Install Manual

4. Installation2-2016
47A045R241 (Issue 7) Copyright © 2016 Cummins Inc.
figure below for available drilling space for conduit holes in the side of the chassis.
Holes up to 3 (7.6 cm) inches in diameter can be made in the chassis in the areas
shown. Exceeding 3 (7.6 cm) inches in diameter may cause failure of the chassis.
Comply with NEC and local codes and standards for installation of wires for
electrical circuits. Refer to NEC standards for required wire bend radius and
ampacity of load leads.
No. Description No. Description
1 Circuit Breaker Side (shaded areas) 3 Drilling Allowed (shaded sections)
2 DC (left) and AC (right) Connection
Area (shaded areas)
FIGURE 15. DRILLING LOCATIONS FOR SIDE ELECTRICAL CONNECTIONS