Spec Sheet

©2015 Cummins Inc. | NAS-5777d-EN (4/15)
power.cummins.com
Product features
Engine
Natural gas/propane 1800 rpm engine
Engine air cleaner – normal duty
Electronic governor, isochronous
Engine starter, 12 VDC motor
Shutdown – low oil pressure
Extension – oil drain
Engine oil
Fuel System
Single fuel – natural gas or propane vapor, field
selectable
Alternator
60 Hz, 1 phase, 4 lead, or 3 phase, 12 lead, 120
o
C
temperature rise at 40
o
C ambient
Exciter/voltage regulator – torque match
Control
PowerCommand 1.1
Display language – English
Control mounting, right facing
Electrical
Single circuit breaker, UL certified, right-side mounted
Battery charging alternator, normal duty
Battery charger – 6 Amp, regulated
Cooling
Generator set cooling capability – 50
o
C
Shutdown – low coolant level
Engine coolant – 50/50 mixture
Extension – coolant drain
Enclosure
Aluminum enclosure Sound Level 1 with muffler
installed, sandstone color
Wind rating – 180 MPH
Code compliance
UL 2200
EPA emissions, emergency, stationary, 40CFR60
IBC Seismic
NFPA110 capable
Generator set application
Coolant heater
Crank case vent heater
Large battery rack
Flexible fuel line
Literature (English) – operator’s manual, installation
quick guide and manual, service manual
Warranty
Base warranty – 2 year standby
Extended warranties available
Packaging
Shipping pallet, poly bag
Generator set performance
Governor regulation class:
ISO 8528 Part 1 Class G2
Voltage regulation, no load to full load:
±1.0%
Random voltage variation:
±1.0%
Frequency regulation:
Isochronous
Random frequency variation:
± 0.75% @ 60 Hz
Radio frequency emissions compliance:
FCC code
Title 47 part 15 Class B
Engine
Design: Turbo with after cooler
Bore:
86.5 mm (3.4 in)
Stroke:
100.0 mm (3.94 in)
Displacement:
2.4 liters (143.5 in
3
)
Cylinder block:
Cast iron, in-line 4 cylinder
Battery capacity:
550 amps at ambient temperature of
0
o
F to 32
o
F (-18
o
C to 0
o
C)
Battery charging alternator:
50 amps
Starting voltage:
12 volt, negative ground
Lube oil filter type(s):
Spin-on with relief valve
Standard cooling system:
50
o
C (122
o
F) ambient
cooling system
Rated speed: 1800 rpm
Fuel supply pressure
Minimum fuel supply pressure, kPa
(in H
2
O): 1.5 (6.0)
Maximum fuel supply pressure, kPa
(in H
2
O): 3.5 (14.0)
Control system
The PowerCommand® electronic control is standard
equipment and provides total generator set system
integration including automatic remote starting/stopping,
precise frequency and voltage regulation, alarm and
status message display, output metering, auto-shutdown
at fault detection and NFPA 110 Level 1 compliance.
Sound attenuated enclosure
The aesthetically appealing enclosure incorporates
special designs that deliver the quietest generator of its
kind. Aluminum material plus durable powder coat paint
provides the best anti-corrosion performance. The
generator set enclosure has been evaluated to withstand
180 MPH wind loads in accordance with ASCE7-10. The
intelligent design has removable panels and service doors
to provide easy access for service and maintenance.