DC control or AC sense wires 1000-2000 feet circuit length => 16-14 AWG
of the insulation type below
All AC and DC wires and cables shall be rated 75 °C minimum, stranded
copper, and rated for wet locations.
For wire sizes 14 AWG and larger, use insulation types including but not
limited to: RHW, RHW-2, THHW, THW, THW-2, THWN, THWN-2, XHHW,
XHHW-2, USE-2, ZW-2
For wire sizes 16 and 18 AWG, use insulation types including but not
limited to: FFH-2, KFF-2, PAFF, PFF, PGFF, PTFF, RFH-2, RFHH-2,
RFHH-3, SFF-2, TFF, TFFN, ZFF
Code compliant 20 A, 120 VAC, GFCI protected circuit for alternator heaters,
battery charger, coolant heater, oil heater, and/or battery heater (if equipped)
Code compliant conduit for all wires
Mounting Materials:
Four base tie-down bolts
NOTICE
Seismic zone installations require compliance to specific mounting
configurations.
Fuel Materials:
Flexible fuel line (provided with generator)
UL listed pipe thread sealant
Fuel line (natural gas and propane: 6 - 12 inch water column [1.5 - 3.0 kPa] fuel
pressure) at generator set
Fuel pressure regulator (as required)
Manual fuel shut-off at generator set ahead of automatic valves on generator
set fuel system
Loose Parts Shipped with the Generator Set
The following loose parts are shipped with the generator set:
Two enclosure keys
Generator set mounting spacers
Circuit breaker cover and screw
Chassis plugs
Terminal block jumper
Literature (Operator Manual, Quick Start Operator Guide, Installation Manual,
Quick Start Installation Guide, Health and Safety Manual, and Warranty
Statements)