Position the generator set so that cooling air is free to enter and leave the area.
Locate and position the generator set so that prevailing winds carry exhaust
gases and potential fuel leaks away from the house or occupied area.
No. Description
1 5 ft Clearance (Shaded Area)
FIGURE 4. CLEARANCES
Laying the Foundation
When laying the foundation:
1. Clear obstructions, and make sure that there is adequate clearance for access.
2. Level the ground, and make sure that the ground is compact and settled.
Ensure that it is stable ground, not subject to flooding.
3. Prepare the concrete pad.
The pad should be constructed of reinforced concrete with a 28-day
compressive strength of at least 2500 psi (17,237 kPa).
The pad should be at least 5 inches (127 mm) deep and extend at least 6
inches (150 mm) beyond the skid on all sides.
NOTICE
Seismic installation may require a different pad and securing
devices.
NOTICE
Local codes and standards may have different requirements.