, such as “AP” #’s: E100-A1063 - 2-1/2 Amp E100-A1064 - 5.0 Amp E100-A1065 - 8.0 Amp E100-A1066 - 15.0 Amp Figure 6D Back-up thermostats such as the TH-1, should always be used in conjunction with the control system.
6. Wiring Figure 6E Propeller speeds for APP Fans stated in the table are the maximum permissible speeds. Exceeding these may result in damage to the fan and serious injury to the operator. CFM ratings listed below were all taken at 0.05 static pressure. Performer series fans use TEAO (Totally Enclosed Air Over) motors. Performer series fans use TEAO (Totally Enclosed Air Over) motors that require the air movement created by the fan to cool the motor as it passes over the motor housing.
6. Wiring APP-14F* Speed Curve #7 Volts RPM CFM without Cone CFM with Cone 230 1765 2367 2631 151 1675 2230 2487 145 1575 2100 2292 144 1475 1953 2130 143 1375 1808 2018 142 1275 1659 1813 140 1175 1471 1581 139 1075 1242 1487 137 975 1044 1280 135 875 854 1023 131 775 558 489 130 675 290 263 121 575 167 160 * Add - BLK suffix to end of fan model for black fans.
6. Wiring APP-24F* Speed Curve #4 Volts RPM CFM without Cone CFM with Cone 230 1040 5798 7386 194 940 5160 6353 176 840 4784 5648 157 740 3830 4688 143 640 2875 3842 130 540 2072 2902 115 440 823 1596 103 340 368 331 * Add - BLK suffix to end of fan model for black fans.
7. Dimension Chart Figure 7A Fan Model “A” “B” “C” APP-12F* 25-5/8" N/A 12-1/2" APP-14F* 21" N/A 15-1/2" APP-14FC* 40" 20-5/8" 20-5/8" APP-18F* 22-3/16" N/A 20" APP-18FC* 40" 22" 25-3/8" APP-24F* 22" N/A 26" APP-24FC* 41" 23-3/8" 31-7/8" APP-36F/APPB-36F* 30-1/4" N/A 37-7/8" APP-36FC/APPB-36FC* 54-1/2" 27" 44-3/8" APPB-50* 34-1/4" N/A 50-3/8" APPB-50C* 55" 24" 56-3/8" * Add - BLK suffix to end of fan model for black fans.
8.
8.
9. 50" Cone Assembly Figure 9A NOTE: Fan must be installed in the wall before proceeding with discharge cone installation. Remove packaging from cone and guard sections.
9. 50" Cone Assembly Cone Assembly Detail See cone assembly detail in Figure 9B below. Partially assemble the cone on the ground by using only the outermost two (2) holes per overlap (six (6) total). Use the 1" bolts, fender washers and flange nuts, leaving bolts loose. Figure 9B Cone Mounting Detail See cone mounting detail in Figure 9C below. Place the cone on the fan leaving a 2" overlap. Mark the nine (9) holes around fan orifice. Remove cone and drill 7/16" holes where marked.
9. 50" Cone Assembly Guard Detail See guard detail in Figure 9D below for appropriate eyelets to be used with fiberglass fans. Push guard into fan until eyelets contact the center of each cone panel. Mark and drill three (3) 7/16" holes in the center of each cone panel. Use 1-1/2" bolts, fender washers and flange nuts to mount guard. Tighten hardware evenly.
10. Warranty GSI Group, LLC Limited Warranty The GSI Group, LLC (“GSI”) warrants products which it manufactures to be free of defects in materials and workmanship under normal usage and conditions for a period of 12 months after sale to the original end-user or if a foreign sale, 14 months from arrival at port of discharge, whichever is earlier.
This equipment shall be installed in accordance with the current installation codes and applicable regulations, which should be carefully followed in all cases. Authorities having jurisdiction should be consulted before installations are made. 1004 E. Illinois St. Assumption, IL 62510-0020 Phone: 1-217-226-4421 Fax: 1-217-226-4420 www.gsiag.com AP/Cumberland is a part of GSI, a worldwide brand of AGCO Corporation.