Install Manual

4. Installation 2-2016
26 A045R241 (Issue 7)Copyright © 2016 Cummins Inc.
No. Description No. Description
1 Cool Air In 2 Hot Air Out
FIGURE 3. GENERATOR SET LOCATION
Generator set location is critical for safety and performance. Follow the guidelines
below:
Must comply with applicable codes (NFPA, NEC, IBC, etc.).
Install outdoors only. For other applications, contact your local Cummins dealer
or reference the Application Manual at the following link:
http://www.cumminspower.com/www/literature/applicationmanuals/t030.pdf
Consider access to utilities (electric/gas meters, transfer switch, remote fuel
tank location, etc.).
Call the local utilities to mark the locations of buried utility services (gas,
electric, or telephone) before digging.
Verify the locations of any other buried components (gas, electric or telephone)
with the homeowner before digging.
Clearances:
The exhaust side of the generator set must be located 5 feet from combustible
materials (NFPA 37).
The exhaust side of the generator must be located 5 feet from any opening in a
wall (window, door, vent, etc.).
The generator must be located such that the exhaust is not able to accumulate
in an occupied area.
The generator must have enough room for installation, service, and
maintenance.
The generator must be located to ensure ventilation openings are not blocked.