3. Pre-Installation Considerations 2-2016
22 A045R241 (Issue 7)Copyright © 2016 Cummins Inc.
◦ DC control or AC sense wires 1000-2000 feet circuit length => 16-14 AWG
of the insulation type below
• All AC and DC wires and cables shall be rated 75 °C minimum, stranded
copper, and rated for wet locations.
◦ For wire sizes 14 AWG and larger, use insulation types including but not
limited to: RHW, RHW-2, THHW, THW, THW-2, THWN, THWN-2, XHHW,
XHHW-2, USE-2, ZW-2
◦ For wire sizes 16 and 18 AWG, use insulation types including but not
limited to: FFH-2, KFF-2, PAFF, PFF, PGFF, PTFF, RFH-2, RFHH-2,
RFHH-3, SFF-2, TFF, TFFN, ZFF
• Code compliant 20 A, 120 VAC, GFCI protected circuit for alternator heaters,
battery charger, coolant heater, oil heater, and/or battery heater (if equipped)
• Code compliant conduit for all wires
Mounting Materials:
• Four base tie-down bolts
NOTICE
Seismic zone installations require compliance to specific mounting
configurations.
Fuel Materials:
• Flexible fuel line (provided with generator)
• UL listed pipe thread sealant
• Fuel line (natural gas and propane: 6 - 12 inch water column [1.5 - 3.0 kPa] fuel
pressure) at generator set
• Fuel pressure regulator (as required)
• Manual fuel shut-off at generator set ahead of automatic valves on generator
set fuel system
Loose Parts Shipped with the Generator Set
The following loose parts are shipped with the generator set:
• Two enclosure keys
• Generator set mounting spacers
• Circuit breaker cover and screw
• Chassis plugs
• Terminal block jumper
• Literature (Operator Manual, Quick Start Operator Guide, Installation Manual,
Quick Start Installation Guide, Health and Safety Manual, and Warranty
Statements)