Commercial generator set
Quiet Diesel
TM
Series
QD 6000/7500/8000
Features and benefits
Weight, size and sound level
Dramatically lower noise, vibration, harshness (NVH)
Up to 15 dB(A) quieter than conventional diesel
generator sets
Load-matching, variable speed operation
Enclosed muffler for added quietness, easy
installation
Automatic glow plug eliminates preheat time
uncertainty
Self-diagnostic capability simplifies troubleshooting
Pure sine wave output for high quality power
Convenient, top-mounted switches and coolant level
check/fills
Complete, integrated package for easy, low-cost
installation
Service and maintenance points accessible through
easy-latch side service door
Weight: 420 lbs (190.9 kg), wet
Size: Length 36.35 in (923.2 mm), width 24.23 in (615.4
mm), height 22.28 in (565.9 mm)
Sound: Before installation
6000:
- 64 dB(A) at 10 ft (3 m), no load
- 65 dB(A) at 10 ft (3 m), 1/2 load
- 69 dB(A) at 10 ft (3 m), full load
7500:
- 64 dB(A) at 10 ft (3 m), no load
- 66 dB(A) at 10 ft (3 m), 1/2 load
- 71 dB(A) at 10 ft (3 m), full load
8000:
- 64 dB(A) at 10 ft (3 m), no load
- 66 dB(A) at 10 ft (3 m), 1/2 load
- 72 dB(A) at 10 ft (3 m), full load
Models and ratings
Model Fan Hz Watts Voltage Amps PF Phase Circuit breaker
6 HDKAV/41934
Internal 60 6000 120 50 1.0 1 (1) 2-pole, 30 A
7.5 HDKAT/41934
Internal 60 7500 120 62.5 1.0 1 (1) 2-pole, 35 A
8 HDKAU/41934
Internal 60 8000 120 66.6 1.0 1 (1) 2-pole, 35 A
- Ratings apply up to 500 ft (152.4 m) altitude, 85
°
F (29
°
C) ambient* with No. 2 diesel fuel.
- Maximum power capability decreases 3.5% for each 1000 ft (305 m) above 500 ft (152.4 m) and 1% for each 10 °F (5.5 °C) increase in
ambient* temperature above 85 °F (29 °C).
- Ratings are at intermittent power output.
* Ambient is defined as the air temperature measured at the cooling air inlet to the set.