Install Manual

5. Startup and Configuration 2-2016
64 A045R241 (Issue 7)Copyright © 2016 Cummins Inc.
Tick Item
All load, line and generator connections are well made and correct.
Generator Set Pre-Start
A safety check was performed just before starting.
The generator set engine is properly serviced with oil and coolant.
The battery is properly installed, serviced and charged.
The battery charger and engine coolant heater are connected and operational, if
applicable.
All generator set covers and safety shields are installed correctly.
The fuel supply is turned on.
All fuel shutoff valves are operational.
The date and time have been set in the generator set control.
The generator set operating mode has been selected.
5.6 Startup
WARNING
Automatic startup of the generator set during installation can cause severe
personal injury or death. Push the control switch OFF and disconnect the
negative (–) cable from the battery to keep the generator set from starting.
After verifying that the installation was completed correctly, start and test the
system. Make sure to connect the battery cables to the battery with the positive (+)
cable first.
Read through the Operator Manual and perform the maintenance and pre-start
checks as instructed. The generator set is shipped from the factory with the proper
level of engine oil and coolant, but should be checked before it is started. Start and
operate the generator set following all the instructions and precautions in the
Operator Manual. Ensure that the bonding bolts are installed into the service panels
before leaving the site.
NOTICE
Before leaving the site, if the generator set is ready to be placed in service,
set the control switch to the AUTO position to provide automatic standby
power.
NOTICE
Contact your local Cummins service representative if you encounter a fault
code.