4. Installation 2-2016
28 A045R241 (Issue 7)Copyright © 2016 Cummins Inc.
4. Lift the generator set onto the pad, and secure it.
No. Description No. Description
1 Pad Thickness (Minimum 5 in) 5 Accessory 120 VAC, 20A Max Wire
Stub-Up
2 Pad Width (Must Extend Minimum 6 in
Beyond Skid)
6 Circuit Breaker 2 Stub-Up (Dual Circuit
Breaker)
3 Pad Length (Must Extend Minimum 6
in Beyond Skid)
7 Circuit Breaker 1 Stub-Up (Standard)
4 Generator Set Control Wire Stub-Up
(DC)
FIGURE 5. CONCRETE PAD PREPARATION
Lifting and Moving the Generator Set
WARNING
Heavy Load
The generator set is heavy. Handle with care.
Use appropriate lifting techniques to move the generator set. Do not use the
lifting eyes on the engine and alternator to lift the entire generator set.
Dropping the generator set can cause severe personal injury or death. Keep
feet and hands clear when lifting the generator set.