Product Manual
Table Of Contents
- Table of Contents
- 1. Important Safety Instructions
- 1.1 Warning, Caution, and Note Styles Used in This Manual
- 1.2 General Information
- 1.3 General Safety Precautions
- 1.4 Generator Set Safety Code
- 1.5 Batteries Can Explode
- 1.6 Electrical Shocks and Arc Flashes Can Cause Severe Personal Injury or Death
- 1.7 Fuel and Fumes Are Flammable
- 1.8 Exhaust Gases Are Deadly
- 1.9 The Hazards of Carbon Monoxide
- 1.10 Earth Ground Connection
- 2. Introduction
- 3. Control System
- 4. Operation - PowerCommand 1.1
- 5. Maintenance
- 6. Troubleshooting
- 6.1 Engine Is Difficult to Start or Does Not Start
- 6.2 Code 143 - Engine Oil Pressure Low (Warning)
- 6.3 Code 151 - Engine Coolant Temperature High (Shutdown)
- 6.4 Code 155 - Intake Manifold Temperature High (Shutdown)
- 6.5 Code 197 - Coolant Level Low (Warning)
- 6.6 Code 415 - Engine Oil Pressure Low (Shutdown)
- 6.7 Code 421 - Engine Oil Temperature High (Warning)
- 6.8 Code 441 - Battery Voltage Low (Warning)
- 6.9 Code 488 - Intake Manifold Temperature High (Warning)
- 6.10 Code 1438 - Fail to Crank (Shutdown)
- 6.11 Code 1472 - High AC Current (Shutdown)
- 6.12 Code 5134 - Unknown Shutdown at Idle
- 7. Manufacturing Facilities
3. Control System 2-2016
48 A045R242 (Issue 7)Copyright © 2016 Cummins Inc.
Off Mode
When in Off mode, the control does not allow the generator set to start. If the
generator set is already running and the control is set to Off, it initiates a normal
shutdown sequence.
Manual Run Mode
When in Manual Run mode, the generator set starts and continues to run until the
control is put into the Off mode. While in Manual Run mode, the remote start signal
is ignored.
Auto Mode
When in Auto mode, the control allows the generator set to be started with a remote
start signal only.
When in Auto mode, the generator set can start at any time. When a remote start
signal is received, the genset starts after a time delay preheat (if programmed) and
time delay start (if programmed) is completed.
If the generator set is running in Auto mode and the Off button is pressed, the
control immediately stops the genset and the control transitions to the Off mode.
When all remote start signals are removed, the control performs a normal shutdown
sequence which may include a time delay stop.